Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By shill Date 2015-09-14 Time 14:18 Rev Time 0.00
Received By shill Date 2015-09-14 Time 14:18 Sent To  
Notes
2015-09-14 14:21:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 5TH EDITION 2014
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 DOCUMENTS SUBMITTED - ONE SET OF ASTM E 90 FOR QEP 6 MM
 CORK, QEP SPEC SHEET, BADGER CORK FLAME SPREAD TEST
  
 TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED.
  
  
 1. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 THE TEST REPORT IS FOR BADGER CORK. THE RELATIONSHIP
 BETWEEN BADGER CORK AND QEP IS NOT CLEAR. PROVIDE A
 COPY OF ASTM E 84 FOR QEP 6 MM CORK.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 18:27 Rev Time 0.00
Received By shill Date 2015-10-07 Time 08:54 Sent To  
Notes
2015-10-08 08:54:45RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-14 Cont ID  
Sent By shill Date 2015-09-14 Time 14:21 Rev Time 0.00
Received By shill Date 2015-09-11 Time 09:56 Sent To  
Notes
2015-09-14 09:56:46ROUTED TO BLDG <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved