Plan Review Details - Permit 15080892
Plan Review Stops For Permit 15080892
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-02-08 Cont ID  
Sent By shill Date 2016-02-08 Time 12:53 Rev Time 0.00
Received By shill Date 2016-02-08 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-01-21 Cont ID  
Sent By shill Date 2016-01-21 Time 08:43 Rev Time 0.00
Received By shill Date 2016-01-21 Time 08:43 Sent To  
Notes
2016-01-21 08:45:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING
 IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE
 DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609
 (ASCE7-10), FS 471, 481.
  
 ENGINEER'S PLAN STATES TO SEE THE DOOR SPEC SHEETS FOR
 DP LIMITATIONS.
  
 ENGINEER TO STATE THE DESIGN PRESSURE REQUIREMENT FOR
 THE BUILDING. THE DOOR PRODUCT APPROVAL IS TO COMPLY
 WITH THE DESIGN PRESSURE REQUIREMENT. REVISE THE PLAN,
 OR ADD A LETTER, WHICH STATES THE DESIGN PRESSURE
 REQUIREMENTS FOR THE EXTERIOR DOORS FOR THIS PROJECT.
 NOTE THAT THIS BUILDING APPEARS TO BE LOCATED IN
 EXPOSURE D. THE DP LIMITATION FOR THE PROPOSED DOORS IS
 +65 / -53.3.
  
 NEW COMMENT:
  
 2. PLEASE COLLATE TWO COMPLETE SETS OF PLANS FOR
 REVISION ISSUANCE. THIS SHOULD INCLUDE:
  
 DOOR PRODUCT APPROVAL REVIEWED BY DESIGNER OF RECORD,
 FBC 107.
 PLANS SHOULD INCLUDE DESIGN PRESSURE REQUIREMENTS, FBC
 1609.
 SPEC SHEETS FOR THE PROPOSED DOOR WHICH SHOWS
 COMPLIANCE WITH THE 90 MINUTE FIRE RESISTANCE RATING IS
 REQUIRED. THE NEW NOA IS FOR MESKER N SERIES DOOR; THE
 SPEC SHEETS ARE FOR DAYBAR, FBC 107.
 INDICATE WHICH THRESHOLD IS PROPOSED. IF ADA THRESHOLD
 IS NOT SELECTED, PLEASE CONTACT ME PRIOR TO RESUBMITTAL
 TO DISCUSS. FBC 2010 ACCESSIBILITY 404.2.5, FAIR
 HOUSING.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2015-12-04 Cont ID  
Sent By shill Date 2015-12-04 Time 17:37 Rev Time 0.00
Received By shill Date 2015-12-04 Time 17:37 Sent To  
Notes
2015-12-04 17:40:12CONTRACTOR SENT LETTER STATING THAT THE OWNER DOES NOT
 WANT TO HAVE THE OPAQUE DOOR WHICH WAS RESUBMITTED
 INSTALLED. OWNER CURRENTLY HAS A 90 MINUTE DOOR WITH
 GLASS. THE DOOR INITIALLY PROPOSED HAS A DP LIMITATION
 OF -53 BUT THE BUILDING HAS A DP REQUIREMENT OF +-65.
  
 SPOKE WITH ROBERT BROWN; ADVISED CONTRACTOR THAT A NON
 IMPACT DOOR WOULD BE ACCEPTABLE (GLAZING LIMITED TO 100
 SI)
  
 PROPOSED PRODUCT SUBMITTED COMPLIES WITH CODE BUT
 PULLED FROM REVIEW BY CONTRACTOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-14 Cont ID  
Sent By pleduc Date 2015-10-06 Time 16:15 Rev Time 0.00
Received By shill Date 2015-10-14 Time 18:19 Sent To  
Notes
2015-10-14 18:21:18****CORRECTIONS****
 REVISED 9/16
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 3. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING
 IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE
 DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609
 (ASCE7-10), FS 471, 481.
  
 ENGINEER'S PLAN STATES TO SEE THE DOOR SPEC SHEETS FOR
 DP LIMITATIONS.
  
 ENGINEER TO STATE THE DESIGN PRESSURE REQUIREMENT FOR
 THE BUILDING. THE DOOR PRODUCT APPROVAL IS TO COMPLY
 WITH THE DESIGN PRESSURE REQUIREMENT. REVISE THE PLAN,
 OR ADD A LETTER, WHICH STATES THE DESIGN PRESSURE
 REQUIREMENTS FOR THE EXTERIOR DOORS FOR THIS PROJECT.
 NOTE THAT THIS BUILDING APPEARS TO BE LOCATED IN
 EXPOSURE D. THE DP LIMITATION FOR THE PROPOSED DOORS IS
 +65 / -53.3.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-29 Cont ID  
Sent By shill Date 2015-08-29 Time 11:06 Rev Time 0.00
Received By shill Date 2015-08-29 Time 11:06 Sent To FIRE
Notes
2015-08-29 11:07:49****CORRECTIONS****
 REVISED 9/16
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS,
 FIRE RATING OF PROPOSED DOORS, AND FIRE RATING FOR THE
 WALLS.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO PERFORM A PLAN
 REVIEW, FBC 107.
  
 PLAN SHOULD SHOW LOCATION OF DOORS, ALL FIRE RATED
 WALLS (ALL APPLICABLE SEPARATIONS SUCH AS FIRE PUMP
 ROOMS, ELECTRICAL ROOMS, STORAGE AS WELL AS OCCUPANCY
 SEPARATION, ETC.). SEE FBC CHAPTERS 5, 7.
  
 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE INFORMATION AND DESIGN. A DESIGN PROFESSIONAL MAY
 BE REQUIRED, FS471, 481.229(C).
  
 3. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING
 IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE
 DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609
 (ASCE7-10), FS 471, 481.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-11 Cont ID  
Sent By pleduc Date 2016-01-11 Time   Rev Time 0.00
Received By pleduc Date 2016-01-11 Time 09:39 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By shill Date 2015-10-14 Time 18:23 Rev Time 0.00
Received By pleduc Date 2015-10-06 Time 16:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-31 Time 10:48 Sent To PC
Notes
2015-08-31 10:55:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS INSUFFICIENT DETAIL TO PROVIDE A PROPER OR
 COMPLETE PLAN REVIEW.
  
 2) THERE IS NO INDICATION OF THE LOCATION OR NUMBER OF
 DOORS.
  
 3) THERE IS NO DOOR SCHEDULE.
  
 4) THERE IS NO INDICATION OF EXISTING DOORS OR DOOR
 TYPES.
  
 5) THERE IS NO INDICATION OF VALUE OF WORK; PROVIDE
 COST OR COPY OF CONTRACT.
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 SUBMITTAL OF THE ABOVE.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-02-08 Cont ID  
Sent By shill Date 2016-02-08 Time 12:53 Rev Time 0.00
Received By shill Date 2016-01-28 Time 15:29 Sent To  
Notes
2016-01-28 15:29:47RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-21 Cont ID  
Sent By shill Date 2016-01-21 Time 08:51 Rev Time 0.00
Received By shill Date 2016-01-08 Time 12:49 Sent To  
Notes
2016-01-08 12:49:46RESUB ROUTED TO PLEDUC

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-04 Cont ID  
Sent By shill Date 2015-12-04 Time 17:40 Rev Time 0.00
Received By shill Date 2015-12-01 Time 10:55 Sent To  
Notes
2015-12-01 10:55:14RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 18:23 Rev Time 0.00
Received By shill Date 2015-10-01 Time 12:51 Sent To FIRE
Notes
2015-10-09 10:43:1610/9 TO SH DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-24 Time 08:18 Sent To  
Notes
2015-08-29 11:08:188/29 TO FIRE BOX
  
  
2015-08-25 09:01:18REVISION ROUTED TO SHILL