Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-03 Cont ID  
Sent By albarran Date 2015-12-03 Time 13:06 Rev Time 0.00
Received By albarran Date 2015-12-03 Time 10:43 Sent To I
Notes
2015-12-03 13:07:27APPROVED WITH THE FOLLOWING EXCEPTION: ELECTRICAL
 PROVISO TO PERMIT 15090563
  
 PER NEC 250.140 THE DRYER PLUG SHALL BE A 4 WIRE
 CONFIGURATION. EXAMPLE NEMA 14-30
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 11:18 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 09:53 Sent To I
Notes
2015-11-24 11:22:41THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. THE LOAD INDICATED FOR PANEL "A" INCLUDES A 20 AMP
 SINGLE POLE CIRCUIT FOR A 1.8 KVA CLOTHES DRYER. IF
 THIS DRYER IS GAS INDICATE THIS ON THE DRAWINGS
 OTHERWISE PROVIDE MANUFACTURER SPEC SHEET FOR THIS
 APPLIANCE OR REVISE THE LOAD CALCS ACCORDINGLY.
 2. NEC 300.9, YOUR WIRING SCHEDULE REFLECTS THHN
 INSULATION FOR THE FEEDERS. THIS INSULATION IS NOT
 LISTED FOR WET LOCATIONS. REVISE THE SCHEDULE
 ACCORDINGLY.
 3. FBC-E C405 HAS MANDATORY SWITCHING REQUIREMENTS.
 REVISE YOUR DRAWINGS TO COMPLY.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-13 Cont ID  
Sent By albarran Date 2015-10-13 Time 17:54 Rev Time 0.00
Received By albarran Date 2015-10-13 Time 17:16 Sent To I
Notes
2015-10-13 17:55:44PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET ADJACENT
 TO EVERY PEDESTRIAN DOOR IN EVERY COMMERCIAL
 ESTABLISHMENT.
 2. NEC 210.62 REQUIRES THAT THERE BE A SHOW WINDOW
 OUTLET FOR EVERY 12 LINEAR FEET OF SHOW WINDOW
 (STOREFRONT) OR PORTION THEREOF. THIS OUTLET SHALL BE
 NO MORE THAN 18? ABOVE OR AWAY FROM THE TOP OF THE SHOW
 WINDOW.
 3. NEC 422.52 REQUIRES THAT THE ELECTRICAL OUTLET FOR
 THE DRINKING FOUNTAIN BE PROTECTED WITH GFCI.
 4. NEC 215.5 REQUIRES A SITE SPECIFIC RISER DIAGRAM
 INCLUDING THE TOTAL CALCULATED LOADS BEFORE AND AFTER
 AND DEMAND FACTORS. CONDUCTOR SIZING SHALL ALSO BE
 INCLUDED. (THIS SHALL INCLUDE EVERY PANELBOARD WITHIN
 THE SCOPE OF THIS PERMIT).
 5. NEC 408.4(A) REQUIRES THAT YOU SUBMIT A CIRCUIT
 DIRECTORY FOR EVERY PANELBOARD.
 6. NEC 408.4(B) REQUIRES THAT ALL PANELS BE MARKED TO
 INDICATE THE LOCATION OF THE SOURCE
 7. FBC-B SECTION 1006 HAS SPECIFIC EMERGENCY LIGHTING
 REQUIREMENTS WHICH DO NOT APPEAR TO HAVE BEEN MET.
 REVISE YOUR EMERGENCY LIGHTING DETAIL/LAYOUT
 ACCORDINGLY.
 8. FBC-E SECTION C405 HAS MANDATORY LIGHTING
 REQUIREMENTS FOR COMMERCIAL ESTABLISHMENTS WHICH HAVE
 TO BE COMPLIED WITH.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-16 Cont ID  
Sent By pleduc Date 2015-11-16 Time   Rev Time 0.00
Received By pleduc Date 2015-11-16 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-16 Cont ID  
Sent By pleduc Date 2015-09-16 Time   Rev Time 0.00
Received By pleduc Date 2015-09-16 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-03 Cont ID  
Sent By albarran Date 2015-12-03 Time 13:09 Rev Time 0.00
Received By albarran Date 2015-12-01 Time 14:59 Sent To  
Notes
2015-12-03 13:12:2412/3/15 PASSED ELECTRICAL REVIEW AND IS READY FOR
 ISSUANCE. NOTIFIED KIM OF BSA VIA PHONE. SENT TO SMALL
 READY BIN "B". MA
2015-12-01 14:59:44RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 11:29 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 09:19 Sent To  
Notes
2015-11-24 11:29:5011/24/15 FAILED ELECTRICAL REVIEW AS NOTED. IN LIEU OF
 EMAIL, CONTRACTOR WAS NOTIFIED VIA EMAIL. SENT TO LARGE
 DENIED BIN "B". MA
2015-11-05 09:19:33B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-13 Cont ID  
Sent By albarran Date 2015-10-13 Time 17:56 Rev Time 0.00
Received By albarran Date 2015-09-14 Time 13:41 Sent To  
Notes
2015-10-13 17:58:1510/13/15 FAILED ELECTRICAL REVIEW. FOR LACK OF EMAIL
 INFORMATION, KIM WAS CONTACTED VIA PHONE CALL AT
 561-272-6350. SENT TO SMALL DENIED BIN "B". MA
2015-09-14 13:41:21B05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 14:25 Rev Time 0.00
Received By ccole Date 2015-11-13 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-23 Cont ID  
Sent By ccole Date 2015-09-23 Time 11:52 Rev Time 0.00
Received By ccole Date 2015-09-23 Time 11:52 Sent To  
Notes
2015-09-23 12:15:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090563
 09/23/15
  
 1) THE NEW DRYER AND DRYER VENTING SHALL BE IN
 COMPLIANCE WITH SECTION 504 FBC-14 MECHANICAL. PLEASE
 REVISE THE DRAWINGS IN ACCORDANCE WITH THE FOLOWING
 CODE COMPLIANCES.
 504.1 INSTALLATION.
 CLOTHES DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTRUCTIONS. DRYER EXHAUST SYSTEMS
 SHALL BE INDEPENDENT OF ALL OTHER SYSTEMS AND SHALL
 CONVEY THE MOISTURE AND ANY PRODUCTS OF COMBUSTION TO
 THE OUTSIDE OF THE BUILDING.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO LISTED AND
 LABELED CONDENSING (DUCTLESS) CLOTHES DRYERS.
 504.2 EXHAUST PENETRATIONS.
 WHERE A CLOTHES DRYER EXHAUST DUCT PENETRATES A WALL OR
 CEILING MEMBRANE, THE ANNULAR SPACE SHALL BE SEALED
 WITH NONCOMBUSTIBLE MATERIAL, APPROVED FIRE CAULKING OR
 A NONCOMBUSTIBLE DRYER EXHAUST DUCT WALL RECEPTACLE.
 DUCTS THAT EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE
 OR BE LOCATED WITHIN ANY FIREBLOCKING, DRAFTSTOPPING OR
 ANY WALL, FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY
 THE FLORIDA BUILDING CODE, BUILDING TO BE
 FIRE-RESISTANCE RATED, UNLESS SUCH DUCT IS CONSTRUCTED
 OF GALVANIZED STEEL OR ALUMINUM OF THE THICKNESS
 SPECIFIED IN SECTION 603.4 AND THE FIRE-RESISTANCE
 RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FIRE DAMPERS, COMBINATION
 FIRE/SMOKE DAMPERS AND ANY SIMILAR DEVICES THAT WILL
 OBSTRUCT THE EXHAUST FLOW SHALL BE PROHIBITED IN
 CLOTHES DRYER EXHAUST DUCTS.
 504.3 CLEANOUT.
 EACH VERTICAL RISER SHALL BE PROVIDED WITH A MEANS FOR
 CLEANOUT.
 504.4 EXHAUST INSTALLATION.
 DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE
 ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION. DUCTS SHALL NOT BE CONNECTED
 OR INSTALLED WITH SHEET METAL SCREWS OR OTHER FASTENERS
 THAT WILL OBSTRUCT THE EXHAUST FLOW. CLOTHES DRYER
 EXHAUST DUCTS SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, VENT OR CHIMNEY. CLOTHES DRYER EXHAUST DUCTS
 SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS.
 504.5 MAKEUP AIR.
 INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09M3/S)
 SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS
 DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN
 OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE
 INCHES (0.0645 M2) SHALL BE PROVIDED IN THE CLOSET
 ENCLOSURE OR MAKEUP AIR SHALL BE PROVIDED BY OTHER
 APPROVED MEANS.
 504.6 DOMESTIC CLOTHES DRYER DUCTS.
 EXHAUST DUCTS FOR DOMESTIC CLOTHES DRYERS SHALL CONFORM
 TO THE REQUIREMENTS OF SECTIONS 504.6.1 THROUGH
 504.6.7.
 504.6.1 MATERIAL AND SIZE.
 EXHAUST DUCTS SHALL HAVE A SMOOTH INTERIOR FINISH AND
 SHALL BE CONSTRUCTED OF METAL A MINIMUM 0.016 INCH (0.4
 MM) THICK. THE EXHAUST DUCT SIZE SHALL BE 4 INCHES (102
 MM) NOMINAL IN DIAMETER.
 504.6.2 DUCT INSTALLATION.
 EXHAUST DUCTS SHALL BE SUPPORTED AT 4-FOOT (1219 MM)
 INTERVALS AND SECURED IN PLACE. THE INSERT END OF THE
 DUCT SHALL EXTEND INTO THE ADJOINING DUCT OR FITTING IN
 THE DIRECTION OF AIRFLOW. DUCTS SHALL NOT BE JOINED
 WITH SCREWS OR SIMILAR FASTENERS THAT PROTRUDE INTO THE
 INSIDE OF THE DUCT.
 504.6.3 TRANSITION DUCTS.
 TRANSITION DUCTS USED TO CONNECT THE DRYER TO THE
 EXHAUST DUCT SYSTEM SHALL BE A SINGLE LENGTH THAT IS
 LISTED AND LABELED IN ACCORDANCE WITH UL 2158A.
 TRANSITION DUCTS SHALL BE A MAXIMUM OF 8 FEET (2438 MM)
 IN LENGTH AND SHALL NOT BE CONCEALED WITHIN
 CONSTRUCTION.
 504.6.4 DUCT LENGTH.THE MAXIMUM ALLOWABLE EXHAUST DUCT
 LENGTH SHALL BE DETERMINED BY ONE OF THE METHODS
 SPECIFIED IN SECTION 504.6.4.1 OR 504.6.4.2.
 504.6.4.1 SPECIFIED LENGTH.
 THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE 35 FEET
 (10 668 MM) FROM THE CONNECTION TO THE TRANSITION DUCT
 FROM THE DRYER TO THE OUTLET TERMINAL. WHERE FITTINGS
 ARE USED, THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL
 BE REDUCED IN ACCORDANCE WITH TABLE 504.6.4.1.
 504.6.4.2 MANUFACTURER'S INSTRUCTIONS.
 THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE
 DETERMINED BY THE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE CODE OFFICIAL SHALL BE PROVIDED WITH
 A COPY OF THE INSTALLATION INSTRUCTIONS FOR THE MAKE
 AND MODEL OF THE DRYER. WHERE THE EXHAUST DUCT IS TO BE
 CONCEALED, THE INSTALLATION INSTRUCTIONS SHALL BE
 PROVIDED TO THE CODE OFFICIAL PRIOR TO THE CONCEALMENT
 INSPECTION. IN THE ABSENCE OF FITTING EQUIVALENT LENGTH
 CALCULATIONS FROM THE CLOTHES DRYER MANUFACTURER, TABLE
 504.6.4.1 SHALL BE USED.
 504.6.5 LENGTH IDENTIFICATION.
 WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING
 CONSTRUCTION, THE EQUIVALENT LENGTH OF THE EXHAUST DUCT
 SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE
 LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEET (1829 MM)
 OF THE EXHAUST DUCT CONNECTION.
 SEE TABLE 504.6.4.1 DRYER EXHAUST DUCT FITTING
 EQUIVALENT LENGTH
 DRYER EXHAUST DUCT FITTING TYPE EQUIVALENT LENGTH
 2) SHEET A002: NO AC RETURN GRILLS ARE SHOWN IN THE
 CEILING OF THE NEW COSTUME SHOP, AND NO SUPPLY
 DIFFUSERS OR RETURNS ARE SHOWN IN THE CEILINGS OF THE
 NEW BREAKROOM AND THE NEW LAUNDRY ROOM- BALANCED AIR IS
 REQUIRED IN ACCORDANCE WITH SECTION 601.5 FBC-14
 MECHANICAL.
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS FOR EACH ROOM AND
 SPACE. TO VERIFY COMPLIANCE WITH THIS SECTION, THE
 CALCULATIONS MUST INDICATE THE REQUIRED AMOUNT OF O/A
 CFM'S AND THE AMOUNT BEING PROVIDED, AND THE PLAN MUST
 SHOW THE AIRFLOW CFM'S AT EACH DIFFUSER AND RETURN
 GRILL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-10 Cont ID  
Sent By gjohnson Date 2015-11-10 Time 12:54 Rev Time 0.00
Received By gjohnson Date 2015-11-10 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 05:28 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 05:11 Sent To  
Notes
2015-10-02 05:23:391) SUBMIT A SANITARY AND WATER RISER FOR THE NEW
 PLUMBING WORK TO BE DONE FOR THE WASHER AND LAUNDRY
 SINK. THE WASHER STANDPIPE SHALL CONNECT TO A MINIMUM 3
 INCH STACK OR DRAIN PER FBC-PLUMBING SEC406.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  