Plan Review Details - Permit 15090101
Plan Review Stops For Permit 15090101 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2016-04-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-04-15 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-04-15 |
Time |
11:46 |
Sent To |
|
|
Notes |
2016-04-15 11:47:26 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090101 | | ADD: 1301 SUMMIT BLVD. | | PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING | | STRUCTURE | | CONT: GAST CONSTRUCTION | | TEL: (321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: FRI. APRIL 15/ 2016 | | ACTION: BUILDING PROVISO | | | | 1) THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE | | PRODUCT APPROVAL AFTER PERMIT ISSUANCE. | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. | | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-04-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-04-11 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-04-11 |
Time |
13:45 |
Sent To |
|
|
Notes |
2016-04-11 15:00:14 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090101 | | ADD: 1301 SUMMIT BLVD. | | PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING | | STRUCTURE | | CONT: GAST CONSTRUCTION | | TEL: (321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: MON. APRIL 11/ 2016 | | ACTION: DENIED | | | | 1-3) COMPLIED. | | | | 4) 3RD REQUEST. SEMI-COMPLIED. THE PANTHER BUILDING AND | | ELEVATION CERTIFICATE MATCH IN THE ELEVATION FINISH | | FLOOR HEIGHT OF 13.2.2 NGVD 1929. | | THERE IS A DISCREPANCY IN THE OTTER BUILDING BETWEEN | | THE PLANS SHEETS A-100, A-101 OF A FINISH FLOOR HEIGHT | | OF 12.5 FT. NGVD 1929 AND THE ELEVATION CERTIFICATE OF | | 13.15 FT. NGVD 1929. | | BOTH ELEVATION CERTIFICATES ARE DATED 2/24/2016. PLEASE | | NOTE ON THE ELEVATION CERTIFICATES THEY DO NOT IDENTIFY | | AS TO WHICH EXHIBIT/ BUILDING THEY ARE INTENDED. | | | | POINT OF CONCERN PERMIT 15090106 IS FOR THE WHITE | | ALLIGATOR EXHIBIT. SHEET A-101 SHOWS THE FINISH FLOOR | | AT ELEVATION 13.15 NGVD LINE A3 DESCRIBES LOCATION AS | | THE RESTROOM BUILDING-PANTHER/ IBIS EXHIBIT. WE NEED | | ELEVATION CERTIFICATES FOR THE WHITE ALAGATOR EXHIBIT | | AS WELL. | | | | 5) 3RD REQUEST. SEMI-COMPLIED. ALTERRA SOILS | | ENGINEERING REPORT WAS SUBMITTED BUT DOES NOT HAVE THE | | SHOP DRAWING STAMP OF THE DESIGNER OF RECORD REVIEWED, | | OR REVIEWED WITH COMMENTS. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC... | | 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS | | ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY | | OF THE SOILS WILL BE. | | SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS INDICATES | | THERE IS TO HAVE A SOILS REPORT INVESTIGATION THIS SITE | | HAS QUESTIONABLE SOILS IN BEARING CAPACITY. THIS REVIEW | | CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B | | 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO | | PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF THE | | SOILS WILL BE. | | | | 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES. | | | | 7A-7B) COMPLIED. THE DESIGNER OF RECORD HAS ELECTED TO | | SUBMIT THE PRODUCT APPROVAL AFTER PERMIT ISSUANCE. | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. | | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | | | 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3. | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-02-10 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-10 |
Time |
09:51 |
Sent To |
|
|
Notes |
2016-02-10 10:37:13 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090101 | | ADD: 1301 SUMMIT BLVD. | | PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING | | STRUCTURE | | CONT: GAST CONSTRUCTION | | TEL: (321)622-6900 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SUN. SEPT. 27/ 2015 | | ACTION: DENIED | | | | 1-3) COMPLIED. | | | | 4) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE | | CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND | | SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300 | | SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED | | FLOOR ELEVATION ARE TO BE SET. | | PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF | | STRUCTURES; THE PROPERTY IS LOCATED IN AN A-7 FLOOD | | ZONE. FLOOD ZONE CERTIFICATES | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH | | FLOOR ELEVATION OF 12 FT. - | | 6 INCHES OR HIGHER. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS | | A/C PADS OR OTHER SLABS FOR GENERATORS | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | JULY 31/2015 | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | 5) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM | | SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A | | QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE | | REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT | | REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE | | WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE | | SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN | | SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS | | REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING | | CAPACITY OF THE SOILS WILL BE. | | SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS INDICATES | | THERE IS TO HAVE A SOILS REPORT INVESTIGATION THIS SITE | | HAS QUESTIONABLE SOILS IN BEARING CAPACITY. THIS REVIEW | | CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B | | 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO | | PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF THE | | SOILS WILL BE. | | | | 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES. | | | | 7A-7B) COMPLIED. THE DESIGNER OF RECORD HAS ELECTED TO | | SUBMIT THE PRODUCT APPROVAL AFTER PERMIT ISSUANCE. | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. | | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | | | 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3. | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-09-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-09-27 |
Time |
07:02 |
Rev Time |
|
Received By |
jwitmer |
Date |
2015-09-26 |
Time |
15:31 |
Sent To |
|
|
Notes |
2015-09-26 16:12:54 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15090101 | | ADD: 1301 SUMMIT BLVD./ PANTHER RENOVATIONS | | CONT: TBD | | TEL: ( ????????? | | E-MAIL: ????????? | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SUN. SEPT. 27/ 2015 | | ACTION: DENIED | | | | 1) THE PERMIT APPLICATION UNDER THE HEADING OF VALUE, | | NOT FILED IN. 108.3* BUILDING PERMIT VALUATION. IF, IN | | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED | | VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | CONGRESS. | | | | 2) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED | | UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR | | AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014 | | FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE. | | | | 3) THE PERMIT APPLICATION INDICATES THIS PERMIT IS FOR | | ONLY THE PANTHER RENOVATIONS. BOTH THE ARCHITECTURAL | | AND STRUCTURAL SHEETS SHOW NEW BUILDING FOUNDATIONS AND | | STRUCTURAL SHEETS FOR THIS BUILDING (S-1) AND OTHER | | BUILDINGS SEE SHEET (S-4- OTTER HOUSING?) . PLEASE NOTE | | ON THE PERMIT APPLICATION IF THESE OTHER STRUCTURES ARE | | TO BE INCLUDED UNDER THE SCOPE OF WORK TO BE COMPLETED | | UNDER THIS PERMIT. IF THESE OTHER SHEETS ARE NOT | | INCLUDED UNDER THE SCOPE OF WORK, PLEAE EITHER VOID THE | | SHEETS, "X" OUT THE DETAILS NOT COVERED UNDER THIS | | PERMIT OR REMOVE THE SHEETS IN THERE INTIRETY.107.2.1.3 | | ADDITIONAL INFORMATION IS REQUIRED. | | | | 4) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION | | OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD | | ZONE. FLOOD ZONE CERTIFICATES | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH | | FLOOR ELEVATION OF 12 FT. - | | 6 INCHES OR HIGHER. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS | | A/C PADS OR OTHER SLABS FOR GENERATORS | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | JULY 31/2015 | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | 5) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS | | INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION | | THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY. | | THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. | | 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS | | ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY | | OF THE SOILS WILL BE. | | | | 6) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10, | | EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT | | SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED | | AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED | | PRESSURES ARE BLANK!!!!!!!!!!! | | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | STRUCTURE: | | | | 6.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND | | GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND | | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | 1609.3.1. | | | | 6.2.) RISK CATEGORY. | | | | 6.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | THAN ONE WIND EXPOSURE IS UTILIZED. | | | | 6.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | 6.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | M2). | | | | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | | | 8) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE | | AS S-1 STORAGE, IT WOULD APPEAR SINCE THE PUBLIC STOPS | | AND VIEWS THE VARIOUS DISPLAYS THE OCCUPANCY WOULD BE | | IN LINE OF A MUSEUM OR AN A3 OCCUPANCY. THE PUBLIC | | WOULD NOT BEGOING AROUND IN A WAREHOUSE VIEWING | | DISPLAYS. | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-03-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-03-15 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-03-15 |
Time |
10:54 |
Sent To |
I |
|
Notes |
2016-03-15 14:14:55 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | SATISFACTORILY CORRECTED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-11-05 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-05 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-11-05 |
Time |
09:03 |
Sent To |
I |
|
Notes |
2015-11-05 09:34:00 | THE PLANS WERE INADVERTENTLY/ERRONEOUSLY STAMPED AS | | APPROVED, BUT THE BELOW MENTIONED ITEMS SHALL BE | | CORRECTED AND PLANS RE-SUBMITTED FOR AN APPROVAL. | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION | | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION | | OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE | | AND BELOW ARE THE DEFICIENCIES NOTED. | | THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING | | CORRECTION: | | | | 1. PER NEC 110.16 ALL ELECTRICAL EQUIPMENT AND PANELS | | SHALL BE LABELED WITH THE ARC-FLASH HAZARD WARNING | | LABEL. | | 2. THE QUOTED 2010 EDITION OF THE ELECTRICAL CODE DOES | | NOT EXIST; THEREFORE COMPLIANCE WITH SAME IS NOT | | POSSIBLE. THE CURRENT ELECTRICAL CODE IN EFFECT IS THE | | 2011 EDITION OF THE NEC. | | 3. PER NEC 406.9(B) IN ADDITION TO THE WEATHER-PROOF | | COVERS ALL 15 ? 20 AMP 120 -240 VOLT NON-LOCKING | | RECEPTACLES INSTALLED IN WET LOCATIONS SHALL BE LISTED | | ?WR? WEATHER RESISTANT. | | 4. ALL LIGHTING HAS TO COMPLY WITH THE REQUIREMENTS OF | | SECTION C405 OF THE FBC-ENERGY CONSERVATION CODE. | | 5. NEC 408.4(B) ALL PANEL SHALL BE MARKED INDICATING | | THE LOCATION OF THEIR SOURCE OF POWER (DISCONNECT). | | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | FOR ANOTHER REVIEW. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2016-04-07 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2016-04-07 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2016-02-09 |
|
|
Cont ID |
|
Sent By |
rlindow |
Date |
2016-02-09 |
Time |
|
Rev Time |
0.00 |
Received By |
rlindow |
Date |
2016-02-09 |
Time |
|
Sent To |
|
|
Notes |
2016-02-09 09:17:31 | | | | | PREVIOUS COMMENTS OF AUTOMATIC FIRE SPRINKLER SYSTEM | | NOT PROVIDED HAVE NOT BEEN ADDRESSED. RLINDOW, 2/9/16 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-09-09 |
|
|
Cont ID |
|
Sent By |
|
Date |
2015-09-09 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2015-09-09 |
Time |
|
Sent To |
|
|
Notes |
2015-09-09 13:58:23 | PANTHER HOUSING FACILITY IS NOT PROVIDED WITH AUTOMATIC | | FIRE SPRINKLER SYSTEM. LINDOW 9/9/15 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-04-12 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-03-25 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-03-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-03-15 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-02 |
Time |
10:55 |
Sent To |
|
|
Notes |
2016-03-15 14:18:58 | 3/15/16 PASSED ELECTRICAL REVIEW BUT FAILED OTHER TRADE | | REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE | | DENIED DRAWER "G". MA | 2016-02-03 10:55:32 | C23 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-11-05 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-05 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-03 |
Time |
13:32 |
Sent To |
|
|
Notes |
2015-11-05 09:59:46 | 11/5/15 FAILED THE ELECTRICAL REVIEW. CONTRACTOR | | NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-02-10 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-02-10 |
Time |
12:20 |
Sent To |
|
|
Notes |
2016-02-10 12:27:19 | MECHANICAL PROVISIOS; | | PERMIT #15090101 | | 2/10/16 | | | | 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | INSTRUCTIONS FOR THE UPONOR PEX CHILLER PIPING SHALL BE | | REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR, AND | | ALL SITE AT TIME OF INSPECTION. | | 2) THE MIAMI-DADE NOA AND/OR FLORIDA PRODUCT APPROVAL | | FOR THE LOUVERS SHALL BE REVIEWED AND APPROVED WITH | | SIGNATURE BY THE EOR AND SUBMITTED TO THE BUILDING | | DEPARTMENT PRIOR TO 1ST INSPECTION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-09-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-09-11 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-09-11 |
Time |
12:31 |
Sent To |
|
|
Notes |
2015-09-11 12:57:17 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15090101 | | 9/11/15 | | | | 1) PROVIDE PIPE PROTECTION DETAILS FOR THE CHILLED | | WATER PIPING. INDICATE THE TYPE AND THICKNESS OF | | CONDUIT AND SLEEVING TO BE USED FOR THE | | UNDERGROUND/UNDERSLAB INSTALLATION- REFER TO SECTIONS | | 305.1.1 FBC-14 PLUMBING. | | 2) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR | | THE CHILLED WATER PIPING- REFER TO SECTION 306.3 FBC-14 | | PLUMBING. | | 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CHILLER PAD, AND WIND LOAD TIE DOWN ENGINEERING FOR | | MOUNTING THE CHILLER TO THE SLAB- SEE SECTION 301.15 | | MECHANICAL. | | 4) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE CHILLER AND | | THE UPONOR TYPE A PEX PIPING, AND FOAM INSULATION. | | 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | ZOOKEEPER AREAS IN THE PANTHER AND OTTER BUILDINGS- | | REFER TO TABLE 403.3 FBC-14 MECHANICAL. INDICATE HOW | | THE DESIGN USING LOUVERED VENT OPENINGS IS PROVIDING | | VENTILATION AIR FOR THOSE AREAS, AND INDICATE HOW THE | | VENT OPENINGS WERE SIZED. | | 6) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR | | MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA | | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-02-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-02-19 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-02-17 |
Time |
14:43 |
Sent To |
|
|
Notes |
2016-02-17 15:20:33 | WHERE ARE THE IRRIGATION PLANS? THEY WERE PART OF THE | | SET IN THE FIRST SUBMITTAL. 2014 FBC SEC. 107.2.1. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-09-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-09-25 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-24 |
Time |
06:48 |
Sent To |
|
|
Notes |
2015-09-24 06:52:16 | 1) SHT. A-001 - THE PLANS REFER TO THE 2010 FBC. THE | | CODE IN EFFECT IS THE 2014 FBC. REVISE NOTE. | | 2) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE | | IBIS/SPOONBILL WATER FEATURE. PIPING DIAGRAM SHALL | | INCLUDE SSUPPLY AND RETURN LINES, MAIN DRAINS, PUMP, | | PUMP CURVE, ETC. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SUBMIT MANUFACTURER SPEC SHEETS FOR THE MAIN DRAINS, | | THE PUMP, PUMP CURVE, ETC.WPB AMEND.TO FBC SEC. | | 107.2.1. | | 4) SHT. IR-1 - SHOWS 4 - 2 INCH LINES BY THE OVERHEAD | | PANTHER WALK BUT THEY ARE ALSO SHOWN AS 3/4 INCH LINES | | ON THE PLAN. CLARIFY. | | 5) SHT. IR-1 - THERE ARE A LOT OF IRRIGATION LINES ON | | THE PLAN THAT HAVE NO PIPE SIZES. AT THE VERY LEAST, | | SIZE THE MAN BRANCH LINES. | | 6) SHT. IR-2 - THE DETAILS AND PRINTED TEXT ARE VERY | | LIGHT AND ILLEGIBLE. SUBMIT A REVISED DRAWING THAT IS | | CLEAR IN TEXT AND DETAILS.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 7) SUBMIT AN ENLARGED FLOOR PLAN FOR THE NEW RESTROOM. | | THE RESTROOM SHALL BE FULLY ACCESSIBLE.2014 FBC - | | ACCESSIBILITY SEC.202.1, 213.1, 213.2. | | 8) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | NEW RESTROOM. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
N |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-02-10 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-10 |
Time |
10:37 |
Sent To |
|
|
Notes |
2016-02-10 10:38:28 | ROOFING PRODUCT APPROVALS DEFERRED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2015-09-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-09-27 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-09-27 |
Time |
06:16 |
Sent To |
|
|
Notes |
2015-09-27 07:10:16 | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED THIS | | REVIEW. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-04-12 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-04-12 |
Time |
12:08 |
Sent To |
|
|
Notes |
2016-04-12 12:09:51 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 04.12.2016 | | PERMIT NO.: 15090101 | | ADDRESS: 1301 SUMMIT BOULEVARD | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | | | 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE | | APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT | | APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS | | SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS | | WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-03-14 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-03-14 |
Time |
15:06 |
Sent To |
|
|
Notes |
2016-03-14 15:06:44 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 03.14.2016 | | PERMIT NO.: 15090101 | | ADDRESS: 1301 SUMMIT BOULEVARD | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS | | ___________________________________________ | | | | REVIEW STATUS: FAILED | | ___________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | | | 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE | | APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT | | APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS | | SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS | | WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | | | 9/10/11 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-10-07 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2015-10-07 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2015-10-07 |
Time |
13:33 |
Sent To |
|
|
Notes |
2015-10-07 13:36:08 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 10.07.2015 | | PERMIT NO.: 15090101 | | ADDRESS: 1301 SUMMIT BOULEVARD | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS | | ___________________________________________ | | | | REVIEW STATUS: FAILED | | ___________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING | | THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK | | MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT | | ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES | | COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING, | | WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE), | | WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED | | SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS | | COMPENSATION INSURANCE AS REQUIRED BY LAW, AND | | INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL | | INSURED. | | | | 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE | | APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT | | APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS | | SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS | | WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | | 2015-09-10 12:37:22 | 9/10/11 |
|
|
|