Plan Review Details - Permit 15080972
Plan Review Stops For Permit 15080972
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By skennedy Date 2015-09-16 Time 15:55 Rev Time 0.00
Received By skennedy Date 2015-09-16 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 10:03 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 10:03 Sent To P
Notes
2015-09-10 10:05:081ST REVIEW: FBC 2014 5TH ED.
  
 PROVIDE TEST REPORST FOR A FLOORING SOUND INSULATION
 DEMONSTRATING COMPLIANCE WITH THE SECTIONS BELOW:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 10:03 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-10 Cont ID  
Sent By scaldero Date 2015-09-10 Time 13:46 Rev Time 0.00
Received By scaldero Date 2015-09-10 Time 13:46 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-16 Cont ID  
Sent By skennedy Date 2015-09-16 Time 15:55 Rev Time 0.00
Received By skennedy Date 2015-09-14 Time 12:00 Sent To  
Notes
2015-09-15 12:00:54RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By scaldero Date 2015-09-10 Time 13:47 Rev Time 0.00
Received By scaldero Date 2015-08-25 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-10 Cont ID  
Sent By gjohnson Date 2015-09-10 Time 12:37 Rev Time 0.00
Received By gjohnson Date 2015-09-10 Time 12:37 Sent To  
Notes
***NONE***