Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-04-15 Cont ID  
Sent By jwitmer Date 2016-04-15 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2016-04-15 Time 11:46 Sent To  
Notes
2016-04-15 11:47:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090101
 ADD: 1301 SUMMIT BLVD.
 PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING
 STRUCTURE
 CONT: GAST CONSTRUCTION
 TEL: (321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. APRIL 15/ 2016
 ACTION: BUILDING PROVISO
  
 1) THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE
 PRODUCT APPROVAL AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS.
 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2016-04-11 Time 13:45 Sent To  
Notes
2016-04-11 15:00:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090101
 ADD: 1301 SUMMIT BLVD.
 PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING
 STRUCTURE
 CONT: GAST CONSTRUCTION
 TEL: (321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. APRIL 11/ 2016
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 3RD REQUEST. SEMI-COMPLIED. THE PANTHER BUILDING AND
 ELEVATION CERTIFICATE MATCH IN THE ELEVATION FINISH
 FLOOR HEIGHT OF 13.2.2 NGVD 1929.
 THERE IS A DISCREPANCY IN THE OTTER BUILDING BETWEEN
 THE PLANS SHEETS A-100, A-101 OF A FINISH FLOOR HEIGHT
 OF 12.5 FT. NGVD 1929 AND THE ELEVATION CERTIFICATE OF
 13.15 FT. NGVD 1929.
 BOTH ELEVATION CERTIFICATES ARE DATED 2/24/2016. PLEASE
 NOTE ON THE ELEVATION CERTIFICATES THEY DO NOT IDENTIFY
 AS TO WHICH EXHIBIT/ BUILDING THEY ARE INTENDED.
  
 POINT OF CONCERN PERMIT 15090106 IS FOR THE WHITE
 ALLIGATOR EXHIBIT. SHEET A-101 SHOWS THE FINISH FLOOR
 AT ELEVATION 13.15 NGVD LINE A3 DESCRIBES LOCATION AS
 THE RESTROOM BUILDING-PANTHER/ IBIS EXHIBIT. WE NEED
 ELEVATION CERTIFICATES FOR THE WHITE ALAGATOR EXHIBIT
 AS WELL.
  
 5) 3RD REQUEST. SEMI-COMPLIED. ALTERRA SOILS
 ENGINEERING REPORT WAS SUBMITTED BUT DOES NOT HAVE THE
 SHOP DRAWING STAMP OF THE DESIGNER OF RECORD REVIEWED,
 OR REVIEWED WITH COMMENTS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS
 ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY
 OF THE SOILS WILL BE.
 SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS INDICATES
 THERE IS TO HAVE A SOILS REPORT INVESTIGATION THIS SITE
 HAS QUESTIONABLE SOILS IN BEARING CAPACITY. THIS REVIEW
 CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B
 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO
 PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF THE
 SOILS WILL BE.
  
 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES.
  
 7A-7B) COMPLIED. THE DESIGNER OF RECORD HAS ELECTED TO
 SUBMIT THE PRODUCT APPROVAL AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS.
 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-10 Cont ID  
Sent By jwitmer Date 2016-02-10 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2016-02-10 Time 09:51 Sent To  
Notes
2016-02-10 10:37:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090101
 ADD: 1301 SUMMIT BLVD.
 PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING
 STRUCTURE
 CONT: GAST CONSTRUCTION
 TEL: (321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. SEPT. 27/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE
 CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND
 SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300
 SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED
 FLOOR ELEVATION ARE TO BE SET.
 PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF
 STRUCTURES; THE PROPERTY IS LOCATED IN AN A-7 FLOOD
 ZONE. FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH
 FLOOR ELEVATION OF 12 FT. -
 6 INCHES OR HIGHER.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM
 SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A
 QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE
 REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT
 REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE
 WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE
 SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN
 SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS
 REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING
 CAPACITY OF THE SOILS WILL BE.
 SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS INDICATES
 THERE IS TO HAVE A SOILS REPORT INVESTIGATION THIS SITE
 HAS QUESTIONABLE SOILS IN BEARING CAPACITY. THIS REVIEW
 CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B
 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO
 PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF THE
 SOILS WILL BE.
  
 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES.
  
 7A-7B) COMPLIED. THE DESIGNER OF RECORD HAS ELECTED TO
 SUBMIT THE PRODUCT APPROVAL AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS.
 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 07:02 Rev Time  
Received By jwitmer Date 2015-09-26 Time 15:31 Sent To  
Notes
2015-09-26 16:12:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090101
 ADD: 1301 SUMMIT BLVD./ PANTHER RENOVATIONS
 CONT: TBD
 TEL: ( ?????????
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. SEPT. 27/ 2015
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE HEADING OF VALUE,
 NOT FILED IN. 108.3* BUILDING PERMIT VALUATION. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED
 UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR
 AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014
 FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE.
  
 3) THE PERMIT APPLICATION INDICATES THIS PERMIT IS FOR
 ONLY THE PANTHER RENOVATIONS. BOTH THE ARCHITECTURAL
 AND STRUCTURAL SHEETS SHOW NEW BUILDING FOUNDATIONS AND
 STRUCTURAL SHEETS FOR THIS BUILDING (S-1) AND OTHER
 BUILDINGS SEE SHEET (S-4- OTTER HOUSING?) . PLEASE NOTE
 ON THE PERMIT APPLICATION IF THESE OTHER STRUCTURES ARE
 TO BE INCLUDED UNDER THE SCOPE OF WORK TO BE COMPLETED
 UNDER THIS PERMIT. IF THESE OTHER SHEETS ARE NOT
 INCLUDED UNDER THE SCOPE OF WORK, PLEAE EITHER VOID THE
 SHEETS, "X" OUT THE DETAILS NOT COVERED UNDER THIS
 PERMIT OR REMOVE THE SHEETS IN THERE INTIRETY.107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION
 OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD
 ZONE. FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH
 FLOOR ELEVATION OF 12 FT. -
 6 INCHES OR HIGHER.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS
 INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION
 THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY.
 THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS
 ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY
 OF THE SOILS WILL BE.
  
 6) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10,
 EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT
 SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED
 AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED
 PRESSURES ARE BLANK!!!!!!!!!!!
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 6.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 6.2.) RISK CATEGORY.
  
 6.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 6.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 6.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 8) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE
 AS S-1 STORAGE, IT WOULD APPEAR SINCE THE PUBLIC STOPS
 AND VIEWS THE VARIOUS DISPLAYS THE OCCUPANCY WOULD BE
 IN LINE OF A MUSEUM OR AN A3 OCCUPANCY. THE PUBLIC
 WOULD NOT BEGOING AROUND IN A WAREHOUSE VIEWING
 DISPLAYS.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 14:14 Rev Time 0.00
Received By albarran Date 2016-03-15 Time 10:54 Sent To I
Notes
2016-03-15 14:14:55ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 09:33 Rev Time 0.00
Received By albarran Date 2015-11-05 Time 09:03 Sent To I
Notes
2015-11-05 09:34:00THE PLANS WERE INADVERTENTLY/ERRONEOUSLY STAMPED AS
 APPROVED, BUT THE BELOW MENTIONED ITEMS SHALL BE
 CORRECTED AND PLANS RE-SUBMITTED FOR AN APPROVAL.
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
 THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING
 CORRECTION:
  
 1. PER NEC 110.16 ALL ELECTRICAL EQUIPMENT AND PANELS
 SHALL BE LABELED WITH THE ARC-FLASH HAZARD WARNING
 LABEL.
 2. THE QUOTED 2010 EDITION OF THE ELECTRICAL CODE DOES
 NOT EXIST; THEREFORE COMPLIANCE WITH SAME IS NOT
 POSSIBLE. THE CURRENT ELECTRICAL CODE IN EFFECT IS THE
 2011 EDITION OF THE NEC.
 3. PER NEC 406.9(B) IN ADDITION TO THE WEATHER-PROOF
 COVERS ALL 15 ? 20 AMP 120 -240 VOLT NON-LOCKING
 RECEPTACLES INSTALLED IN WET LOCATIONS SHALL BE LISTED
 ?WR? WEATHER RESISTANT.
 4. ALL LIGHTING HAS TO COMPLY WITH THE REQUIREMENTS OF
 SECTION C405 OF THE FBC-ENERGY CONSERVATION CODE.
 5. NEC 408.4(B) ALL PANEL SHALL BE MARKED INDICATING
 THE LOCATION OF THEIR SOURCE OF POWER (DISCONNECT).
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-04-07 Cont ID  
Sent By wjolin Date 2016-04-07 Time 08:47 Rev Time 0.00
Received By wjolin Date 2016-04-07 Time 08:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-02-09 Cont ID  
Sent By rlindow Date 2016-02-09 Time   Rev Time 0.00
Received By rlindow Date 2016-02-09 Time   Sent To  
Notes
2016-02-09 09:17:31 
  
 PREVIOUS COMMENTS OF AUTOMATIC FIRE SPRINKLER SYSTEM
 NOT PROVIDED HAVE NOT BEEN ADDRESSED. RLINDOW, 2/9/16

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By   Date 2015-09-09 Time   Rev Time  
Received By   Date 2015-09-09 Time   Sent To  
Notes
2015-09-09 13:58:23PANTHER HOUSING FACILITY IS NOT PROVIDED WITH AUTOMATIC
 FIRE SPRINKLER SYSTEM. LINDOW 9/9/15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-12 Cont ID  
Sent By jroach Date 2016-04-12 Time 12:10 Rev Time 0.00
Received By jroach Date 2016-03-25 Time 10:38 Sent To  
Notes
2016-03-28 10:38:35C23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 14:16 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 10:55 Sent To  
Notes
2016-03-15 14:18:583/15/16 PASSED ELECTRICAL REVIEW BUT FAILED OTHER TRADE
 REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE
 DENIED DRAWER "G". MA
2016-02-03 10:55:32C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 09:56 Rev Time 0.00
Received By albarran Date 2015-09-03 Time 13:32 Sent To  
Notes
2015-11-05 09:59:4611/5/15 FAILED THE ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-10 Cont ID  
Sent By ccole Date 2016-02-10 Time 12:20 Rev Time 0.00
Received By ccole Date 2016-02-10 Time 12:20 Sent To  
Notes
2016-02-10 12:27:19MECHANICAL PROVISIOS;
 PERMIT #15090101
 2/10/16
  
 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE UPONOR PEX CHILLER PIPING SHALL BE
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR, AND
 ALL SITE AT TIME OF INSPECTION.
 2) THE MIAMI-DADE NOA AND/OR FLORIDA PRODUCT APPROVAL
 FOR THE LOUVERS SHALL BE REVIEWED AND APPROVED WITH
 SIGNATURE BY THE EOR AND SUBMITTED TO THE BUILDING
 DEPARTMENT PRIOR TO 1ST INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By ccole Date 2015-09-11 Time 12:31 Rev Time 0.00
Received By ccole Date 2015-09-11 Time 12:31 Sent To  
Notes
2015-09-11 12:57:171ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090101
 9/11/15
  
 1) PROVIDE PIPE PROTECTION DETAILS FOR THE CHILLED
 WATER PIPING. INDICATE THE TYPE AND THICKNESS OF
 CONDUIT AND SLEEVING TO BE USED FOR THE
 UNDERGROUND/UNDERSLAB INSTALLATION- REFER TO SECTIONS
 305.1.1 FBC-14 PLUMBING.
 2) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR
 THE CHILLED WATER PIPING- REFER TO SECTION 306.3 FBC-14
 PLUMBING.
 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CHILLER PAD, AND WIND LOAD TIE DOWN ENGINEERING FOR
 MOUNTING THE CHILLER TO THE SLAB- SEE SECTION 301.15
 MECHANICAL.
 4) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE CHILLER AND
 THE UPONOR TYPE A PEX PIPING, AND FOAM INSULATION.
 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 ZOOKEEPER AREAS IN THE PANTHER AND OTTER BUILDINGS-
 REFER TO TABLE 403.3 FBC-14 MECHANICAL. INDICATE HOW
 THE DESIGN USING LOUVERED VENT OPENINGS IS PROVIDING
 VENTILATION AIR FOR THOSE AREAS, AND INDICATE HOW THE
 VENT OPENINGS WERE SIZED.
 6) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR
 MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-19 Cont ID  
Sent By tklarge Date 2016-02-19 Time 13:34 Rev Time 0.00
Received By tklarge Date 2016-02-17 Time 14:43 Sent To  
Notes
2016-02-17 15:20:33WHERE ARE THE IRRIGATION PLANS? THEY WERE PART OF THE
 SET IN THE FIRST SUBMITTAL. 2014 FBC SEC. 107.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-25 Cont ID  
Sent By tklarge Date 2015-09-25 Time 08:58 Rev Time 0.00
Received By tklarge Date 2015-09-24 Time 06:48 Sent To  
Notes
2015-09-24 06:52:161) SHT. A-001 - THE PLANS REFER TO THE 2010 FBC. THE
 CODE IN EFFECT IS THE 2014 FBC. REVISE NOTE.
 2) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE
 IBIS/SPOONBILL WATER FEATURE. PIPING DIAGRAM SHALL
 INCLUDE SSUPPLY AND RETURN LINES, MAIN DRAINS, PUMP,
 PUMP CURVE, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER SPEC SHEETS FOR THE MAIN DRAINS,
 THE PUMP, PUMP CURVE, ETC.WPB AMEND.TO FBC SEC.
 107.2.1.
 4) SHT. IR-1 - SHOWS 4 - 2 INCH LINES BY THE OVERHEAD
 PANTHER WALK BUT THEY ARE ALSO SHOWN AS 3/4 INCH LINES
 ON THE PLAN. CLARIFY.
 5) SHT. IR-1 - THERE ARE A LOT OF IRRIGATION LINES ON
 THE PLAN THAT HAVE NO PIPE SIZES. AT THE VERY LEAST,
 SIZE THE MAN BRANCH LINES.
 6) SHT. IR-2 - THE DETAILS AND PRINTED TEXT ARE VERY
 LIGHT AND ILLEGIBLE. SUBMIT A REVISED DRAWING THAT IS
 CLEAR IN TEXT AND DETAILS.WPB AMEND. TO FBC SEC.
 107.2.1.
 7) SUBMIT AN ENLARGED FLOOR PLAN FOR THE NEW RESTROOM.
 THE RESTROOM SHALL BE FULLY ACCESSIBLE.2014 FBC -
 ACCESSIBILITY SEC.202.1, 213.1, 213.2.
 8) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 NEW RESTROOM. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-02-10 Cont ID  
Sent By jwitmer Date 2016-02-10 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2016-02-10 Time 10:37 Sent To  
Notes
2016-02-10 10:38:28ROOFING PRODUCT APPROVALS DEFERRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2015-09-27 Time 06:16 Sent To  
Notes
2015-09-27 07:10:16NO ROOFING PRODUCT APPROVALS WERE SUBMITTED THIS
 REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2016-04-12 Cont ID  
Sent By jroach Date 2016-04-12 Time 12:08 Rev Time 0.00
Received By jroach Date 2016-04-12 Time 12:08 Sent To  
Notes
2016-04-12 12:09:51ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.12.2016
 PERMIT NO.: 15090101
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
  
 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT
 APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS
 SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS
 WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-14 Cont ID  
Sent By jroach Date 2016-03-14 Time 15:06 Rev Time 0.00
Received By jroach Date 2016-03-14 Time 15:06 Sent To  
Notes
2016-03-14 15:06:44ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.14.2016
 PERMIT NO.: 15090101
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
  
 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT
 APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS
 SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS
 WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  
 9/10/11

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By jroach Date 2015-10-07 Time 13:33 Rev Time 0.00
Received By jroach Date 2015-10-07 Time 13:33 Sent To  
Notes
2015-10-07 13:36:08ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.07.2015
 PERMIT NO.: 15090101
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: PANTHER HABITAT RENOVATIONS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 234-15, BEFORE COMMENCING
 THE IMPROVEMENTS, THE ZOO SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 COMMERCIAL GENERAL LIABILITY INSURANCE (INCLUDING,
 WITHOUT LIMITATION, CONTRACTOR?S LIABILITY COVERAGE),
 WRITTEN ON AN OCCURRENCE BASIS WITH A MINIMUM COMBINED
 SINGLE LIMIT OF $2,000,000, ALONG WITH WORKERS
 COMPENSATION INSURANCE AS REQUIRED BY LAW, AND
 INCLUDING THE CITY OF WEST PALM BEACH AS AN ADDITIONAL
 INSURED.
  
 2. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT
 APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS
 SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS
 WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  