Plan Review Details - Permit 15080984
Plan Review Stops For Permit 15080984
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By gjohnson Date 2015-08-26 Time 17:26 Rev Time 0.00
Received By gjohnson Date 2015-08-31 Time 16:47 Sent To  
Notes
2015-08-26 17:25:321ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
 1. PIPING UNDER BUILDINGS SHALL BE SLEEVED TO COMPLY
 WITH.
 FBC G 404.14
 2. SHOW LAYOUT ON FLOOR PLAN WPB AMEND. 107.2.1
 3. NEED SPEC SHEETS FOR ALL APPLIANCES . WPB AMEND.
 107.1.2
  
 1.CONTRACTOR ADDRESSED ISSUE PIPING NOT UNDER HOUSE
 2.PROVIDED LAY OUT
 3.SPECS TO BE ON JOB SITE NOTED ON PLAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2015-08-26 Time 15:00 Sent To  
Notes
2015-08-26 15:00:13PLUMB -$5000