Plan Review Details - Permit 15080942
Plan Review Stops For Permit 15080942
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 08:45 Rev Time 0.00
Received By ccole Date 2015-12-03 Time 14:47 Sent To  
Notes
2015-12-03 14:47:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-15 Cont ID  
Sent By ccole Date 2015-10-15 Time 14:59 Rev Time 0.00
Received By ccole Date 2015-10-15 Time 13:44 Sent To  
Notes
2015-10-15 13:44:24RESUB ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 08:44 Rev Time 0.00
Received By ccole Date 2015-12-07 Time 08:44 Sent To  
Notes
2015-12-07 08:48:08PROVISO:
 MECHANICAL ENGINEER'S SIGNED AND SEALED AC LOAD
 CALCULATIONS MUST BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-15 Cont ID  
Sent By ccole Date 2015-10-15 Time 14:57 Rev Time 0.00
Received By ccole Date 2015-10-15 Time 14:57 Sent To  
Notes
2015-10-15 15:03:152ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080942
 10/15/15
  
 1 ) 2ND REQUEST FOR AC LOAD CALCULATIONS. REFER TO
 COMMENT #1 FROM 1ST REVIEW: SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION: CALCULATION OF HEATING AND COOLING
 LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) 2ND REQUEST FOR CONDENSER TIE-DOWN ENGINEERING.
 PROVIDE STRUCTURAL DETAILS FOR THE INSTALLATION OF THE
 CONDENSER PAD, AND WIND LOAD-TIE DOWN ENGINEERING FOR
 MOUNTING THE CONDENSER TO THE PAD- SECTION 301.15
 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By ccole Date 2015-08-27 Time 06:54 Rev Time 0.00
Received By ccole Date 2015-08-27 Time 06:54 Sent To  
Notes
2015-08-27 07:00:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080942
 8/27/15
  
 1) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW
 MINI-SPLIT SYSTEM- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) PROVIDE A PLAN SHOWING THE LOCATIONS OF THE OUTDOOR
 AND INDOOR UNITS AND INCLUDE TIE DOWN ENGINEERING FOR
 THE CONDENSER, AND A CONDENSATE DISPOSAL PLAN FOR THE
 AIR HANDLER- SECTION 301.15 AND 307 FBC-14 MECHANICAL.
 3) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  