Plan Review Details - Permit 15090401
Plan Review Stops For Permit 15090401
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2016-05-11 Cont ID  
Sent By rmcdouga Date 2016-05-11 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2016-05-11 Time 13:14 Sent To  
Notes
2016-05-11 13:14:42APPROVED WITH EXCEPTIONS.
  
 1) A SEPARATE PERMIT, APPLICATION AND REVIEW OF PLANS
 FOR THE FIRE SPRINKLER SYSTEM REQUIRED BY
 FBC903.2.11.3.1 ARE REQUIRED TO BE SUBMITTED AND
 APPROVED AT A LATER DATE PER YOUR REQUEST.
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 WRITING FOR THE SECTIONAL GARAGE DOORS, EXTERIOR DOORS
 AND WINDOWS, STRUCTURAL MULLIONS, ROOFING MATERIALS,
 ROOF TOP ATTIC VENTILATORS AND ANY OTHER PRODUCTS
 REGULATED BY DCA RULE 9N-3.
  
 3) SUBMIT A GEOTECHNICAL EVALUATION REPORT WITH THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL. THE
 ONES SUBMITTED HAVE COPIED SIGNATURES. FAC 61G15-23.002
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-03-23 Cont ID  
Sent By rmcdouga Date 2016-03-23 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2016-03-23 Time 10:25 Sent To  
Notes
2016-03-23 10:26:19CONTRACTOR SUBMITTED ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-03-21 Cont ID  
Sent By rmcdouga Date 2016-03-21 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2016-03-18 Time 17:01 Sent To  
Notes
2016-03-21 09:20:29THE ENERGY CALCULATIONS FOR THIS UNIT ARE MISSING FROM
 THE PERMIT PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-02-16 Cont ID  
Sent By rmcdouga Date 2016-02-16 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2016-02-16 Time 09:57 Sent To  
Notes
2016-02-16 09:57:41PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SURVEY SPECIFIES THE PROPERTY AS BEING IN FLOOD
 ZONE B WHEN IT IS ACTUALLY IN FLOOD ZONE C. IF NOT
 CORRECTED, THIS MAY RESULT IN THE HOMEOWNERS PAYING
 MORE FOR FLOOD INSURANCE.
 I DID NOT FIND THE NEW SURVEY THAT WAS REFERENCED IN
 YOUR RESPONSE LETTER IN THE RE-SUBMITTAL. TWO COPIES OF
 THE CORRECTED SURVEY ARE REQUIRED. BECAUSE THESE ARE
 FEE SIMPLE TOWNHOUSES, TWO SETS OF INDIVIDUAL SURVEYS
 FOR EACH LOT ARE REQUIRED FOR EACH UNIT.
  
 2) SHOW COMPLIANCE WITH FBC-R806.1 VENTILATION
 REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW. SUBMIT
 TWO COPIES OF THE PRODUCT APPROVALS AND MANUFACTURER'S
 SPECIFICATIONS FOR THE 18" DIAMETER INTAKE AND EXHAUST
 ATTIC VENTS ON THE ROOF. PROVIDE INFORMATION TO SHOW
 THAT THEY WILL PROVIDE THE REQUIRED ATTIC VENTILATION.
  
 3) THE PRODUCT APPROVALS WILL BE A PROVISO ITEM TO BE
 SUBMITTED FOR REVIEW AND APPROVAL AT A LATER DATE PRIOR
 TO INSTALLATION AS REQUESTED. FBC 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES (INCLUDING SECTIONAL GARAGE DOORS).
  
 4) THE ENERGY PERFORMANCE EVALUATION FORM CONTAINS
 ERRORS AND IS MISSING INFORMATION. THE FORMS REQUIRE
 THE SIGNATURE OF THE OWNER/AGENT. INDICATE THE CORRECT
 ADDRESS ON THE ENERGY FORM FOR THAT SPECIFIC UNIT.
  
 5) SHEETS 1, 2 AND 5 FROM FRANCIS ENGINEERING ( FIRE
 SPRINKLER PLANS? ) ARE MISSING. A SEPARATE PERMIT,
 APPLICATION AND REVIEW OF FIRE SPRINKLER PLANS ARE
 REQUIRED TO BE SUBMITTED AT A LATER DATE PER YOUR
 REQUEST.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-23 Cont ID  
Sent By rmcdouga Date 2015-12-23 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2015-12-23 Time 17:57 Sent To  
Notes
2015-12-23 17:57:48PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SURVEY SPECIFIES THE PROPERTY AS BEING IN FLOOD
 ZONE B WHEN IT IS ACTUALLY IN FLOOD ZONE C. IF NOT
 CORRECTED, THIS MAY RESULT IN THE HOMEOWNERS PAYING
 MORE FOR FLOOD INSURANCE.
 I DID NOT FIND THE NEW SURVEY THAT WAS REFERENCED IN
 YOUR RESPONSE LETTER IN THE RE-SUBMITTAL.
  
 2) SHOW COMPLIANCE WITH FBC-R806.1 VENTILATION
 REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW.
 VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF
 1/16 INCH MINIMUM AND 1/4 INCH MAXIMUM. VENTILATION
 OPENINGS HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH MINIMUM
 AND 1/4 INCH MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.1.8.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR. CALCULATIONS FOR THE REQUIRED AREA OF
 VENTILATION OPENINGS WERE ADDED TO THE PLANS. I DID NOT
 SEE THE LOCATIONS AND SIZES OF THE VENT OPENINGS SHOWN
 ON THE PLANS.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES (INCLUDING
 SECTIONAL GARAGE DOORS).
 THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL
 WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 4) THE ENERGY PERFORMANCE EVALUATION FORM CONTAINS
 ERRORS AND IS MISSING INFORMATION. THE FORMS REQUIRE
 THE SIGNATURE OF THE OWNER/AGENT. THE STREET IS LAKE
 AVE. AND NOT LAKE WORTH AVE. THE CITY IS WEST PALM
 BEACH AND NOT LANTANA. THE JURIDICTION NUMBER IS
 604700. THE UNITS DO NOT MEET THE CRITERIA IN FBC
 ENERGY CONSERVATION SECTION R405.7.4 TO USE THE CROSS
 VENTILATION OPTION CREDIT. THE FORMS SPECIFY AN
 UNVENTED ATTIC AND THE PLANS SHOW A VENTILATED ATTIC.
 THE FORMS SPECIFY A CONCRETE ROOF AND THE PLANS HAVE A
 PLYWOOD ROOF WITH ASPHALT ROOFING.
  
 5) ACCORDING TO THE DRAWING INDEX ON SHEET CV-1.0,
 SHEET A-6.0 IS MISSING. SHEETS 1, 2 AND 5 FROM FRANCIS
 ENGINEERING ( FIRE SPRINKLER PLANS? ) ARE ALSO MISSING.
  
 6) THE SIGNATURE OF THE STRUCTURAL ENGINEER APPEARS TO
 BE A FASCIMILE. FLORIDA STATUTES REQUIRE THAT ALL
 DRAWINGS AND DOCUMENTS FROM ENGINEERS, AS WELL AS,
 ARCHITECTS THAT ARE SUBMITTED FOR PUBLIC RECORD HAVE
 THEIR HANDWRITTEN SIGNATURES ON THEM IN ADDITION TO
 THEIR SEALS. FAC 61G15-23.002 AND 61G1-16.003
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By rmcdouga Date 2015-10-22 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2015-10-22 Time 10:14 Sent To  
Notes
2015-10-22 10:15:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS WILL NEED TO BE DIVIDED INTO TWO SEPARATE
 SUBMITTAL PACKAGES SUCH THAT ALL OF THE DRAWINGS AND
 CONSTRUCTION DOCUMENTS FOR THE 6 TOWNHOUSE UNIT A
 BUILDING ARE IN ONE AND THE DRAWINGS AND CONSTRUCTION
 DOCUMENTS FOR THE 8 TOWNHOUSE UNIT B BUILDING ARE IN
 THE OTHER. THIS WILL PROVIDE CLARIFICATION FOR RECORD
 MANAGEMENT AND HELP TO AVOID CONFUSION AND DELAYS IN
 THE FIELD DUE TO FAILED INSPECTIONS. FBC 107.2.1.4
  
 2) THE SURVEY SPECIFIES THE PROPERTY AS BEING IN FLOOD
 ZONE B WHEN IT IS ACTUALLY IN FLOOD ZONE C. IF NOT
 CORRECTED, THIS MAY RESULT IN THE HOMEOWNERS PAYING
 MORE FOR FLOOD INSURANCE.
  
 3) THE FLOOR PLANS AND ELEVATIONS SHOW THE ADJACENT
 INTERIOR UNITS WITH WINDOWS ON THE ZERO LOT LINE, WHICH
 IS NOT ALLOWED. FBC-R302.1
  
 4) THE NOTE STATING THAT THE WINDOWS IN THE SIDE WALL
 ARE ONLY ON THE END UNITS IS MISSING FROM SHEET A-1.7
  
 5) PROVIDE A DETAIL FOR THE 2 HOUR FIRE RATED COMMON
 WALL BETWEEN DWELLING UNITS AND DETACHED GARAGES THAT
 SHOWS COMPLIANCE WITH FBC-R302.2 TOWNHOUSES.
 EACH TOWNHOUSE SHALL BE CONSIDERED A SEPARATE BUILDING
 AND SHALL BE SEPARATED BY FIRE-RESISTANCE-RATED WALL
 ASSEMBLIES MEETING THE REQUIREMENTS OF SECTION R302.1
 FOR EXTERIOR WALLS. EXCEPTION: A COMMON 2-HOUR
 FIRE-RESISTANCE-RATED WALL ASSEMBLY TESTED IN
 ACCORDANCE WITH ASTM E 119 OR UL 263 IS PERMITTED FOR
 TOWNHOUSES IF SUCH WALLS DO NOT CONTAIN PLUMBING OR
 MECHANICAL EQUIPMENT, DUCTS OR VENTS IN THE CAVITY OF
 THE COMMON WALL, UNLESS SUCH MATERIALS AND METHODS OF
 PENETRATION COMPLY WITH SECTION R302.4. THE WALL SHALL
 BE RATED FOR FIRE EXPOSURE FROM BOTH SIDES AND SHALL
 EXTEND TO AND BE TIGHT AGAINST EXTERIOR WALLS AND THE
 UNDERSIDE OF THE ROOF SHEATHING. ELECTRICAL
 INSTALLATIONS SHALL BE INSTALLED IN ACCORDANCE WITH
 CHAPTER 34. PENETRATIONS OF ELECTRICAL OUTLET BOXES
 SHALL BE IN ACCORDANCE WITH SECTION R302.4.
  
 6) SHOW COMPLIANCE WITH R302.2.4 STRUCTURAL
 INDEPENDENCE. EACH INDIVIDUAL TOWNHOUSE SHALL BE
 STRUCTURALLY INDEPENDENT.
  
 7) SHOW COMPLIANCE WITH FBC-R302.2.2 PARAPETS.
 PARAPETS CONSTRUCTED IN ACCORDANCE WITH SECTION
 R302.2.3 SHALL BE CONSTRUCTED FOR TOWNHOUSES AS AN
 EXTENSION OF EXTERIOR WALLS OR COMMON WALLS IN
 ACCORDANCE WITH THE FOLLOWING:
 1. WHERE ROOF SURFACES ADJACENT TO THE WALL OR WALLS
 ARE AT THE SAME ELEVATION, THE PARAPET SHALL EXTEND NOT
 LESS THAN 30 INCHES ABOVE THE ROOF SURFACES.
 2. WHERE ROOF SURFACES ADJACENT TO THE WALL OR WALLS
 ARE AT DIFFERENT ELEVATIONS AND THE HIGHER ROOF IS NOT
 MORE THAN 30 INCHES ABOVE THE LOWER ROOF, THE PARAPET
 SHALL EXTEND NOT LESS THAN 30 INCHES ABOVE THE LOWER
 ROOF SURFACE.
 EXCEPTION: A PARAPET IS NOT REQUIRED IN THE TWO CASES
 ABOVE WHEN THE ROOF IS COVERED WITH A MINIMUM CLASS C
 ROOF COVERING, AND THE ROOF DECKING OR SHEATHING IS OF
 NONCOMBUSTIBLE MATERIALS OR APPROVED
 FIRE-RETARDANT-TREATED WOOD FOR A DISTANCE OF 4 FEET ON
 EACH SIDE OF THE WALL OR WALLS, OR ONE LAYER OF
 5/8-INCH TYPE X GYPSUM BOARD IS INSTALLED DIRECTLY
 BENEATH THE ROOF DECKING OR SHEATHING, SUPPORTED BY A
 MINIMUM OF NOMINAL 2-INCH LEDGERS ATTACHED TO THE SIDES
 OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM DISTANCE OF
 4 FEET ON EACH SIDE OF THE WALL OR WALLS AND THERE ARE
 NO OPENINGS OR PENETRATIONS IN THE ROOF WITHIN 4 FEET
 OF THE COMMON WALLS.
 3. A PARAPET IS NOT REQUIRED WHERE ROOF SURFACES
 ADJACENT TO THE WALL OR WALLS ARE AT DIFFERENT
 ELEVATIONS AND THE HIGHER ROOF IS MORE THAN 30 INCHES
 ABOVE THE LOWER ROOF. THE COMMON WALL CONSTRUCTION FROM
 THE LOWER ROOF TO THE UNDERSIDE OF THE HIGHER ROOF DECK
 SHALL HAVE NOT LESS THAN A 1-HOUR FIRE-RESISTANCE
 RATING. THE WALL SHALL BE RATED FOR EXPOSURE FROM BOTH
 SIDES.
  
 8) SHOW COMPLIANCE WITH FBC-R302.2.3 PARAPET
 CONSTRUCTION.
 PARAPETS SHALL HAVE THE SAME FIRE-RESISTANCE RATING AS
 THAT REQUIRED FOR THE SUPPORTING WALL OR WALLS. ON ANY
 SIDE ADJACENT TO A ROOF SURFACE, THE PARAPET SHALL HAVE
 NONCOMBUSTIBLE FACES FOR THE UPPERMOST 18 INCHES, TO
 INCLUDE COUNTERFLASHING AND COPING MATERIALS. WHERE THE
 ROOF SLOPES TOWARD A PARAPET AT SLOPES GREATER THAN 2
 UNITS VERTICAL IN 12 UNITS HORIZONTAL, THE PARAPET
 SHALL EXTEND TO THE SAME HEIGHT AS ANY PORTION OF THE
 ROOF WITHIN A DISTANCE OF 3 FEET, BUT IN NO CASE SHALL
 THE HEIGHT BE LESS THAN 30 INCHES.
  
 9) THERE IS A NOTE ON THE ROOF FRAMING PLANS FOR
 BUILDING A THAT STATES SEE DETAIL 10/S5 FOR PLYWOOD
 NAILING PATTERN. THERE IS NO DETAIL 10 ON SHEET S5. FBC
 107.2.1
  
 10) THERE IS A NOTE ON THE ROOF FRAMING PLANS FOR
 BUILDING B THAT STATES SEE DETAIL 1/S12 FOR PLYWOOD
 NAILING PATTERN. DETAIL 1 ON SHEET S12 DOES NOT PROVIDE
 THE PLYWOOD NAILING PATTERN. THE NAILING FOR THE ROOF
 SHEATHING IS SPECIFIED ON DETAIL 4 ON S15. FBC 107.2.1
  
 11) SHOW COMPLIANCE WITH FBC-R302.5.1 OPENING
 PROTECTION. OPENINGS BETWEEN THE GARAGE AND RESIDENCE
 SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN
 1-3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB-CORE
 STEEL DOORS NOT LESS THAN 1-3/8 INCHES THICK, OR
 20-MINUTE FIRE-RATED DOORS, EQUIPPED WITH A
 SELF-CLOSING DEVICE.
  
 12) SHOW COMPLIANCE WITH FBC-R302.6 DWELLING/GARAGE
 FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS
 REQUIRED BY TABLE R302.6. OPENINGS IN GARAGE WALLS
 SHALL COMPLY WITH SECTION R302.5. THIS PROVISION DOES
 NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR TO THE
 ADJACENT DWELLING UNIT WALL.
  
 13) SHOW COMPLIANCE WITH FBC-R311.7.8.1 HANDRAIL
 HEIGHT, MEASURED VERTICALLY FROM THE SLOPED PLANE
 ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF RAMP
 SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM) AND
 NOT MORE THAN 38 INCHES (965 MM).
  
 14) SHOW COMPLIANCE WITH FBC-R806.1 VENTILATION
 REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW.
 VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF
 1/16 INCH MINIMUM AND 1/4 INCH MAXIMUM. VENTILATION
 OPENINGS HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH MINIMUM
 AND 1/4 INCH MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.1.8.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR.
  
 15) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES (INCLUDING
 SECTIONAL GARAGE DOORS).
 THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL
 WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 16) THE ENERGY PERFORMANCE EVALUATION FORM CONTAINS
 ERRORS AND IS MISSING INFORMATION. THE FORMS REQUIRE
 THE SIGNATURE OF THE OWNER/AGENT. THE STREET IS LAKE
 AVE. AND NOT LAKE WORTH AVE. THE CITY IS WEST PALM
 BEACH AND NOT LANTANA. THE JURIDICTION NUMBER IS
 604700. THE UNITS DO NOT MEET THE CRITERIA IN FBC
 ENERGY CONSERVATION SECTION R405.7.4 TO USE THE CROSS
 VENTILATION OPTION CREDIT.
  
 17) THERE IS AN OVER-TYPE ERROR IN THE TITLE BLOCK OF
 SHEETS S10, S11, S12 AND S13. FBC 107.2.1
  
 18) SPECIFY THE TYPE OF CONSTRUCTION AND OCCUPANCY ON
 THE PLANS. THE CONSTRUCTION IS TYPE V-B AND TOWNHOUSES
 ARE R-3 OCCUPANCIES. FBC 601 AND FBC 302.1
  
 19) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 RE-SUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2016-04-27 Cont ID  
Sent By albarran Date 2016-04-27 Time 10:35 Rev Time 0.00
Received By albarran Date 2016-04-27 Time 10:35 Sent To B
Notes
2016-04-27 10:35:39ALL PREVIOUSLY MENTIONED ITEMS HAVE BEEN SATISFACTORILY
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2016-03-29 Cont ID  
Sent By albarran Date 2016-03-29 Time 10:15 Rev Time 0.00
Received By albarran Date 2016-03-29 Time 10:04 Sent To  
Notes
2016-03-29 10:16:004TH ELECTRICAL REVIEW NOTES FOR PERMIT 15090401 . PLANS
 FILED UNDER PERMIT #:15090395
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014,
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
  
 1. PER A TELEPHONE CONVERSATION WITH ANDREW OF
 SILBERSTEIN ARCHITECTURE THE SOUTH ELEVATION OF UNIT
 ?B? WILL BE REVISED TO SHOW THE SLIDING DOOR ENTRY FROM
 THE COURTYARD. IN DOING SO, THE RECEPTACLES NOW
 INDICATED ON THE PLANS SHALL BE RELOCATED TO MEET NEC
 210.52 REQUIREMENTS.
 2. THE ADDITION OF THE DOOR/ENTRY WILL GENERATE THE
 NEED TO LIGHT CONTROL AS PER NEC 210.70 FOR THE
 REQUIRED LIGHT OUTSIDE THE DOOR.
 3. NEC 210.52 (E)(3) REQUIRES THAT YOU PROVIDE A GFI
 OUTLET IN EVERY BALCONY GREATER THAN 20 SQ. FT. (B202,
 B302 & B306)
 4. IN THE INTEREST OF LIFE SAFETY, USER CONVENIENCE AND
 ENERGY CONSERVATION, 3 WAY SWITCHING IS RECOMMENDED AT
 A MINIMUM FOR THE TRAVERSE LIGHTING.
 5. FBC-R MECHANICAL VENTILATION IS REQUIRED FOR ROOMS
 B102, B303 & B304. THE EXHAUST FAN SHALL COME ON WITH
 THE LIGHT.
 6. NEC 314.27 A LISTED FAN BOX IS REQUIRED FOR ROOM
 B101.
 7. NEC 210.70 REQUIRES THAT ROOM LIGHTS BE SWITCH UPON
 ENTRY, THEREFORE IF WALL CONTROL IS DESIRED FOR THE
 PADDLE FAN, AN ADDITIONAL SWITCH WILL BE REQUIRED.
 8. NEC 404.2(C) REQUIRES THAT A GROUNDED CONDUCTOR BE
 PROVIDED AT EVERY LIGHT SWITCH.
 9. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE
 LAMPS IN PERMANENTLY INSTALLED FIXTURES BE HIGH
 EFFICIENCY.
 10. THESE COMMENTS ARE IN ADDITION TO ANY OF THE
 PREVIOUSLY MENTIONED WHICH HAVE NOT YET BEEN SATISFIED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-02-18 Cont ID  
Sent By albarran Date 2016-02-17 Time 10:15 Rev Time 0.00
Received By albarran Date 2016-02-17 Time 10:15 Sent To  
Notes
2016-02-18 09:50:51IN FOLLOWING THE RESPONSE LETTER, I INITIALLY DID NOT
 REALIZE THAT THE POWER AND LIGHTING PLAN SHEETS IN THE
 BLDG B SET ARE THOSE OF UNITS A. THIS MUST BE CORRECTED
 AND THE PLANS REVIEWED FOR CORRECTNESS BEFORE WE CAN
 PROCEED.
2016-02-17 10:15:23WITH THE EXCEPTION OF THE UTILITY EASEMENTS ALL
 PREVIOUS COMMENTS HAVE BEEN SATISFACTORILY ADDRESSED.
 THE RERSPONSE NARRATIVE DOES INDICATE THAT THE EASMENTS
 HAVE BEEN SECURED, THEREFORE I WILL APPROVE THE REVIEW
 WITH A PROVISO THAT THE EASMENTS SHALL BE PROVIDED FOR
 FINAL INSPECTIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-22 Cont ID  
Sent By albarran Date 2015-12-22 Time 15:08 Rev Time 0.00
Received By albarran Date 2015-12-22 Time 15:08 Sent To  
Notes
2015-12-22 15:08:49DECEMBER 22ND, 2015 2ND ELECTRICAL REVIEW
  
 RE: RESPONSE TO FIRST REVIEW COMMENTS FOR THE PARK
 SLOPE TOWNHOUSES.
  
 BELOW IS MY RESPONSE TO YOUR COMMENTS. PLEASE NOTE THAT
 THEY APPEAR IN THE SAME ORDER IN WHICH YOU SUBMITTED
 THEM TO ME.
  
 10) I INFORMED YOU THAT WE WILL NEED A COPY OF THE
 RECORDED EASEMENTS BEFORE WE CAN APPROVE THE ELECTRICAL
 REVIEW. YOU DELEGATED TO SOMEONE ELSE, BUT REGARDLESS
 OF WHO SECURES THE EASEMENTS. A COPY OF THE RECORDED
 DOCUMENTS SHALL ACCOMPANY YOUR SUBMITTAL PRIOR TO
 APPROVAL.
  
 11) WE ALREADY ESTABLISHED A SEPARATE PERMIT FOR THE
 HOUSE METER AND OTHER ITEMS RELATED THERETO.
  
 12) WE CONCUR ON THE POOL PERMIT ISSUE.
  
 13) YOU CORRECTED THE NOTE BUT INCORRECT CODE
 REFERENCES REMAIN. THE PROPER CODES TO FOLLOW ARE: THE
 FLORIDA FIRE PREVENTION CODE (FFPC) 2012, NFPA 70
 (NATIONAL ELECTRICAL CODE) 2011, NFPA 72 2010 EDITION,
 AND THE 5TH EDITION OF THE 2014 FLORIDA BUILDING CODE
 (FBC). CORRECT YOUR NOTE ACCORDINGLY.
  
 17) YOU CONTINUE TO REFER TO A NONEXISTENT CABLE. BX
 CABLE IS NOT RECOGNIZED IN THE CODE BOOK.
  
 22 -28) REFER TO SHEET E301 WHICH WAS NOT PROVIDED.
  
 33 & 34) I ASKED FOR A FLOOR OUTLET SO THAT YOU COULD
 GET AWAY WITH A SINGLE UNIT BUT YOU HAVE IMPROVED ON
 THAT BY ADDING TO OUTLETS IN THE CORRIDORS. FYI AND
 OUTLET IS REQUIRED HERE EVEN THOUGH THIS IS A HALLWAY.
 SEE NEC 210.52 (H).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME. HAVE A VERY MERRY CHRISTMAS AND A
 PROSPEROUS 2016.
  
 MIKE ALBARRAN,
 ELECTRICAL PLANS EXAMINER
 (561) 805-6746
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 19:01 Rev Time 0.00
Received By albarran Date 2015-10-21 Time 11:21 Sent To  
Notes
2015-10-21 19:02:05THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
 1. YOU SHALL PROVIDE PROOF OF THE RECORDED EASEMENTS
 FOR THE FLORIDA POWER & LIGHT (FPL) UNDERGROUND FEEDERS
 TRAVERSING NEIGHBORING AND NON RELATED PROPERTIES.
 2. THE HOUSE METER AND PANEL ?H? ON THE EXTERIOR OF
 1200 S. LAKE AVENUE, ALONG WITH THE RESPECTIVE
 LANDSCAPE LIGHTING AND ANY INCIDENTAL ATTACHED THERETO
 INDICATED OR NOT ON THE APPROVED PLANS SHALL BE
 INSTALLED UNDER A SEPARATE PERMIT.
 3. ALL POOL ELECTRIC SHALL BE UNDER A SEPARATE PERMIT.
 4. SPEC NOTE 3, QUOTES NON-APPLICABLE CODES. CORRECT TO
 REFLECT THE CODES IN EFFECT AS INDICATED ABOVE.
 5. SPEC NOTE 9, REFLECTS INCORRECT ARC-FAULT
 REQUIREMENTS FOR THE CURRENT CODE. CORRECT ACCORDINGLY.
 6. SPEC NOTE 10, CONDUCTOR INSULATION HAS NOTHING TO DO
 WITH WIRE GAUGE, BUT WITH INSTALLATION CONDITIONS. THWN
 SHALL BE REQUIRED REGARDLESS OF GAUGE FOR CONDUCTORS IN
 WET LOCATIONS.
 7. GENERAL NOTES 10, REFER TO BX CABLE, CORRECT THAT TO
 REFLECT NM OR AC AS IN THE CURRENT EDITION OF THE NEC.
 8. GENERAL NOTES 11, ALL LUMINARIES SHALL BE GROUNDED
 AS INDICATED IN PART V OF SECTION 410 OF THE 2011 NEC.
 9. ADDITIONAL NOTES REQUIRED:
 A) ALL RECEPTACLES TO BE LISTED TAMPER-RESISTANT ?TR?
 AS REQUIRED IN NEC 406.12.
 B) ALL CEILING LUMINAIRE OUTLETS SHALL BE RATED TO
 SUPPORT 50# AS INDICATED IN NEC 314.27.
 C) RECEPTACLES IN WET LOCATIONS SHALL BE LISTED FOR THE
 PURPOSE ?WR? AS INDICATED IN NEC 406.8
 10. UNIT ?H? FEEDER NOTES, BLDG. GRD. PER NEC 250.66 A
 100 AMP SERVICE REQUIRES A #8CU GEC. *THE 5OHM
 RESISTANCE CALLED FOR ON THE PLANS IS PROBABLY
 UNOBTAINABLE. CODE CALLS FOR 25 OHMS IN NEC 250.53.
 11. ARE YOU SURE YOU WANT THE PANELS SURFACE MOUNTED AS
 INDICATED ON THE RESPECTIVE PANEL SCHEDULES?
 12. PANEL SCHEDULE ?A? CIRCUIT 14 IS LABELED AS
 DISPOSAL YET INDICATED AS D/W ON FLOOR PLAN. CORRECT
 ACCORDINGLY.
  
  
 UNIT ?A?
 1. INDICATE LOCATION OF ELECTRIC METER & SERVICE
 DISCONNECT ON FLOOR PLAN.
 2. NEC 210.52(E)(3) REQUIRES THAT THERE BE AN OUTLET IN
 THE PORCH AREA.
 3. ROOM A103, OUTLET SPACING SHALL BE AS PER NEC
 210.52(A), CHECK THE NORTH WALL.
 4. THE AREA BETWEEN THE PANTRY AND THE POWDER ROOM IS
 MISSING AN OUTLET. NEC 210.52(A).
 5. ROOM A300 IS MISSING AN OUTLET ON THE EXTERIOR WALL
 OF ROOM A303.
 6. ROOM A307 IS MISSING AN OUTLET ON THE EXTERIOR WALL
 OF ROOM A309.
 7. ROOM A306 REQUIRES A LIGHT CONTROLLED BY A WALL
 SWITCH PER NEC 210.70(A)(3)
 8. IT APPEARS THAT THERE IS AN HVAC UNIT INSIDE THE
 ATTIC, IF THIS IS CASE; NEC 110.33(B) REQUIRES THAT
 THERE BE A PERMANENT LADDER INTO THE ATTIC. OTHER
 SECTIONS OF THE CODE REQUIRE THAT THERE BE A GFI OUTLET
 AND A LIGHT CONTROLLED BY A WALL SWITCH AND NOT A PULL
 CHAIN INSIDE THE ATTIC. THIS LIGHT SWITCH SHOULD HAVE
 AN INDICATOR SO AS NOT TO LEAVE THE LIGHT ON INSIDE THE
 ATTIC WHEN NOT NEEDED.
  
 UNIT ?B?
 1. INDICATE LOCATION OF ELECTRIC METER & SERVICE
 DISCONNECT ON FLOOR PLAN.
 2. NEC 680.10 PROHIBITS ANY UNDERGROUND WIRING FROM
 RUNNING UNDER THE POOL OF WITHIN 5? HORIZONTALLY OF THE
 INSIDE WALL OF THE POOL UNLESS THE WIRING IS DIRECTLY
 RELATED TO THE POOL.
 3. THERE IS A MISSING OUTLET FOR THE SPACE OUTSIDE OF
 THE SOUTH WALL OF ROOM B302.
 4. A FLOOR OUTLET SHALL BE INSTALLED ALONG THE FLOOR
 LINE OF THE STAIR RAILING.
 5. ROOM B200 IS MISSING AN OUTLET ON THE WALL OUTSIDE
 OF THE BATHROOM.
 6. ROOM B307 REQUIRES A LIGHT CONTROLLED BY A WALL
 SWITCH.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 05:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-01-27 Cont ID  
Sent By tklarge Date 2015-12-06 Time 13:12 Rev Time 0.00
Received By tklarge Date 2015-12-06 Time 13:12 Sent To  
Notes
2016-01-27 13:13:341) THE RESPONSE FROM THE ENGINEERING FIRM FOR THE GAS
 COMMENT REGARDING COMBUSTION AIR REFERS TO SHT. M301.
 THERE IS NO SUCH DRAWING IN THIS SET OF PLANS. CLARIFY.
 2) SHT. M401 - WATER HEATER COMBUSTION AIR CALCULATIONS
 SHOWS THE TANKLESS WATER HEATER AS 35,000 BTU'S AND THE
 GAS RISER SHOWS THE BTU LOAD AS 199,000 BTU'S. THIS IS
 OBVIOUSLY A MISPRINT. REVISE.
 3) THE PLUMBING PLANS SHALL BEAR THE WET SIGNATURE OF
 THE ENGINEER OF RECORD PER THE F.A.C. RULE
 61G15-23.001, .002, & .003.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-09-21 Cont ID  
Sent By gjohnson Date 2015-09-21 Time 07:21 Rev Time 0.00
Received By gjohnson Date 2015-09-21 Time 07:21 Sent To  
Notes
2015-09-21 07:22:081ST REVIEW: FBC 2014
  
 GAS COMMENTS:
 1.SHEETS P203 AND P303 YOU REFERENCED SIZING TABLES
 FROM FBC FUEL GAS 2010 AND ON P303 THE TABLE ON THE LOW
 PRESSURE SIDE OF THE RISER IS NOTE MATCHING UP TO THE
 TABLE AT THE TOP OF THE PAGE . THE RISER APPEARS TO BE
 OVER SIZED PLEASE RESIZE USE TABLES FROM FBC FUEL GAS
 2014.
 2. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR WATER
 HEATER AND DRYER. PER WPB AMEND 107.2.1
 3. PLEASE PROVIDE SPEC SHEETS ON DRYER, TANKLESS HEATER
 AND RANGE. PER WPB AMEND 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-05-11 Cont ID  
Sent By rmcdouga Date 2016-05-11 Time 13:15 Rev Time 0.00
Received By rmcdouga Date 2016-04-25 Time 13:57 Sent To  
Notes
2016-04-25 13:58:04RESUB ROUTED TO MALBARRAN
 TRAVELLING WITH 15090395, 15090396, 15090397, 15090398,
 15090399, 15090400, 15090401, 15090402

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-25 Cont ID  
Sent By lmarchan Date 2016-04-25 Time 13:57 Rev Time 0.00
Received By lmarchan Date 2016-03-07 Time 11:49 Sent To  
Notes
2016-03-07 11:49:27R33 TRAVELLING WITH 15090395, 15090396, 15090397,
 15090398, 15090399, 15090400, 15090401 & 15090402

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-19 Cont ID  
Sent By lmarchan Date 2016-02-19 Time 09:50 Rev Time 0.00
Received By lmarchan Date 2016-02-01 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-28 Cont ID  
Sent By lmarchan Date 2016-01-28 Time 11:37 Rev Time 0.00
Received By lmarchan Date 2015-11-23 Time 09:37 Sent To  
Notes
2015-11-30 09:37:08TRAVELLING WITH 15090395

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-05 Cont ID  
Sent By lmarchan Date 2015-11-05 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2015-08-31 Time 10:57 Sent To  
Notes
2015-09-14 10:57:08TRAVELLING WITH 15090395

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status N Date 2017-02-09 Cont ID  
Sent By jwitmer Date 2017-02-09 Time 12:45 Rev Time 0.00
Received By jwitmer Date 2017-02-09 Time 12:45 Sent To  
Notes
2017-02-09 12:45:59PALM BEACH COUNTY IMPACT FEES
 MU-2016-419
 $60,512.72
 802,391 SQ. FT.
 J. W. 2/09/2017

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-05-11 Cont ID  
Sent By rmcdouga Date 2016-05-11 Time 13:15 Rev Time 0.00
Received By rmcdouga Date 2016-05-11 Time 13:15 Sent To  
Notes
2016-05-11 13:15:09BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-03-18 Cont ID  
Sent By rmcdouga Date 2016-03-18 Time 17:01 Rev Time 0.00
Received By rmcdouga Date 2016-03-18 Time 17:01 Sent To  
Notes
2016-03-18 17:23:36BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-02-16 Cont ID  
Sent By rmcdouga Date 2016-02-16 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2016-02-16 Time 09:58 Sent To  
Notes
2016-02-16 09:59:15SEE COMMENTS FROM 1ST REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-12-23 Cont ID  
Sent By rmcdouga Date 2015-12-23 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2015-12-23 Time 18:03 Sent To  
Notes
2015-12-23 18:03:43SEE PREVIOUS COMMENTS

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By rmcdouga Date 2015-10-22 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2015-10-22 Time 11:04 Sent To  
Notes
2015-10-22 11:04:59BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON CITY APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-23 Cont ID  
Sent By ccole Date 2016-03-23 Time 09:59 Rev Time 0.00
Received By ccole Date 2016-03-23 Time 09:59 Sent To  
Notes
2016-03-23 09:59:45MECHANICAL PROVISIO:
 3/23/16
  
 1) PER ENGINEER'S REQUEST, REVISED AC CALCULATIONS,
 PLANS, AND SPECIFICATIONS WILL BE SUBMITTED AT A FUTURE
 DATE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-12 Cont ID  
Sent By ccole Date 2016-02-12 Time 09:46 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 09:46 Sent To  
Notes
2016-02-12 09:46:503RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090401: MODEL B- #764.
 2/12/16
  
 1) THERE ARE SEVERAL CONFLICTS BETWEEN THE AC COOLING
 LOAD CALCULATIONS, THE ENERGY CALCULATIONS AND THE AC
 PLANS.
 A) THE AC CALCULATIONS INDICATE TWO ZONES WITH
 CALCULATED COOLING LOADS OF 2.0 ON THE 1ST LEVEL, AND
 3.8 TONS ON THE 2ND AND 3RD LEVELS. ON SHEET M201,
 HOWEVER, 3-TON AND 4-TON SYSTEMS ARE SHOWN FOR UNIT
 #764, AND ON M301 TWO 4-TON SYSTEMS ARE SHOWN (NOTE
 THAT A 4-TON SYSTEM IS USED TO SUPPLY THE 1ST AND 2ND
 LEVEL WHICH CONFLICTS WITH THE CALCS). PLEASE CORRECT
 AND ALSO REFER TO SECTION R403.6.1.1 FBC-14 ENERGY
 CONSERVATION WHICH PROHIBITS OVERSIZING OF AC SYSTEMS
 GREATER THAN 1.15 TIMES THE CALCULATED LOAD.
 B) THE SUBMITTED ENERGY CALCULATION FORM R405-2014
 SHOWS COMPLIANCE DATA FOR A SINGLE COOLING SYSTEM WHICH
 APPEARS TO ACTUALLY BE COMPLIANCE DATA FOR BOTH OF THE
 AC SYSTEMS( 3-TON & 4-TON) COMBINED AND AVERAGED.
 PLEASE PROVIDE COMPLIANCE DATA FOR EACH INDIVIDUAL
 SYSTEM AND, AS NOTED ABOVE, COMPARE WITH THE PLANS
 WHICH INDICATES TWO 4-TON SYSTEMS.
 C) THE AC CALCULATIONS FORM IS INDICATING THE FRONT
 DOOR FACES EAST HOWEVER THE FRONT DOOR IS FACING NORTH.
 2) SHEET: M301: THE MAIN RETURN DUCT SIZES FROM THE
 18X18" GRILL AND THE14X14" GRILLS ARE NOT SHOWN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-27 Cont ID  
Sent By ccole Date 2015-12-14 Time 09:08 Rev Time 0.00
Received By ccole Date 2015-12-14 Time 09:08 Sent To  
Notes
2016-01-27 09:09:212ND REVIEW 2014 MECHANICAL
 PERMIT #15090401
 12/14/15
  
 I HAVE REVIEWED THE REVISED PLANS AND THE RESPONSE
 NARRATIVE FROM JWL ENGINEERING, HOWEVER INADEQUATE
 REVISIONS AND RESPONSES HAVE BEEN GIVEN TO SOME OF THE
 COMMENTS. THE FOLLWOWNG REVIEW WILL REFER BACK TO THOSE
 1ST REVIEW COMMENTS. PLEASE NOTE THE RESPONSE NARRATIVE
 FROM JWL ADDRESSES ONLY THE FIRST FOUR COMMENTS (LISTED
 AS 6-9 IN THE NARRATIVE), AND THERE WERE NO RESPONSES
 FROM THE ARCHITECT.
 1) COMMENT #1: THE NARRATIVE REPONSE TO THIS COMMENT
 STATES THAT THE REQUESTED DESIGN CRITERIA FOR THE
 PROJECT IS NOTED ON SHEET M101, HOWEVER I DID NOT SEE
 ANY INFORMATION LISTED IN THE MECH SPEC NOTES.
 2) COMMENT #3: SECTION 405.4.2 EXCEPTION ALLOWS FOR
 WORSE CASE SCENARARIOS, HOWEVER AS NOTED IN THE 1ST
 REVIEW, INDIVIDUAL ENERGY AND AC CALCULATIONS SHALL BE
 SUBMITTED FOR EACH TOWN HOME UNDER PERMIT PER SECTION
 R103.1 FBC-14 ENERGY CONSERVATION. PLEASE NOTE THAT THE
 RE-SUBMITTED ENERGY FORM R405-2014 INDICATES IT IS NOT
 A WORSE CASE ON PAGE 1.
 3) COMMENT #4: RE-SUBMITTED FORM R405-2014 : A) PAGE 1
 INDICATES 98.7 KBTU/HR FOR 2263 SQ.FT.- ONE OF THESE
 VALUES IS INCORRECT. B) PAGE 3- THE COOLING SYSTEM DATA
 DOES NOT INDICATE A COOLING CAPACITY VALUE, AND THE
 2960 AIR FLOW CFM'S DOES NOT MATCH THE CFM'S INDICATED
 IN THE AC EQUIPMENT SCHEDULE ON M101.
 4) COMMENTS #6, 8,9,10,11,12,13,&14- NO RESPONSES OR
 REVISIONS WERE PROVIDED: REFER TO 1ST REVIEW COMMENTS
 AND COMPLY. PLEASE NOTE IN REGARD TO COMMENT #9- THE
 PLUMBING PLANS LIST THE WATER HEATER CAPACTITY AT 199
 CFH NOT AT 34 KBTUH,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By ccole Date 2015-09-29 Time 07:33 Rev Time 0.00
Received By ccole Date 2015-09-29 Time 07:33 Sent To  
Notes
2015-09-29 07:33:381ST REVIEW: FBC 2014 RESIDENTIAL
 PERMIT #15090401
 9/29/15
  
 1) DESIGN CRITERIA: PLEASE PROVIDE DEFINITIVE DESIGN
 CRITERIA AND CODE DATA ON THE PLANS FOR THE PROPOSED
 PROJECT. AS THE PERMIT APPLICATIONS INDICATE "TOWN
 HOMES" I AM REVIEWING THE PLANS FOR COMPLIANCE WITH THE
 FBC-14 RESIDENTIAL CODE. PLEASE REVIEW AND REVISE WHERE
 REQUIRED.
 2) CORRECT THE SUBMITTED ENERGY AND HVAC CALCULATIONS
 INDICATING "LANTANA, FL." IN THE TITLE ADDRESSES- THE
 PROPOSED PROJECT IS IN THE CITY OF WEST PALM BEACH.
 3) INDIVIDUAL ENERGY CALCULATIONS AND AC COOLING AND
 HEATING CALCULATIONS SHALL BE SUBMITTED SEPARATELY FOR
 EACH TOWN HOME IN ACCORDANCE WITH SECTION R103.1 FBC-14
 ENERGY CONSERVATION- "GENERAL. CONSTRUCTION DOCUMENTS
 AND OTHER SUPPORTING DATA SHALL BE SUBMITTED IN ONE OR
 MORE SETS WITH EACH APPLICATION FOR A PERMIT. THE
 CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY THE
 STATUTES OF THE JURISDICTION IN WHICH THE PROJECT IS TO
 BE CONSTRUCTED. WHERE SPECIAL CONDITIONS EXIST, THE
 CODE OFFICIAL IS AUTHORIZED TO REQUIRE NECESSARY
 CONSTRUCTION DOCUMENTS TO BE PREPARED BY A REGISTERED
 DESIGN PROFESSIONAL." EACH SUBMITTAL DOCUMENT SHALL
 BEAR THE SAME ADDRESS AS THE ONE LISTED ON THE
 CORRESPONDING PERMIT APPLICATION, AND MANUAL J AC
 SIZING WORKSHEETS SHALL BE SUBMITTED FOR EACH NEW TOWN
 HOME INDICATING DIRECTIONAL ORIENTATIONS AND CALCULATED
 LOADS FOR EACH INDIVIDUAL TOWN HOME- REFER TO SECTION
 R403.6.1 FBC-14 ENERGY CONSERVATION- "WORST CASE
 SCENARIOS" FOR EACH BUILDING ARE NOT ACCEPTABLE.
 4) REVIEW OF THE SUBMITTED ENERGY EFFICIENCY FORM
 R405-2014 FOR BLDG. B REVEALED THESE DEFICIENCIES: A)
 THE SQUARE FOOTAGE CALCULATION DOESN'T MATCH THE
 FOOTAGE LISTED ON SHEET A-1.0. B) THE WINDOW U-VALUES
 LISTED DON'T MATCH THE U-VALUES LISTED ON THE AC
 CALCULATIONS. C) THE AIRFLOW CFM'S AND HEATING
 CAPACITIES LISTED DON'T MATCH THE AC SCHEDULE.
 5) REVIEW OF THE SUBMITTED HVAC CALCULATIONS REVEALED
 THESE DEFICIENCIES: A) THE COOLING EQUIPMENT SUMMARIES
 WERE NOT COMPLETED FOR EACH SYSTEM. B) REFER TO COMMENT
 #3.
 6) SHEET M101: CORRECT THE REFERENCES TO THE FBCM SHOWN
 ON THE BUILDING AND GARAGE VENTILATION TABLES. PROVIDE
 CALCULATIONS IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL.
 7) M102, DETAIL A7: THE PRINT IN THE DETAIL AND
 STRAPPING TABLE IS TOO FAINT TO READ AND NEEDS TO BE
 EMBOLDENED FOR REVIEW AND COMPUTER SCANNING. PLEASE
 NOTE THAT THE ROOM ID NUMBERS SHOWN ON ALL OF THE
 LAYOUT PLANS ALSO NEED TO BE EMBOLDENED.
 8) M102, DETAIL C7: INDICATE THE TYPE AND SIZE OF
 CONDENSATE PIPING TO BE INSTALLED.
 9) M401: CORRECT THE REFERENCES TO THE FBCFG ON THE
 RANGE AND DRYER COMBUSTION TABLES. PROVIDE CALCULATIONS
 IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL. PLEASE NOTE
 THE DRYER IN THE CLOSET MUST BE PROVIDED COMBUSTION AIR
 THROUGH OPENINGS IN THE DOORS- SEE SECTION G2407.5.3
 FBC-14 RESIDENTIAL AND PROVIDE SIZING CALCULATIONS AND
 OPENING SIZES.
 10) M401: REFER TO SECTION M1305.1.1 AND SHOW
 COMPLIANCE FOR THE AIR HANDLERS IN THE CLOSETS- PROVIDE
 AN ENLARGED DETAIL IF NECESSARY TO SHOW THE REQUIRED
 CLEARANCE DIMENSIONS.
 11) M401: INDICATE THE SIZE OF THE LOUVER AT THE FIRST
 FLOOR AIR HANDLER CLOSET. CLARIFY HOW ALL AIR IS BEING
 RETURNED TO THE AIR HANDLERS- THE PLAN SHOWS A LOUVERED
 DOOR, BUT THE DETAIL ON M102 SHOWS A DUCTED RETURN IN
 THE CLOSET.
 12) SHOW THE CONDENSATE DISPOSAL PIPING RUNS AND
 DISCHARGE LOCATIONS.
 13) SHOW THE REFRIGERANT PIPING RUNS.
 14) PROVIDE A SUBMITTAL PACKAGE CONSISTING OF THE
 RANGE, RANGE HOOD AND EXHAUST DUCT, WATER HEATER AND
 VENT PIPING, DRYER AND VENT PIPING, AC SYSTEMS, AND THE
 VAV BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 05:38 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 05:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-12-06 Cont ID  
Sent By tklarge Date 2016-01-27 Time 12:49 Rev Time 0.00
Received By tklarge Date 2015-12-06 Time 12:49 Sent To  
Notes
2016-01-27 12:49:361) SHT. A-1.0 SHOWS A DECK DRAIN BY THE POOL. IS THE
 DRAIN AND PIPING BEING INSTALLED UNDER THE PLUMBING FOR
 THE BUILDING? IF SO, SHOW THE PIPING ON THE CIVIL
 DRAWINGS, THE SIZE AND THE SQUARE FOOTAGE DRAINED BY
 THE DRAIN. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A SCUPPER DETAIL. THE LOCATION OF THE SCUPPER
 SHALL COMPLY WITH 2014 FBCR SEC.R903.4.1.SUBMIT
 CALCULATIONS FOR THE SIZE OF THE OVERFLOW SCUPPER.
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH 2014
 FBC-PLUMBING.
 4) SHT.A-3.1 REFERS TO A-6.0 FOR A SECTION DETAIL. THIS
 SHEET IS NOT IN THE PLANS. DOES THIS SHEET SHOW THE
 SCUPPER DETAIL? CLARIFY.
 5) SHT. A-5.3-DETAIL #1 CALLS OUT AN ENLARGED KITCHEN
 PLAN BUT A BATHROOM IS SHOW. PLEASE REVISE.
 6) SHT. P-102 SHOWS A MAIN WATER METER. WHAT WILL THIS
 METER SERVICE? CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P301 - SIZE THE VENTS ON THE SANITARY RISER. IF
 THE VENTS ARE TYPICAL, SIZE THE VENT AND NOTE THAT THE
 OTHER VENTS ARE TYPICAL SIZE. THE VENT SYSTEM SHALL BE
 SIZED IN ACCORDANCE WITH 2014 FBCR- SEC.P3113.1.
 8) THE RESPONSE FROM THE ENGINEERING FIRM FOR THE GAS
 COMMENT REGARDING COMBUSTION AIR REFERS TO SHT. M301.
 THERE IS NO SUCH DRAWING IN THIS SET OF PLANS. CLARIFY.
 9) SHT. M401 - WATER HEATER COMBUSTION AIR CALCULATIONS
 SHOWS THE TANKLESS WATER HEATER AS 35,000 BTU'S AND THE
 GAS RISER SHOWS THE BTU LOAD AS 199,000 BTU'S. THIS IS
 OBVIOUSLY A MISPRINT. REVISE.
 10) SHT. P101-WATER HEATER DETAIL REFERS TO A HOT WATER
 RECIRCULATING LINE (?) BUT THIS IS NOT SHOWN ON THE
 WATER PIPING PLAN VIEW. CLARIFY.
 11) THE PLUMBING PLANS SHALL BEAR THE WET SIGNATURE OF
 THE ENGINEER OF RECORD PER THE F.A.C. RULE
 61G15-23.001, .002, & .003.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-21 Cont ID  
Sent By gjohnson Date 2015-09-21 Time 07:22 Rev Time 0.00
Received By gjohnson Date 2015-09-21 Time 07:22 Sent To  
Notes
2015-09-21 07:22:391ST REVIEW: FBC 2014
  
 PLUMBING COMMENTS:
 1. PLEASE PROVIDE WATER RISER DIAGRAM. PER WPB AMEND.
 107.3.5.1.3(13)
 2. PLEASE PROVIDE SPEC. ON SHOWER PANS, TUBS AND THE
 TANKLESS WATER HEATER. PER WPB AMEND. 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-03-28 Cont ID  
Sent By llouie Date 2016-03-28 Time 14:26 Rev Time 0.00
Received By llouie Date 2016-03-28 Time 14:26 Sent To  
Notes
2016-03-28 14:27:03ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) LANDSCAPE HEDGE REQUIRED IN FRONT OF THE CHAIN LINK
 FENCE WITHIN THE PROPERTY LINE ALONG THE EASTERN
 BOUNDARY OF THE SITE.
  
 2.) CHAIN LINK FENCE ALONG EASTERN BOUNDARY OF SITE
 SHALL NOT EXCEED 4 FT. IN HEIGHT WITHIN THE FIRST 25
 FT. OF THE FRONT PROPERTY LINE.
  
 3.) SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR
 LANDSCAPING.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-02-01 Cont ID  
Sent By llouie Date 2016-02-01 Time 15:56 Rev Time 0.00
Received By llouie Date 2016-02-01 Time 15:56 Sent To  
Notes
2016-02-01 15:56:45ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR
 LANDSCAPING.
  
 2.) LANDSCAPE HEDGE WILL BE REQUIRED IN FRONT OF CHAIN
 LINK FENCE ON THE EAST SIDE OF BUILDING B.
  
 3.) APPLICATION IS SUBJECT TO REQUIREMENT FOR ART IN
 PUBLIC PLACES (AIPP). PLEASE CONTACT SYBILLE WELTER,
 AIPP COORDINATOR AT (561) 822-1521.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-01-27 Cont ID  
Sent By llouie Date 2016-01-27 Time 10:25 Rev Time 0.00
Received By llouie Date 2016-01-27 Time 10:25 Sent To  
Notes
2016-01-27 10:26:03** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT: A RE-PLAT OF THE PROPERTY IS
 REQUIRED. AN APPLICATION FOR A RE-PLAT SHALL BE
 SUBMITTED TO AND APPROVED BY THE CITY, AND RECORDED
 WITH PALM BEACH COUNTY PRIOR TO THE APPROVAL OF A
 BUILDING PERMIT.
  
 (12/10/15 NOTE: THE RE-PLAT (RESOLUTION NO. 366-15) IS
 SCHEDULED FOR THE 1/4/16 CITY COMMISSION MEETING FOR
 APPROVAL.)
  
 ADDITIONAL NOTE(S):
  
 * ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $500,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINED IN
 CHAPTER 78, ARTICLE V OF THE CITY'S CODE OF ORDINANCES.
 PLEASE CONTACT SYBILLE WELTER, AIPP COORDINATOR, AT
 (561) 822-1521 FOR MORE INFORMATION.
  
 * PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-28 Cont ID  
Sent By llouie Date 2015-10-28 Time   Rev Time 0.00
Received By llouie Date 2015-10-28 Time 15:36 Sent To  
Notes
2015-10-28 15:33:31** FAILED **
  
 CONDITIONS OF APPROVAL FOR THE SITE PLAN HAVE NOT BEEN
 ADDRESSED (REFERENCE: ISPR 15-01):
  
 1.) A RE-PLAT OF THE PROPERTY IS REQUIRED. AN
 APPLICATION FOR A RE-PLAT SHALL BE SUBMITTED TO AND
 APPROVED BY THE CITY, AND RECORDED WITH PALM BEACH
 COUNTY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 2.) ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $500,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINED IN
 CHAPTER 78, ARTICLE V OF THE CITY'S CODE OF ORDINANCES.
 PLEASE CONTACT SYBILLE WELTER, AIPP COORDINATOR, AT
 (561) 822-1521 FOR MORE INFORMATION.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU HAVE
 QUESTIONS.
  
  