Plan Review Details - Permit 15081122
Plan Review Stops For Permit 15081122
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 17:45 Rev Time 0.00
Received By jgomez Date 2016-01-07 Time 17:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-01-06 Cont ID  
Sent By jgomez Date 2016-01-06 Time 08:41 Rev Time 0.00
Received By jgomez Date 2016-01-06 Time 08:38 Sent To  
Notes
2016-01-06 08:41:44RESIDENTIAL (R3) RE-ROOF 4TH BUILDING REVIEW CHECKLIST.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- NEW CLAY TILE FLORIDA PRODUCT APPROVAL FL17152-R1
 WAS SUBMITTED. LIMITATION #3 ON THIS PRODUCT APPROVAL
 SPECIFIES THAT TILES SHALL BE MECHANICALLY ATTACHED FOR
 WIND LOAD RESISTANCE. PRODUCT APPROVAL SUBMITTED
 DOESN'T SPECIFY THE TILE ATTACHMENT RESISTANCE. NEED
 THIS INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE
 PROPOSED MECHANICAL ATTACHMENT IS GOING TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
 NOTE: NOA 14-0107.02 PREVIOUSLY SUBMITTED HAD ALL THIS
 INFORMATION. THE ONLY THING THAT WAS MISSING WAS THE
 PRODUCT APPROVAL FOR THE ADHESIVE TO BE USED.
  
 RESPONSE TO MR. MUNROE'S E-MAIL:
 GOOD MORNING MR. MUNROE,
 THE NOA 14-0529.02 SUBMITTED FOR THE FLAT ROOF IS OK. I
 ALREADY PRINTED THE PAGES WE NEED INCLUDING PAGE 37
 WITH THE SELECTED ASSEMBLY TO BE INSTALLED.
 REGARDING THE CLAY ROOF TILE ENGINEER CALCULATIONS, YOU
 CAN E-MAIL THEM TO ME FOR REVIEW. ASK THE ENGINEER TO
 INCLUDE THE DESIGN CRITERIA FBC-RESIDENTIAL, 5TH
 EDITION (2014), DESIGN PRESSURES, WIND SPEED, BUILDING
 HEIGHT AND THE BUILDING EXPOSURE IS "C".
 WE WILL NEED THE ENGINEER'S CALCULATIONS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 THANK YOU,
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-12-29 Cont ID  
Sent By jgomez Date 2015-12-29 Time 17:14 Rev Time 0.00
Received By jgomez Date 2015-12-29 Time 17:13 Sent To HIST
Notes
2015-12-29 17:13:58RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- NEW CLAY TILE FLORIDA PRODUCT APPROVAL FL17152-R1
 WAS SUBMITTED. LIMITATION #3 ON THIS PRODUCT APPROVAL
 SPECIFIES THAT TILES SHALL BE MECHANICALLY ATTACHED FOR
 WIND LOAD RESISTANCE. PRODUCT APPROVAL SUBMITTED
 DOESN'T SPECIFY THE TILE ATTACHMENT RESISTANCE. NEED
 THIS INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE
 PROPOSED MECHANICAL ATTACHMENT IS GOING TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
 NOTE: NOA 14-0107.02 PREVIOUSLY SUBMITTED HAD ALL THIS
 INFORMATION. THE ONLY THING THAT WAS MISSING WAS THE
 PRODUCT APPROVAL FOR THE ADHESIVE TO BE USED.
  
 2- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED
 IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE
 NOTE #8 ON PAGE 2 OF 76.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL. THIRD TIME).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-12-11 Cont ID  
Sent By jgomez Date 2015-12-11 Time 16:42 Rev Time 0.00
Received By jgomez Date 2015-12-11 Time 16:42 Sent To  
Notes
2015-12-11 16:43:4212/11/15 TALKED TO MONICA CORTEZ. (954)802-3726. I TOLD
 HER, I HAVE NOT SEEN ANY NEW ENGINEERING FOR THIS
 HOUSE. MY LAST REVIEW WAS DONE ON 10/16/15. THERE ARE
 NO RE-SUBMITTALS FOR THIS PROJECT AFTER THAT DATE. JG.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-16 Cont ID  
Sent By jgomez Date 2015-10-16 Time 17:19 Rev Time 0.00
Received By jgomez Date 2015-10-16 Time 17:19 Sent To  
Notes
2015-10-16 18:14:10RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- ORIGINALLY THIS HOUSE WAS DESIGNED TO HAVE SHINGLES
 ROOFING. PROPOSAL TO INSTALL CLAY TILES REQUIRES
 ENGINEERING ANALYSIS TO VERIFY IF THE STRUCTURE IS
 ADEQUATE TO RECEIVE THE ADDITIONAL LOAD. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 RESPONSE:
 ENGINEER LETTER SUBMITTED:
 (1) IT APPEARS THAT WRONG HOUSE WAS INSPECTED BY THE
 ENGINEER. IT LOOKS LIKE THE ENGINEER INSPECTED THE
 HOUSE LOCATED AT 505 38TH STREET AS STATED ON THE
 LETTER. THE HOUSE FOR THIS PERMIT IS 502 38TH STREET,
 WHICH IS LOCATED ACROSS THE STREET. THE BUILDING
 FRAMING SYSTEM IS DIFFERENT FOR BOTH HOUSES. ONE HOUSE
 WAS BUILT IN 1954 AND THE OTHER ONE WAS BUILT IN 1925.
 THERE MAY NOT BE A TRUSS SYSTEM ON THE HOUSE BUILT IN
 THE 1925'S. ENGINEER TO REVISE ADDRESS AND PROVIDE
 COMPLETE ROOF FRAMING AND SUPPORTING WALLS INFORMATION
 FOR THE CORRECT HOUSE. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 (2) THE ORIGINAL ROOF COVERING OF THIS HOUSE WAS
 SHINGLES NOT CLAY TILES. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 (3) ENGINEER TO PROVIDE ALL HIS INFORMATION AND THE
 FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR THE TILE ADHESIVE LISTED ON THE
 CLAY TILE NOA.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED
 IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE
 NOTE #8 ON PAGE 2 OF 76.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 19:04 Rev Time 0.00
Received By jgomez Date 2015-08-31 Time 18:38 Sent To  
Notes
2015-08-31 19:18:52RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- ORIGINALLY THIS HOUSE WAS DESIGNED TO HAVE SHINGLES
 ROOFING. PROPOSAL TO INSTALL CLAY TILES REQUIRES
 ENGINEERING ANALYSIS TO VERIFY IF THE STRUCTURE IS
 ADEQUATE TO RECEIVE THE ADDITIONAL LOAD. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR THE TILE ADHESIVE LISTED ON THE
 CLAY TILE NOA.
  
 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED
 IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE
 NOTE #8 ON PAGE 2 OF 76.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By jroach Date 2015-08-31 Time 11:21 Rev Time 0.00
Received By jroach Date 2015-08-28 Time 13:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 17:43 Rev Time 0.00
Received By jgomez Date 2016-01-07 Time 17:43 Sent To  
Notes
2016-01-07 17:44:21HI MR. GOMEZ,
 I'M JUST GOING TO FOAM THE TILES DOWN TO MAKE IT
 SIMPLE. I'M HAVING A HARD TIME WITH THE ENGINEER
 GETTING THEM TO RESPOND, THEY WANT TO CHARGE FOR THE
 LETTER, ETC. SO LET'S JUST GO WITH THE MIAMI DADE
 APPROVAL OF FOAMING IF YOU NEED ME TO CIRCLE THAT OR IF
 YOU CAN JUST CIRCLE THE ORIGINAL ONE I SUBMITTED THAT
 WOULD BE GREAT.
  
 THANKS
  
 SENT FROM MY IPHONE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-06 Cont ID  
Sent By jgomez Date 2016-01-06 Time 08:38 Rev Time 0.00
Received By jgomez Date 2016-01-06 Time 08:37 Sent To  
Notes
2016-01-06 08:37:50RECEIVED E-MAIL FROM TONY MUNROE. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-29 Cont ID  
Sent By jgomez Date 2015-12-29 Time 17:14 Rev Time 0.00
Received By jgomez Date 2015-12-23 Time 15:16 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-16 Cont ID  
Sent By jgomez Date 2015-10-16 Time 17:19 Rev Time 0.00
Received By jgomez Date 2015-10-15 Time 16:10 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 18:49 Rev Time 0.00
Received By jgomez Date 2015-08-28 Time 15:00 Sent To  
Notes
2015-08-31 15:00:47JGOMEZ