Plan Review Details - Permit 15090106
Plan Review Stops For Permit 15090106 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2016-05-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-05-19 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-05-19 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-04-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-04-11 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-04-11 |
Time |
16:01 |
Sent To |
|
|
Notes |
2016-04-11 16:52:56 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090106 | | ADD: 1301 SUMMIT BLVD. | | WHITE ALLIGATOR EXHIBIT | | CONT: GAST CONSTRUCTION | | TEL: (321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: MON. APRIL 11/ 2016 | | ACTION: DENIED | | | | 1-2) COMPLIED. | | | | 3) 3RD REQUEST. SEMI-COMPLIED. THE WHITE ALLIGATOR | | EXHIBIT BUILDING, VIEWING AREA AND RESTROOM . THE SHEET | | A101 SHOWS THE FINISH FLOOR OF THE WHITE ALLIGATOR | | EXHIBIT (RESTROOM) AT A HEIGHT OF 13.15 FT. NGVD-1929. | | THERE ARE NO FINISH FLOOR HEIGHT FOR THE EXHIBIT FLOOR | | VIEWING AREAS NOR THE EQUIPMENT SLAB. UPDATED 4/15/16. | | JW | | | | 5) COMPLIED.. ALTERRA SOILS ENGINEERING REPORT. UPDATED | | 4/15/16 JW | | | | 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES. | | | | 7A-7B) COMPLIED. 107.3. DEFERRED SUBMITTALS THE | | DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE PRODUCT | | APPROVAL AFTER PERMIT ISSUANCE. 2010 FLORIDA BUILDING | | CODE W 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2 | | DEFERRED SUBMITTALS. | | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3. | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
|
Date |
2016-02-10 |
Time |
06:30 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-10 |
Time |
05:56 |
Sent To |
|
|
Notes |
2016-02-10 06:31:52 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090106 | | ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR | | EXHIBIT. | | CONT: GAST CONSTRUCTION | | TEL: ( 321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: WED. FEB. 10/ 2016 | | ACTION: DENIED | | | | 1-2) COMPLIED | | | | 3) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE | | CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND | | SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300 | | SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED | | FLOOR ELEVATION ARE TO BE SET, INCLUDING THE UPPER AND | | LOWER POND LEVELS. THE PONDS SET AT OR BELOW BFE WOULD | | NEED ENGINEERING OR A HYDROSTATIC RELIEF VALVE. | | | | PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF | | STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD | | ZONE. FLOOD ZONE CERTIFICATES FBC BUILDING 1612 AND | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | ADDITIONAL 6 INCHES OF ELEVATION. FINISH FLOOR | | ELEVATION OF 12 FT. - | | 6 INCHES OR HIGHER. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS | | A/C PADS OR OTHER SLABS FOR GENERATORS | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | JULY 31/2015 | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF | | THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE | | PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE | | ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY | | CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS: | | SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF | | REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO | | A STRUCTURE, TAKING PLACE DURING THE LIFE OF A | | STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR | | EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE | | STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE | | THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START | | OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF | | DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE | | OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, | | "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN | | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR | | OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, | | WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL | | DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL | | IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT | | OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, | | SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO | | ENSURE SAFE LIVING CONDITIONS. | | | | SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION. | | (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION | | OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL, | | INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL | | EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT, | | ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE | | FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND | | SANITARY FACILITIES, BE FLOOD-PROOFED SO THAT BELOW SIX | | INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS | | WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE | | PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING | | THE CAPABILITY OF RESISTING HYDROSTATIC AND | | HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A | | REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL | | CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE | | SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE | | CITY ENGINEER. | | | | NOTE IF THE EXISTING STRUCTURE IS BELOW THE BASE FLOOD | | ELEVATION OF 12 FT. 6 INCHES AND SUBSTANTIAL | | IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF | | THE STRUCTURE AND THE OPTION IS TO INSTALL FLOOD VENTS | | TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE | | FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK | | RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSERS WILL | | NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND | | FLOOD ELEVATIONS ARE REQUIRED. | | | | 4) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM | | SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A | | QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE | | REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT | | REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE | | WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE | | SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN | | SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS | | REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING | | CAPACITY OF THE SOILS WILL BE. | | | | 5) COMPLIED. | | | | 6-7) THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE | | PRODUCT APPROVAL AFTER PERMIT ISSUANCE. | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. | | PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. 2014 | | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF | | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | (F) SKYLIGHT REPAIR OR REPLACEMENT? | | | | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 8) NEW COMMENT: SHEET S3.0 INDICATES POOLS BY OTHERS, A | | SEPARATE PERMIT AND PLANS WILL BE REQUIRED. | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-09-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-09-27 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-09-27 |
Time |
07:02 |
Sent To |
|
|
Notes |
2015-09-27 07:49:01 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090106 | | ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR | | EXHIBIT. | | CONT: CAG CONSTRUCTION | | TEL: ( 321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SUN. SEPT. 27/ 2015 | | ACTION: DENIED | | | | 1) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED | | UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR | | AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014 | | FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE. | | | | 2) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE | | AS U- OCCUPANCY (LIVESTOCK SHELTER) , IT WOULD APPEAR | | SINCE THE PUBLIC STOPS AND VIEWS THE VARIOUS DISPLAYS | | THE OCCUPANCY WOULD BE IN LINE OF A MUSEUM OR AN A3 | | OCCUPANCY. THE PUBLIC WOULD NOT BE GOING AROUND IN A | | LIVE STOCK SHELTER VIEWING A DISPLAY. | | | | 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION | | OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD | | ZONE. FLOOD ZONE CERTIFICATES | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH | | FLOOR ELEVATION OF 12 FT. - | | 6 INCHES OR HIGHER. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS | | A/C PADS OR OTHER SLABS FOR GENERATORS | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | JULY 31/2015 | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF | | THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE | | PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE | | ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY | | CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS: | | SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF | | REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO | | A STRUCTURE, TAKING PLACE DURING THE LIFE OF A | | STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR | | EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE | | STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE | | THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START | | OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF | | DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE | | OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, | | "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN | | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR | | OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, | | WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL | | DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL | | IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT | | OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, | | SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO | | ENSURE SAFE LIVING CONDITIONS. | | | | SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION. | | (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION | | OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL, | | INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL | | EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT, | | ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE | | FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND | | SANITARY FACILITIES, BE FLOODPROOFED SO THAT BELOW SIX | | INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS | | WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE | | PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING | | THE CAPABILITY OF RESISTING HYDROSTATIC AND | | HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A | | REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL | | CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE | | SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE | | CITY ENGINEER. | | | | NOTE IF THE EXISITNG STRUCTURE IS BELOW THE BASE FLOOD | | ELEVATION OF 12 FT. 6 INCHES AND SUBSTANIAL | | IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF | | THE STRUCTURE ANOTHE OPTION IS TO INSTALL FLOOD VENTS | | TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE | | FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK | | RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSORS WILL | | NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND | | FLOOD ELEVATIONS ARE REQUIED. | | | | 4) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS | | INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION | | THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY. | | THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. | | 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS | | ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY | | OF THE SOILS WILL BE. | | | | 5) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10, | | EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT | | SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED | | AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED | | PRESSURES ARE BLANK!!!!!!!!!!! | | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | STRUCTURE: | | | | 5.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND | | GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND | | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | 1609.3.1. | | | | 5.2.) RISK CATEGORY. | | | | 5.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | THAN ONE WIND EXPOSURE IS UTILIZED. | | | | 5.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | 5.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | M2). | | | | 6) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | (F) SKYLIGHT REPAIR OR REPLACEMENT? | | | | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-02-26 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-26 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-26 |
Time |
08:20 |
Sent To |
|
|
Notes |
2016-02-26 10:20:33 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | SATISFACTORILY CORRECTED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-11-19 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-19 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-11-19 |
Time |
09:09 |
Sent To |
I |
|
Notes |
2015-11-19 10:25:26 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | 1. THE CODE INFORMATION BLOCK ON THE FRONT SHEET | | REFERENCES NON APPLICABLE OR NONEXISTENT CODES. THE | | APPLICABLE CODES FOR THIS PROJECT ARE THE 5TH EDITION | | OF THE 2014 FBC AND THE 2011 EDITION OF THE NEC. | | 2. NEC 110.16 REQUIRES THAT THE PANELBOARDS BE MARKED | | WITH THE ARC-FLASH HAZARD WARNING LABELS. | | 3. NEC 406.9(B) STATES THAT ALL 15 - 20 AMP RECEPTACLES | | INSTALLED IN WET LOCATIONS SHALL IN ADDITION TO THE | | IN-USE TYPE COVER BE LISTED FOR THE PURPOSE AS | | WEATHER-RESISTANT. TYPE. | | 4. NEC 408.4(B) ALL PANELS SHALL BE MARKED TO INDICATE | | THE LOCATION OF THE SOURCE OF POWER. | | 5. NEC 422.52 REQUIRES THAT ELECTRIC WATER COOLERS BE | | CONNECTED TO A GFCI PROTECTED OUTLET. | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED DEFICIENCIES. | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2016-05-19 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-05-19 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-05-19 |
Time |
13:18 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2016-04-07 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2016-04-07 |
Time |
09:00 |
Sent To |
|
|
Notes |
2016-04-07 09:03:43 | 1301 SUMMIT BOULEVARD - ALLIGATOR EXHIBIT | | PERMIT #15090106 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLAN INDICATES THIS PROJECT IS A LEVEL 3 ALTERATION | | AFFECTING OVER 50% OF THE EXISTING BUILDING AREA; | | THEREFORE, PER NFPA 101 SECTION 43.5.2.3 WHERE THE | | TOTAL AREA OF ALL THE REHABILITATION WORK AREAS | | INCLUDED IN A MODIFICATION EXCEEDS 50 PERCENT OF THE | | AREA OF THE BUILDING, THE WORK SHALL BE CONSIDERED AS A | | RECONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS | | OF SECTION 43.6 FOR THE APPLICABLE OCCUPANCY. | | 101-43.6.4.2 ON ANY STORY WITH REHABILITATION WORK | | AREAS INVOLVING OVER 50 PERCENT OF THE AREA OF THE | | STORY, A SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT | | THE STORY IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER | | SECTIONS OF THIS CODE APPLICABLE TO NEW CONSTRUCTION | | FOR THE OCCUPANCY. | | | | PER NFPA 150 STRUCTURES HOUSING TYPE A ANIMALS | | (REPTILES) SHALL BE PROTECTED THROUGHOUT WITH AN | | AUTOMATIC SPRINKLER SYSTEM. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
Sent By |
rlindow |
Date |
2016-02-09 |
Time |
|
Rev Time |
0.00 |
Received By |
rlindow |
Date |
2016-02-09 |
Time |
|
Sent To |
|
|
Notes |
2016-02-09 07:36:52 | PASSED WITH PROVISO: ADDITION OF NEW BATHROOM SHALL NOT | | INTERFERE WITH EXISTING MEANS OF EGRESS. LINDOW 2/9/16 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2015-09-09 |
|
|
Cont ID |
|
Sent By |
|
Date |
2015-09-09 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2015-09-09 |
Time |
|
Sent To |
|
|
Notes |
2015-09-09 14:32:27 | PASSED WITH PROVISO: ADDITION OF NEW BATHROOM SHALL NOT | | INTERFERE WITH EXISTING MEANS OF EGRESS. LINDOW 9/9/15 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2016-05-24 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-05-24 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-05-13 |
Time |
17:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-04-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-04-14 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-25 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-03-14 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-03-14 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-02-02 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-11-19 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-19 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-03 |
Time |
13:38 |
Sent To |
|
|
Notes |
2015-11-19 10:33:01 | 11/19/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2016-04-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-04-07 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-04-07 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-02-10 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-02-10 |
Time |
11:21 |
Sent To |
|
|
Notes |
2016-02-10 11:57:30 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15090106 | | 2/10/16 | | | | 1) SHEET M2: IT APPEARS THE FLOOR PLAN DRAWINGS DID NOT | | COPY ONTO THE AC AND BOILER PIPING LAYOUT PLANS. PLEASE | | PROVIDE COMPLETE PLANS SHOWING ROOMS AND SPACES, | | EXTERIOR PERIMETERS ETC. | | 2) THE REQUESTED AC COOLING AND HEATING LOAD | | CALCULATIONS WERE NOT SUBMITTED AS WAS STATED IN THE | | NARRATIVE RESPONSE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-09-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-09-14 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-09-14 |
Time |
11:13 |
Sent To |
|
|
Notes |
2015-09-14 11:35:42 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15090106 | | 9/14/15 | | | | 1) A NEW DX SPLIT AC SYSTEM IS SHOWN ON THE PLANS- | | PLEASE REVISE NEW WORK NOTE #1 ON SHEET M2 INDICATING | | REBALANCING AN EXISTING RTU. | | 2) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION | | AND PROVIDE AC COOLING AND HEATING CALCULATIONS: | | CALCULATION OF HEATING AND COOLING LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HWB-1 HOT | | WATER BOILER. | | 4) PLEASE SHOW THE LOCATION OF THE RFM-1 MANIFOLD AS | | SHOWN IN THE RADIANT SCHEDULE. | | 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL | | PLANS FOR THE NEW AHU- REFER TO SECTION 307 FBC-14 | | MECHANICAL. | | 6) PROVIDE PIPE PROTECTION DETAILS FOR THE HOT WATER | | PIPING. INDICATE THE TYPE AND THICKNESS OF CONDUIT AND | | SLEEVING TO BE USED FOR THE UNDERGROUND/UNDERSLAB | | INSTALLATION- REFER TO SECTIONS 305.1.1 FBC-14 | | PLUMBING. | | 7) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR | | THE HOT WATER PIPING- REFER TO SECTION 306.3 FBC-14 | | PLUMBING. | | 8) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE PEX PIPING, | | AND FOAM INSULATION. | | 9) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR | | MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA | | DEPARTMENT DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3. | | 10) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY | | CONSERVATION AND SHOW COMPLIANCE: SHUTOFF DAMPER | | CONTROLS. | | BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE | | EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY | | SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. | | EXCEPTIONS: | | 1. GRAVITY DAMPERS SHALL BE PERMITTED IN BUILDINGS LESS | | THAN THREE STORIES IN HEIGHT. | | 2. GRAVITY DAMPERS SHALL BE PERMITTED FOR BUILDINGS OF | | ANY HEIGHT LOCATED IN CLIMATE ZONES 1, 2 AND 3. | | 3. GRAVITY DAMPERS SHALL BE PERMITTED FOR OUTSIDE AIR | | INTAKE OR EXHAUST AIRFLOWS OF 300 CFM (0.14 M3/S) OR | | LESS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2016-05-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-05-20 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-05-20 |
Time |
03:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2016-04-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-04-14 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-04-14 |
Time |
13:28 |
Sent To |
|
|
Notes |
2016-04-14 13:35:37 | 1) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE | | MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS | | COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT | | OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE | | ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS | | STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS | | REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE | | LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES | | SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS | | REQUIREMENT. THERE WAS NO DOCUMENT IN THE RESUBMITTAL | | PACKAGE SHOWING ADDITIONAL SANITARY FACILITIES. | | 2) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE | | AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER | | SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC. | | 454.1.6.5.3.2. THIS WAS ANSWERED IN THE NARRATIVE BUT I | | DID NOT SEE WHERE THIS NOTE WAS PLACED ON THE PLANS. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-02-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-02-17 |
Time |
12:12 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-02-11 |
Time |
04:37 |
Sent To |
|
|
Notes |
2016-02-11 06:34:27 | 1) SUBMIT THE OCCUPANT LOAD FOR THIS SPACE SINCE THE | | OCCUPANCY HAS BEEN IDENTIFIED. COMPLY WITH 2014 FBC | | TABLE .1004.1.2. | | 2) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE | | MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS | | COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT | | OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE | | ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS | | STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS | | REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE | | LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES | | SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS | | REQUIREMENT. | | 3) HOT/TEMPERED WATER IS REQUIRED TO THE LAVATORY. SHOW | | THIS ON THE WATER PIPING RISER.2014 FPC SEC. 607.1. | | 4) SHT. A-400 - DETAILS #1 & # 3 THE GRAB BARS SHALL BE | | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014 | | FBC-ACCESS. SEC. 609.4. | | 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 | | FBC-ACCESS. SEC.307.2. AN OPTIONAL SKIRT MAY BE | | REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES. | | 6) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE | | AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER | | SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC. | | 454.1.6.5.3.2. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-09-11 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-09-11 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-11 |
Time |
09:09 |
Sent To |
|
|
Notes |
2015-09-11 09:45:07 | 1) SHT. A-001 - CODE INFORMATION - THE PLANS REFERENCE | | THE 2010 FBC. THE CODES IN EFFECT ARE THE 2014 | | EDITIONS. REVISE THE NOTES. | | 2) CLARIFY AS TO HOW THIS PROJECT CAN BE CLASSIFIED AS | | A "U" OCCUPANCY WHEN IT IS A PUBLIC EXHIBIT LOCATED IN | | A ZOO. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC CHAPTER | | 3. | | 3) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE WATER | | FILTRATION SYSTEM. SUBMIT MANUF. SPECS FOR THE MAIN | | DRAIN GRATES, THE PUMP, HEAT PUMP, AND THE OZONE | | SYSTEM. SHOW ALL PIPE SIZES. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 4) A BACKFLOW PREVVENTION DEVICE IS REQD. ON THE WATER | | SUPPLY PER THE CWPB UTILITIES DEPT. CROSS CONNECTION | | CONTROL MANUAL. | | 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR | | THE INSTANTANEOUS WATER HEATER. | | 6) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQD. PER THE | | 2014 FPC TABLE 403.1 FOOTNOTE # (E) & 2014 | | FBC-ACCESSIBILITY SEC. 211.2. | | 7) EXPLAIN THE PURPOSE OF THE FLOOR SINK AND THE FLOOR | | DRAIN IN THE POOL. THEY CANNOT BE USED TO DRAIN THE | | POOL. DISCHARGE TO THE SANITARY SYSTEM SHALL BE THROUGH | | AN AIR GAP.2014 FBC SEC. 454.1.6.5.15. | | 8) PROVIDE DETAILS FOR MAKEUP WATER. WPB AMEND. TO FBC | | SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
N |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-02-10 |
Time |
06:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-10 |
Time |
06:15 |
Sent To |
|
|
Notes |
2016-02-10 06:16:25 | THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE | | PRODUCT APPROVAL AFTER PERMIT ISSUANCE. | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. | | PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. 2014 | | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF | | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | PRODUCT APPROVALS: | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES | | (F) SKYLIGHT REPAIR OR REPLACEMENT? | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2015-09-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-09-27 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-09-27 |
Time |
07:02 |
Sent To |
|
|
Notes |
2015-09-27 07:53:59 | NO ROOFING PRODUCT APPROVAL WAS SUBMITTED THIS REVIEW. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2016-05-24 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-05-24 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-05-24 |
Time |
11:13 |
Sent To |
|
|
Notes |
2016-05-24 11:14:11 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 05.24.2016 | | PERMIT NO.: 15090106 | | ADDRESS: 1301 SUMMIT BOULEVARD | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: REPTILE RENOVATIONS (WHITE ALLIGATOR) | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-04-12 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-04-12 |
Time |
12:26 |
Sent To |
|
|
Notes |
2016-04-12 12:27:06 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 04.12.2016 | | PERMIT NO.: 15090106 | | ADDRESS: 1301 SUMMIT BOULEVARD | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: REPTILE RENOVATIONS (WHITE ALLIGATOR) | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-03-14 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-03-14 |
Time |
14:57 |
Sent To |
|
|
Notes |
2016-03-14 14:58:04 | PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-10-07 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2015-10-05 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2015-10-07 |
Time |
13:30 |
Sent To |
|
|
Notes |
2015-10-07 13:31:42 | PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | | 2015-09-10 12:38:15 | 9/10/11 |
|
|
|