Plan Review Details - Permit 15090106
Plan Review Stops For Permit 15090106
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-05-19 Cont ID  
Sent By jwitmer Date 2016-05-19 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2016-05-19 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 16:52 Rev Time 0.00
Received By jwitmer Date 2016-04-11 Time 16:01 Sent To  
Notes
2016-04-11 16:52:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090106
 ADD: 1301 SUMMIT BLVD.
 WHITE ALLIGATOR EXHIBIT
 CONT: GAST CONSTRUCTION
 TEL: (321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. APRIL 11/ 2016
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 3RD REQUEST. SEMI-COMPLIED. THE WHITE ALLIGATOR
 EXHIBIT BUILDING, VIEWING AREA AND RESTROOM . THE SHEET
 A101 SHOWS THE FINISH FLOOR OF THE WHITE ALLIGATOR
 EXHIBIT (RESTROOM) AT A HEIGHT OF 13.15 FT. NGVD-1929.
 THERE ARE NO FINISH FLOOR HEIGHT FOR THE EXHIBIT FLOOR
 VIEWING AREAS NOR THE EQUIPMENT SLAB. UPDATED 4/15/16.
 JW
  
 5) COMPLIED.. ALTERRA SOILS ENGINEERING REPORT. UPDATED
 4/15/16 JW
  
 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES.
  
 7A-7B) COMPLIED. 107.3. DEFERRED SUBMITTALS THE
 DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE PRODUCT
 APPROVAL AFTER PERMIT ISSUANCE. 2010 FLORIDA BUILDING
 CODE W 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2
 DEFERRED SUBMITTALS.
 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3.
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-10 Cont ID  
Sent By   Date 2016-02-10 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-02-10 Time 05:56 Sent To  
Notes
2016-02-10 06:31:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090106
 ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR
 EXHIBIT.
 CONT: GAST CONSTRUCTION
 TEL: ( 321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. FEB. 10/ 2016
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE
 CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND
 SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300
 SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED
 FLOOR ELEVATION ARE TO BE SET, INCLUDING THE UPPER AND
 LOWER POND LEVELS. THE PONDS SET AT OR BELOW BFE WOULD
 NEED ENGINEERING OR A HYDROSTATIC RELIEF VALVE.
  
 PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF
 STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD
 ZONE. FLOOD ZONE CERTIFICATES FBC BUILDING 1612 AND
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION. FINISH FLOOR
 ELEVATION OF 12 FT. -
 6 INCHES OR HIGHER.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF
 THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE
 PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE
 ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY
 CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO
 A STRUCTURE, TAKING PLACE DURING THE LIFE OF A
 STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE
 STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE
 THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START
 OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE PURPOSES OF THIS DEFINITION,
 "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OF THE BUILDING COMMENCES,
 WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL
 DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL
 IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT
 OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH,
 SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO
 ENSURE SAFE LIVING CONDITIONS.
  
 SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION.
 (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND
 SANITARY FACILITIES, BE FLOOD-PROOFED SO THAT BELOW SIX
 INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS
 WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING
 THE CAPABILITY OF RESISTING HYDROSTATIC AND
 HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A
 REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL
 CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE
 SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE
 CITY ENGINEER.
  
 NOTE IF THE EXISTING STRUCTURE IS BELOW THE BASE FLOOD
 ELEVATION OF 12 FT. 6 INCHES AND SUBSTANTIAL
 IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF
 THE STRUCTURE AND THE OPTION IS TO INSTALL FLOOD VENTS
 TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE
 FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK
 RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSERS WILL
 NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND
 FLOOD ELEVATIONS ARE REQUIRED.
  
 4) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM
 SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A
 QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE
 REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT
 REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE
 WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE
 SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN
 SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS
 REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING
 CAPACITY OF THE SOILS WILL BE.
  
 5) COMPLIED.
  
 6-7) THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE
 PRODUCT APPROVAL AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS.
 PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHT REPAIR OR REPLACEMENT?
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) NEW COMMENT: SHEET S3.0 INDICATES POOLS BY OTHERS, A
 SEPARATE PERMIT AND PLANS WILL BE REQUIRED.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2015-09-27 Time 07:02 Sent To  
Notes
2015-09-27 07:49:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090106
 ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR
 EXHIBIT.
 CONT: CAG CONSTRUCTION
 TEL: ( 321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. SEPT. 27/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED
 UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR
 AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014
 FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE.
  
 2) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE
 AS U- OCCUPANCY (LIVESTOCK SHELTER) , IT WOULD APPEAR
 SINCE THE PUBLIC STOPS AND VIEWS THE VARIOUS DISPLAYS
 THE OCCUPANCY WOULD BE IN LINE OF A MUSEUM OR AN A3
 OCCUPANCY. THE PUBLIC WOULD NOT BE GOING AROUND IN A
 LIVE STOCK SHELTER VIEWING A DISPLAY.
  
 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION
 OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD
 ZONE. FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH
 FLOOR ELEVATION OF 12 FT. -
 6 INCHES OR HIGHER.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF
 THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE
 PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE
 ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY
 CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO
 A STRUCTURE, TAKING PLACE DURING THE LIFE OF A
 STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE
 STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE
 THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START
 OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE PURPOSES OF THIS DEFINITION,
 "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OF THE BUILDING COMMENCES,
 WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL
 DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL
 IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT
 OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH,
 SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO
 ENSURE SAFE LIVING CONDITIONS.
  
 SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION.
 (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND
 SANITARY FACILITIES, BE FLOODPROOFED SO THAT BELOW SIX
 INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS
 WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING
 THE CAPABILITY OF RESISTING HYDROSTATIC AND
 HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A
 REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL
 CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE
 SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE
 CITY ENGINEER.
  
 NOTE IF THE EXISITNG STRUCTURE IS BELOW THE BASE FLOOD
 ELEVATION OF 12 FT. 6 INCHES AND SUBSTANIAL
 IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF
 THE STRUCTURE ANOTHE OPTION IS TO INSTALL FLOOD VENTS
 TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE
 FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK
 RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSORS WILL
 NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND
 FLOOD ELEVATIONS ARE REQUIED.
  
 4) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS
 INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION
 THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY.
 THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS
 ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY
 OF THE SOILS WILL BE.
  
 5) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10,
 EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT
 SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED
 AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED
 PRESSURES ARE BLANK!!!!!!!!!!!
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2.) RISK CATEGORY.
  
 5.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHT REPAIR OR REPLACEMENT?
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-26 Cont ID  
Sent By albarran Date 2016-02-26 Time 10:19 Rev Time 0.00
Received By albarran Date 2016-02-26 Time 08:20 Sent To  
Notes
2016-02-26 10:20:33ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 10:24 Rev Time 0.00
Received By albarran Date 2015-11-19 Time 09:09 Sent To I
Notes
2015-11-19 10:25:26THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. THE CODE INFORMATION BLOCK ON THE FRONT SHEET
 REFERENCES NON APPLICABLE OR NONEXISTENT CODES. THE
 APPLICABLE CODES FOR THIS PROJECT ARE THE 5TH EDITION
 OF THE 2014 FBC AND THE 2011 EDITION OF THE NEC.
 2. NEC 110.16 REQUIRES THAT THE PANELBOARDS BE MARKED
 WITH THE ARC-FLASH HAZARD WARNING LABELS.
 3. NEC 406.9(B) STATES THAT ALL 15 - 20 AMP RECEPTACLES
 INSTALLED IN WET LOCATIONS SHALL IN ADDITION TO THE
 IN-USE TYPE COVER BE LISTED FOR THE PURPOSE AS
 WEATHER-RESISTANT. TYPE.
 4. NEC 408.4(B) ALL PANELS SHALL BE MARKED TO INDICATE
 THE LOCATION OF THE SOURCE OF POWER.
 5. NEC 422.52 REQUIRES THAT ELECTRIC WATER COOLERS BE
 CONNECTED TO A GFCI PROTECTED OUTLET.
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-05-19 Cont ID  
Sent By pleduc Date 2016-05-19 Time   Rev Time 0.00
Received By pleduc Date 2016-05-19 Time 13:18 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2016-04-07 Cont ID  
Sent By wjolin Date 2016-04-07 Time 09:18 Rev Time 0.00
Received By wjolin Date 2016-04-07 Time 09:00 Sent To  
Notes
2016-04-07 09:03:431301 SUMMIT BOULEVARD - ALLIGATOR EXHIBIT
 PERMIT #15090106
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN INDICATES THIS PROJECT IS A LEVEL 3 ALTERATION
 AFFECTING OVER 50% OF THE EXISTING BUILDING AREA;
 THEREFORE, PER NFPA 101 SECTION 43.5.2.3 WHERE THE
 TOTAL AREA OF ALL THE REHABILITATION WORK AREAS
 INCLUDED IN A MODIFICATION EXCEEDS 50 PERCENT OF THE
 AREA OF THE BUILDING, THE WORK SHALL BE CONSIDERED AS A
 RECONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS
 OF SECTION 43.6 FOR THE APPLICABLE OCCUPANCY.
 101-43.6.4.2 ON ANY STORY WITH REHABILITATION WORK
 AREAS INVOLVING OVER 50 PERCENT OF THE AREA OF THE
 STORY, A SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 THE STORY IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER
 SECTIONS OF THIS CODE APPLICABLE TO NEW CONSTRUCTION
 FOR THE OCCUPANCY.
  
 PER NFPA 150 STRUCTURES HOUSING TYPE A ANIMALS
 (REPTILES) SHALL BE PROTECTED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-09 Cont ID  
Sent By rlindow Date 2016-02-09 Time   Rev Time 0.00
Received By rlindow Date 2016-02-09 Time   Sent To  
Notes
2016-02-09 07:36:52PASSED WITH PROVISO: ADDITION OF NEW BATHROOM SHALL NOT
 INTERFERE WITH EXISTING MEANS OF EGRESS. LINDOW 2/9/16

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-09 Cont ID  
Sent By   Date 2015-09-09 Time   Rev Time  
Received By   Date 2015-09-09 Time   Sent To  
Notes
2015-09-09 14:32:27PASSED WITH PROVISO: ADDITION OF NEW BATHROOM SHALL NOT
 INTERFERE WITH EXISTING MEANS OF EGRESS. LINDOW 9/9/15

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-24 Cont ID  
Sent By jroach Date 2016-05-24 Time 11:14 Rev Time 0.00
Received By jroach Date 2016-05-13 Time 17:25 Sent To  
Notes
2016-05-16 08:28:16C22

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-14 Cont ID  
Sent By tklarge Date 2016-04-14 Time 13:35 Rev Time 0.00
Received By tklarge Date 2016-03-25 Time 10:48 Sent To  
Notes
2016-03-28 10:48:39C22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By jroach Date 2016-03-14 Time 14:58 Rev Time 0.00
Received By jroach Date 2016-02-02 Time 10:48 Sent To  
Notes
2016-02-03 10:48:24C22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 10:31 Rev Time 0.00
Received By albarran Date 2015-09-03 Time 13:38 Sent To  
Notes
2015-11-19 10:33:0111/19/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-08 Cont ID  
Sent By ccole Date 2016-04-07 Time 08:27 Rev Time 0.00
Received By ccole Date 2016-04-07 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-10 Cont ID  
Sent By ccole Date 2016-02-10 Time 11:21 Rev Time 0.00
Received By ccole Date 2016-02-10 Time 11:21 Sent To  
Notes
2016-02-10 11:57:302ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090106
 2/10/16
  
 1) SHEET M2: IT APPEARS THE FLOOR PLAN DRAWINGS DID NOT
 COPY ONTO THE AC AND BOILER PIPING LAYOUT PLANS. PLEASE
 PROVIDE COMPLETE PLANS SHOWING ROOMS AND SPACES,
 EXTERIOR PERIMETERS ETC.
 2) THE REQUESTED AC COOLING AND HEATING LOAD
 CALCULATIONS WERE NOT SUBMITTED AS WAS STATED IN THE
 NARRATIVE RESPONSE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By ccole Date 2015-09-14 Time 11:13 Rev Time 0.00
Received By ccole Date 2015-09-14 Time 11:13 Sent To  
Notes
2015-09-14 11:35:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090106
 9/14/15
  
 1) A NEW DX SPLIT AC SYSTEM IS SHOWN ON THE PLANS-
 PLEASE REVISE NEW WORK NOTE #1 ON SHEET M2 INDICATING
 REBALANCING AN EXISTING RTU.
 2) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION
 AND PROVIDE AC COOLING AND HEATING CALCULATIONS:
 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HWB-1 HOT
 WATER BOILER.
 4) PLEASE SHOW THE LOCATION OF THE RFM-1 MANIFOLD AS
 SHOWN IN THE RADIANT SCHEDULE.
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS FOR THE NEW AHU- REFER TO SECTION 307 FBC-14
 MECHANICAL.
 6) PROVIDE PIPE PROTECTION DETAILS FOR THE HOT WATER
 PIPING. INDICATE THE TYPE AND THICKNESS OF CONDUIT AND
 SLEEVING TO BE USED FOR THE UNDERGROUND/UNDERSLAB
 INSTALLATION- REFER TO SECTIONS 305.1.1 FBC-14
 PLUMBING.
 7) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR
 THE HOT WATER PIPING- REFER TO SECTION 306.3 FBC-14
 PLUMBING.
 8) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE PEX PIPING,
 AND FOAM INSULATION.
 9) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR
 MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA
 DEPARTMENT DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
 10) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND SHOW COMPLIANCE: SHUTOFF DAMPER
 CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 EXCEPTIONS:
 1. GRAVITY DAMPERS SHALL BE PERMITTED IN BUILDINGS LESS
 THAN THREE STORIES IN HEIGHT.
 2. GRAVITY DAMPERS SHALL BE PERMITTED FOR BUILDINGS OF
 ANY HEIGHT LOCATED IN CLIMATE ZONES 1, 2 AND 3.
 3. GRAVITY DAMPERS SHALL BE PERMITTED FOR OUTSIDE AIR
 INTAKE OR EXHAUST AIRFLOWS OF 300 CFM (0.14 M3/S) OR
 LESS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-05-20 Cont ID  
Sent By tklarge Date 2016-05-20 Time 15:24 Rev Time 0.00
Received By tklarge Date 2016-05-20 Time 03:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-14 Cont ID  
Sent By tklarge Date 2016-04-14 Time 13:28 Rev Time 0.00
Received By tklarge Date 2016-04-14 Time 13:28 Sent To  
Notes
2016-04-14 13:35:371) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE
 MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS
 COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT
 OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE
 ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS
 STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS
 REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES
 SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS
 REQUIREMENT. THERE WAS NO DOCUMENT IN THE RESUBMITTAL
 PACKAGE SHOWING ADDITIONAL SANITARY FACILITIES.
 2) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE
 AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER
 SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC.
 454.1.6.5.3.2. THIS WAS ANSWERED IN THE NARRATIVE BUT I
 DID NOT SEE WHERE THIS NOTE WAS PLACED ON THE PLANS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-17 Cont ID  
Sent By tklarge Date 2016-02-17 Time 12:12 Rev Time 0.00
Received By tklarge Date 2016-02-11 Time 04:37 Sent To  
Notes
2016-02-11 06:34:271) SUBMIT THE OCCUPANT LOAD FOR THIS SPACE SINCE THE
 OCCUPANCY HAS BEEN IDENTIFIED. COMPLY WITH 2014 FBC
 TABLE .1004.1.2.
 2) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE
 MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS
 COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT
 OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE
 ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS
 STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS
 REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES
 SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS
 REQUIREMENT.
 3) HOT/TEMPERED WATER IS REQUIRED TO THE LAVATORY. SHOW
 THIS ON THE WATER PIPING RISER.2014 FPC SEC. 607.1.
 4) SHT. A-400 - DETAILS #1 & # 3 THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014
 FBC-ACCESS. SEC. 609.4.
 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC.307.2. AN OPTIONAL SKIRT MAY BE
 REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES.
 6) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE
 AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER
 SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC.
 454.1.6.5.3.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By tklarge Date 2015-09-11 Time 10:20 Rev Time 0.00
Received By tklarge Date 2015-09-11 Time 09:09 Sent To  
Notes
2015-09-11 09:45:071) SHT. A-001 - CODE INFORMATION - THE PLANS REFERENCE
 THE 2010 FBC. THE CODES IN EFFECT ARE THE 2014
 EDITIONS. REVISE THE NOTES.
 2) CLARIFY AS TO HOW THIS PROJECT CAN BE CLASSIFIED AS
 A "U" OCCUPANCY WHEN IT IS A PUBLIC EXHIBIT LOCATED IN
 A ZOO. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC CHAPTER
 3.
 3) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE WATER
 FILTRATION SYSTEM. SUBMIT MANUF. SPECS FOR THE MAIN
 DRAIN GRATES, THE PUMP, HEAT PUMP, AND THE OZONE
 SYSTEM. SHOW ALL PIPE SIZES. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A BACKFLOW PREVVENTION DEVICE IS REQD. ON THE WATER
 SUPPLY PER THE CWPB UTILITIES DEPT. CROSS CONNECTION
 CONTROL MANUAL.
 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR
 THE INSTANTANEOUS WATER HEATER.
 6) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQD. PER THE
 2014 FPC TABLE 403.1 FOOTNOTE # (E) & 2014
 FBC-ACCESSIBILITY SEC. 211.2.
 7) EXPLAIN THE PURPOSE OF THE FLOOR SINK AND THE FLOOR
 DRAIN IN THE POOL. THEY CANNOT BE USED TO DRAIN THE
 POOL. DISCHARGE TO THE SANITARY SYSTEM SHALL BE THROUGH
 AN AIR GAP.2014 FBC SEC. 454.1.6.5.15.
 8) PROVIDE DETAILS FOR MAKEUP WATER. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-02-10 Cont ID  
Sent By jwitmer Date 2016-02-10 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2016-02-10 Time 06:15 Sent To  
Notes
2016-02-10 06:16:25THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE
 PRODUCT APPROVAL AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS.
 PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHT REPAIR OR REPLACEMENT?
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-09-27 Time 07:02 Sent To  
Notes
2015-09-27 07:53:59NO ROOFING PRODUCT APPROVAL WAS SUBMITTED THIS REVIEW.

Review Stop Z ZONING
Rev No 4 Status P Date 2016-05-24 Cont ID  
Sent By jroach Date 2016-05-24 Time 11:13 Rev Time 0.00
Received By jroach Date 2016-05-24 Time 11:13 Sent To  
Notes
2016-05-24 11:14:11ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.24.2016
 PERMIT NO.: 15090106
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: REPTILE RENOVATIONS (WHITE ALLIGATOR)
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-04-12 Cont ID  
Sent By jroach Date 2016-04-12 Time 12:26 Rev Time 0.00
Received By jroach Date 2016-04-12 Time 12:26 Sent To  
Notes
2016-04-12 12:27:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.12.2016
 PERMIT NO.: 15090106
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: REPTILE RENOVATIONS (WHITE ALLIGATOR)
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-14 Cont ID  
Sent By jroach Date 2016-03-14 Time 14:57 Rev Time 0.00
Received By jroach Date 2016-03-14 Time 14:57 Sent To  
Notes
2016-03-14 14:58:04PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By jroach Date 2015-10-05 Time 14:11 Rev Time 0.00
Received By jroach Date 2015-10-07 Time 13:30 Sent To  
Notes
2015-10-07 13:31:42PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  
2015-09-10 12:38:159/10/11