Plan Review Details - Permit 15080803
Plan Review Stops For Permit 15080803
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By albarran Date 2016-04-27 Time 09:12 Rev Time 0.00
Received By albarran Date 2016-04-27 Time 08:05 Sent To  
Notes
2016-04-27 09:15:18ALL PREVIOUSLY MENTIONED ITEMS HAVE BEEN SATISFACTORILY
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By albarran Date 2015-09-14 Time 15:51 Rev Time 0.00
Received By albarran Date 2015-09-14 Time 14:30 Sent To I
Notes
2015-09-14 16:05:50PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PG. E5: LARGE VIEW 4: DS-AC 12 & DS-AC 14 APPEARS TO
 BE ENCROACHING THE SAFE WORKING CLEARANCE REQUIRED BY
 NEC 110.26.
 2. PG. E6: PER NEC 406.8, THE WP RECEPTACLE OUTDOORS ON
 THE ROOF SHALL ALSO BE LISTED AS WEATHER RESISTANT
 ?WR?.
 3. PG. E7: VERIFY THE ALLOTTED CLEARANCE ABOUT
 ELECTRICAL EQUIPMENT SPECIFIED IN NEC 110.26. MAIN
 ELECTRICAL ROOM APPEARS TO BE IN VIOLATION.
 THE OVER CURRENT PROTECTION FOR THE FPL FEEDER IS 200
 AMP. CORRECT ACCORDINGLY
 PROVIDE LOAD CALCS FOR PANEL ?L1? AND ?MSBD? TO
 ASCERTAIN PROPER ACCEPTANCE OF NEW LOADS.
 INDICATE CONDUCTOR SIZES FEEDING DISCONNECTS OFF OF
 PANEL L1 CIRCUITS 7 ? 10.
 DESCRIBE WHAT PART OF THE SCOPE INVOLVES PANEL ?F?.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-27 Cont ID  
Sent By ccole Date 2016-04-27 Time 15:44 Rev Time 0.00
Received By ccole Date 2016-04-19 Time 11:14 Sent To  
Notes
2016-04-20 11:14:58RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-14 Cont ID  
Sent By albarran Date 2015-09-14 Time 16:11 Rev Time 0.00
Received By albarran Date 2015-08-21 Time 13:56 Sent To  
Notes
2015-09-14 16:26:479/14/15 FAILED LAST REVIEW. CONTACT PERSON NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "TBD". MA
  
2015-08-21 13:56:25MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By ccole Date 2016-04-27 Time 15:44 Rev Time 0.00
Received By ccole Date 2016-04-27 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By ccole Date 2015-08-28 Time 15:19 Rev Time 0.00
Received By ccole Date 2015-08-28 Time 15:19 Sent To  
Notes
2015-08-28 15:29:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080803
 8/28/15
  
 1) SHEET M-1: PROVIDE DETAILS FOR THE O/A AIR DUCT AND
 CHILLED WATER PIPE INSULATIONS- TYPES, THICKNESSES, AND
 R-VALUES: REFER TO TABLE C403.2.7.1 AND C403.2.8 FBC-14
 ENERGY CONSERVATION.
 2) M-2 & M-17: THE FLORIDA BUILDING CODE FIFTH EDITION
 2014 WENT INTO EFFECT ON JUNE 30, 2015. PLEASE UPDATE
 THE CODE REFERENCES ACCORDINGLY AND VERIFY THE DESIGN
 IS IN COMPLIANCE.
 3) M-5- M-10: REVIEW THE NEW WORK SECTIONS AND NOTES. I
 AM FINDING MANY NOTES MISSING FROM THE DRAWINGS SUCH AS
 NOTE #1, 3, 5, 11 ETC.
 4) M-12 & M21: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF THE NEW OAU-1 PER SECTION 606.2.1
 FBC-14 MECHANICAL. PLEASE NOTE THAT LEVEL 1 ALTERATIONS
 SHALL COMPLY WITH THE CURRRENT 2014 FLORIDA BUILDING
 CODES- REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING
 CODE.
 5) M-15: PROVIDE A SCHEDULE FOR THE PIPE HANGERS
 INDICATING THE REQUIRED SPACINGS PER PIPE DIAMETER, AND
 ANCHOR TYPES PER SUBSTRATE MATERIAL.
 6) M-16: REFER TO THE SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS- 2005, AND SMACNA FIBROUS GLASS DUCT
 CONSTRUCTION STANDARDS- 2010. PROVIDE HANGER AND
 SUPPORT DETAILS FOR BOTH METAL AND FIBROUS DUCTS.
 7) THE CITY OF WPB CONSTRUCTION SERVICES AC CHANGE-OUT
 COMPLIANCE FORM: PROVIDE COPIES OF THE FORM IN
 DUPLICATE FOR THE AHU'S AND THE OAU-1.
 8) COMMISSSIONING: REFER TO SECTION C408 FBC-14 ENERGY
 COMPLIANCE. PLEASE PROVIDE A COMMISSIONING PLAN IN
 ACCORDANCE WITH C408.2.1. REVIEW ALL SUB-SECTIONS THAT
 ARE APPLICABLE TO THE PROPOSED PROJECT INCLUDING
 SECTION C408.2.4.1 FOR FINAL INSPECTION APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719