Plan Review Details - Permit 15080832
Plan Review Stops For Permit 15080832
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-02-25 Cont ID  
Sent By jgomez Date 2016-02-25 Time 13:54 Rev Time 0.00
Received By jgomez Date 2016-02-25 Time 13:54 Sent To  
Notes
2016-02-25 14:01:40RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- FOOTPRINT SIZE OF THE GARAGE SHOWN ON SURVEY AND
 PLANS SUBMITTED DON'T MATCH THE FOOTPRINT OF THE CITY
 RECORDS AND THE PROPERTY APPRAISER RECORDS. THE
 ORIGINAL FOOTPRINT SHOWN ON CITY RECORDS AND PROPERTY
 APPRAISER SHOW A GARAGE FOOTPRINT OF 12'-0" BY 20'-0".
 SURVEY AND PLANS SHOW A BUILDING DOUBLE THE SIZE. THERE
 ARE NO PERMITS FOR THE ENLARGEMENT OF THE GARAGE.
 REVISE PLANS AND SURVEY AS REQUIRED AS REQUIRED.
 CLEARLY IDENTIFY WHAT'S EXISTING AND WHAT'S NEW. . SEC.
 107.2.1 CITY AMENDMENTS.
 NOTE: OLD PLANS SUBMITTED ON PREVIOUS REVIEWS SHOW THE
 CORRECT SIZE OF THE GARAGE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED.
 NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014
 CODE. (NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT
 APPROVAL, THEN THE MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL. COMPLETE SIGNED AND SEALED PRODUCT
 APPROVAL PACKAGE WILL NEED TO BE SUBMITTED FOR BUILDING
 OFFICIAL APPROVAL).
 RESPONSE: PRODUCT APPROVAL INFORMATION SUBMITTED
 DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR
 FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
 RESPONSE: (REPEAT COMMENT). FLORIDA PRODUCT APPROVAL
 #10865 SHOWN ON WALL SECTION "A" DOESN'T SHOW THE
 SPECIFIED CONNECTORS. REVISE AS REQUIRED. CLEARLY
 SPECIFY FLORIDA PRODUCT APPROVAL NUMBER FOR EACH
 CONNECTOR SPECIFIED ON THE WALL SECTION "A" , INCLUDING
 THE SIMPSON 5P2 .
  
 3- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 4- GENERAL NOTE # 15 OF SURVEY SUBMITTED STATES THAT
 THIS SURVEY CAN NOT BE USED FOR CONSTRUCTION OR
 PERMITTING PURPOSES WITHOUT WRITTEN CONSENT FROM MIGUEL
 ESPINOZA. PROVIDE SURVEY WITH SURVEYOR'S ORIGINAL SEAL
 AND SIGNATURE THAT CAN BE USED FOR PERMITTING AND
 CONSTRUCTION. CHAPTER 472 FLORIDA STATUTE.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-07 Cont ID  
Sent By jgomez Date 2015-12-07 Time 17:46 Rev Time 0.00
Received By jgomez Date 2015-12-07 Time 17:46 Sent To E
Notes
2015-12-07 17:46:59RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 SEE ZONING COMMENTS REGARDING BUILDING SETBACKS. IN
 ADDITION, SEE COMMENTS BELOW.
  
 1- BASED ON SURVEY SUBMITTED, THE ADDITION IS LOCATED
 LESS THAN 3'-0" FROM THE PROPERTY LINE. NEED TO COMPLY
 WITH THE FOLLOWING:
 A) NO OPENINGS ALLOWED. SEC. R302.1 AND TABLE R302.1(1)
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) NEED TO SPECIFY 1 HR FIRE RATED EXTERIOR WALL
 ASSEMBLY. SPECIFY PUBLISHED ASSEMBLY NUMBER. ASSEMBLY
 SPECIFIED TO BE TESTED IN ACCORDANCE WITH ASTM E 119 OR
 UL 263 WITH EXPOSURE ON BOTH SIDES. SEC. R302.1 AND
 TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) SPECIFY 1 HR FIRE RATED ASSEMBLY FOR THE UNDERSIDE
 OF THE ROOF PROJECTION AS REQUIRED BY SEC. R302.1 AND
 TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) WALL PENETRATIONS NEED TO COMPLY WITH SEC. R302.1
 AND TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED.
 NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014
 CODE.
 RESPONSE: PRODUCT APPROVAL INFORMATION SUBMITTED
 DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR
 FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. AND, DRAWINGS SUBMITTED DON'T MATCH
 TYPE OF DOOR SHOWN ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
 RESPONSE: CLEARLY SPECIFY FLORIDA PRODUCT APPROVAL
 NUMBER FOR EACH CONNECTOR SPECIFIED ON THE WALL SECTION
 "A" , INCLUDING THE SIMPSON 5P2 . ALSO, THERE ARE OTHER
 CONNECTORS LIKE THE SIMPSON HTU28 THAT ARE NOT COVERED
 UNDER THE FLORIDA PRODUCT APPROVAL FL10865. REVISE AS
 REQUIRED.
  
 3- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: DOOR PRODUCT APPROVAL APPROVED BY THE
 ENGINEER DOESN'T MATCH PLANS.
  
 4- THERE ARE TWO DIFFERENT SURVEYS SUBMITTED. PLANS AND
 SURVEY SUBMITTED DON'T MATCH. REVISE AS REQUIRED.
 PROVIDE CLEAR DRAWINGS SHOWN WHAT'S EXISTING AND WHAT'S
 PROPOSED. SEC. 107.2.1 CITY AMENDMENTS.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By jgomez Date 2015-10-02 Time 17:20 Rev Time 0.00
Received By jgomez Date 2015-10-02 Time 15:33 Sent To E
Notes
2015-10-02 17:29:10RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- PROVIDE SITE PLAN OR SURVEY WITH COMPLETE DIMENSIONS
 SHOWING LOCATION OF NEW ADDITION AND EXISTING HOUSE.
 SEC. 107.3.5.3(1). CITY AMENDMENTS.
  
 2- IDENTIFY THE NAME OF THE ROOM OF PROPOSED ADDITION.
 WHAT'S THE ROOM GOING TO BE USED FOR?. NEED TO IDENTIFY
 ROOM FOR PROPER PLAN REVIEW. IS THIS ROOM GOING TO BE
 USED FOR LIVING PURPOSES?. CLARIFY WHY THERE IS NOT A
 DOOR BETWEEN THE STORAGE ROOM AND THE NEW ADDITION.
 CLARIFY WHY IS THERE A BATHROOM IN THE NEW ROOM
 ADJACENT TO THE STORAGE ROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $15,000. THE
 PERMIT FEE BALANCE IS $1453.60.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- SPECIFY THE ROOF PITCH OF THE NEW ADDITION TO VERIFY
 COMPLIANCE WITH SHINGLES INSTALLATION ON THE PROPOSED
 SLOPE. SEC. R905.2.2 OF FBC-RESIDENTIAL , 5TH EDITION
 (2014).
  
 6- LETTERING ON THE "TYP. HEADERS IN DR. & WINDOW
 FRAMING" DETAIL ON SHEET 2 OF 2 IS TO SMALL AND IS NOT
 LEGIBLE. REVISE AS REQUIRED. PROVIDE BIGGER AND CLEAR
 LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 7- WALL SECTION "A" ON SHEET 2 OF 2:
 A) SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 OF FBC-RESIDENTIAL , 5TH EDITION (2014).
  
 B) SPECIFY FOOTING SIZE. SEC. R301 OF FBC-RESIDENTIAL ,
 5TH EDITION (2014).
 NOTE: COORDINATE WITH ITEM #7(C) AND #7(D) BELOW.
  
 C) SPECIFY THE 6" CLEARANCE FROM GRADE TO FINISH FLOOR
 AS REQUIRED BY SEC. R404.1.6 OF FBC-RESIDENTIAL , 5TH
 EDITION (2014).
  
 D) SPECIFY FOOTING TO BE 12" BELOW FINISHED GRADE AS
 REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL , 5TH
 EDITION (2014).
  
 E) LENGTH OF RED HEAD ANCHOR SPECIFIED TO CONNECT THE
 BOTTOM PLATE TO THE CONCRETE SLAB IS NOT CLEAR. REVISE
 AS REQUIRED. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 F) SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF FBC-RESIDENTIAL , 5TH EDITION (2014).
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED.
 NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014
 CODE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
  
 9- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 *** PLEASE PROVIDE ENGINEER RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-03-09 Cont ID  
Sent By mvaldes Date 2016-03-09 Time 10:34 Rev Time 0.00
Received By mvaldes Date 2016-03-09 Time 10:34 Sent To  
Notes
2016-03-09 10:38:47REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - NEC 210.8 A2 ALL GARAGES AND BATHROOMS OUTLETS SHALL
 BE GFCI PROTECTED.
  
 - NEC 212.52 SINCE CONVERTING GARAGE TO LIVABLE SPACE
 RECEPTACLES MUST SPACED 6FT IN BETWEEN EACH OTHER ON
 THE FLOOR PLANS. FURTHER MORE ANY SPACE 2FT OR MORE
 UNBROKEN BY OPENINGS SHALL HAVE A RECEPTACLE ON FLOOR
 PLANS.
  
 - NEC 210.70 2B A LIGHT IS REQUIRED OUTSIDE EVERY DOOR
 FOR SECURITY ILLUMINATION PURPOSES.
  
 PLEASE ADDRESS THESE COMMENTS ACCORDINGLY TO AVOID A 4X
 THE REVIEW FEE PENALTY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 13:19 Rev Time 0.00
Received By mvaldes Date 2015-12-10 Time 12:59 Sent To  
Notes
2015-12-10 13:29:581ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-
 AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED
 IN
 210.8(A)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL.
 (1) BATHROOMS
 (2) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT HAVE A
 FLOOR
 LOCATED AT OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE
 ROOMS AND LIMITED TO STORAGE AREAS, WORK AREAS,
 AND AREAS OF SIMILAR USE
  
 (A) GENERAL PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM,
 DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM,
 BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR AREA OF
 DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH THE GENERAL PROVISIONS SPECIFIED IN 210.52(A)(1)
 THROUGH (A)(3).
 (1) SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT
 NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY
 WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET.
 (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE
 SHALL
 INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG
 THE FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES,
 AND FIXED CABINETS
 (2) THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS,
 EXCLUDING SLIDING PANELS
 (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS
 FREESTANDING BAR-TYPE COUNTERS OR RAILINGS
  
 FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL SWITCH?
 CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION
 ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS
 WITH GRADE LEVEL ACCESS. A VEHICLE DOOR IN A GARAGE
 SHALL NOT
 BE CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT
  
  
2015-12-07 18:42:41NEW PLANS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-05 Cont ID  
Sent By ppetty Date 2015-10-05 Time 11:27 Rev Time 0.00
Received By ppetty Date 2015-10-05 Time 11:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-09 Cont ID  
Sent By mvaldes Date 2016-03-09 Time 11:04 Rev Time 0.00
Received By mvaldes Date 2016-02-16 Time 13:44 Sent To  
Notes
2016-02-16 13:44:44R10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-10 Cont ID  
Sent By cpuell Date 2015-12-10 Time 15:46 Rev Time 0.00
Received By cpuell Date 2015-11-18 Time 12:51 Sent To  
Notes
2015-11-19 12:52:04R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-05 Cont ID  
Sent By ppetty Date 2015-10-05 Time 11:27 Rev Time 0.00
Received By ppetty Date 2015-08-21 Time 16:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-02-25 Cont ID  
Sent By jgomez Date 2016-02-25 Time 18:57 Rev Time 0.00
Received By jgomez Date 2016-02-25 Time 18:56 Sent To  
Notes
2016-02-25 18:57:411- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. THEN, BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-12-07 Cont ID  
Sent By jgomez Date 2015-12-07 Time 18:41 Rev Time 0.00
Received By jgomez Date 2015-12-07 Time 18:41 Sent To  
Notes
2015-12-07 18:42:111- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By jgomez Date 2015-10-02 Time 18:14 Rev Time 0.00
Received By jgomez Date 2015-10-02 Time 18:14 Sent To  
Notes
2015-10-02 18:14:501- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-02-24 Cont ID  
Sent By gjohnson Date 2016-02-24 Time 16:12 Rev Time 0.00
Received By gjohnson Date 2016-02-24 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By tklarge Date 2015-11-23 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-11-23 Time 04:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-01 Cont ID  
Sent By tklarge Date 2015-09-01 Time 04:07 Rev Time 0.00
Received By tklarge Date 2015-09-01 Time 03:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By jgomez Date 2016-02-25 Time 18:57 Rev Time 0.00
Received By jgomez Date 2016-02-25 Time 18:57 Sent To  
Notes
2016-02-25 18:58:39SHINGLES NOA 14-1022.16

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-10-05 Cont ID  
Sent By jgomez Date 2015-10-05 Time 11:07 Rev Time 0.00
Received By jgomez Date 2015-10-05 Time 11:07 Sent To  
Notes
2015-10-05 11:07:56SHINGLES NOA 12-1127.03.

Review Stop Z ZONING
Rev No 3 Status F Date 2016-03-07 Cont ID  
Sent By ajones Date 2016-03-07 Time 13:30 Rev Time 0.00
Received By ajones Date 2016-03-07 Time 13:30 Sent To E
Notes
2016-03-07 13:31:543/7/16- FAILED SEE BUILDING COMMENT #1
 ANGELLA VANN, AICP
 561-822-1441

Review Stop Z ZONING
Rev No 2 Status F Date 2015-12-04 Cont ID  
Sent By sgraham Date 2015-12-04 Time 16:13 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2015-12-04 16:16:0112/3/15 ZONING FAILED
  
 1. THE ADDITION MUST 5' FEET FROM THE REAR PROPERTY AND
 SIDE PROPERTY.
 2. THE ADDITION MUST BE USED ONLY AS STORAGE AND
 EXERCISE ROOM ONLY, ROOM CAN NOT BE USED AS A SLEEPING
 AREA.
 3. THE SITE PLAN AND THE PLANS DO NOT MATCH, SUBMIT
 PLANS THE MATCH.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By sgraham Date 2015-08-25 Time 08:29 Rev Time 0.00
Received By sgraham Date 2015-08-25 Time 08:29 Sent To  
Notes
2015-08-25 08:30:438/25/15 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF UP TO DATE SURVEYS SHOWING
 LOCATION OF THE ADDITION.
2015-08-24 11:11:398/24/15