Plan Review Details - Permit 15080942
Plan Review Stops For Permit 15080942 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-12-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-07 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-03 |
Time |
14:47 |
Sent To |
|
|
Notes |
2015-12-03 14:47:53 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-10-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-10-15 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-10-15 |
Time |
13:44 |
Sent To |
|
|
Notes |
2015-10-15 13:44:24 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-12-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-07 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-07 |
Time |
08:44 |
Sent To |
|
|
Notes |
2015-12-07 08:48:08 | PROVISO: | | MECHANICAL ENGINEER'S SIGNED AND SEALED AC LOAD | | CALCULATIONS MUST BE SUBMITTED PRIOR TO PERMIT | | ISSUANCE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-10-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-10-15 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-10-15 |
Time |
14:57 |
Sent To |
|
|
Notes |
2015-10-15 15:03:15 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080942 | | 10/15/15 | | | | 1 ) 2ND REQUEST FOR AC LOAD CALCULATIONS. REFER TO | | COMMENT #1 FROM 1ST REVIEW: SECTION C403.2.1 FBC-14 | | ENERGY CONSERVATION: CALCULATION OF HEATING AND COOLING | | LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | 2) 2ND REQUEST FOR CONDENSER TIE-DOWN ENGINEERING. | | PROVIDE STRUCTURAL DETAILS FOR THE INSTALLATION OF THE | | CONDENSER PAD, AND WIND LOAD-TIE DOWN ENGINEERING FOR | | MOUNTING THE CONDENSER TO THE PAD- SECTION 301.15 | | FBC-14 MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-08-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-08-27 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-08-27 |
Time |
06:54 |
Sent To |
|
|
Notes |
2015-08-27 07:00:49 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080942 | | 8/27/15 | | | | 1) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW | | MINI-SPLIT SYSTEM- SEE SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION: CALCULATION OF HEATING AND COOLING LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | 2) PROVIDE A PLAN SHOWING THE LOCATIONS OF THE OUTDOOR | | AND INDOOR UNITS AND INCLUDE TIE DOWN ENGINEERING FOR | | THE CONDENSER, AND A CONDENSATE DISPOSAL PLAN FOR THE | | AIR HANDLER- SECTION 301.15 AND 307 FBC-14 MECHANICAL. | | 3) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
|