Plan Review Stops For Permit 15080784 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2015-11-20 |
|
|
Cont ID |
|
Sent By |
|
Date |
2015-11-20 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2015-11-20 |
Time |
15:44 |
Sent To |
|
|
Notes |
2015-11-20 16:35:43 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15080784 | | ADD: 330 CLEMATIS STREET # 110 | | CONT: TBD | | TEL: (561)686-5853 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3D REVIEW | | DATE: THURS. FRI. NOV. 20/ 2015 | | | | ACTION: BUILDING PROVISO | | BUILDING APPROVED WITH EXCEPTION! | | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES | | | | | | 1) PLEASE PROVIDE COMPLIANCE WITH THE BAR AREA IN THE | | EXTERIOR WALL. SHOW HOW COMPLIANCE WITH 2014 | | ACCESSIBILITY CODE 226.2 DISPERSION. DINING SURFACES | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | SURFACES. | | 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT, PLEASE SHOW | | HOW COMPLIANCE WITH THE HEIGHT OF THE BAR WILL BE | | ACHIEVED. THE TOP OF DINING SURFACES SHALL BE A MINIMUM | | OF 28 INCHES AND A MAXIMUM OF 34 INCHES ABOVE THE | | FINISH FLOOR. | | | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2015-11-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-11-04 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-11-04 |
Time |
07:30 |
Sent To |
|
|
Notes |
2015-11-05 08:32:21 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15080784 | | ADD: 330 CLEMATIS STREET # 110 | | CONT: TBD | | TEL: (561)686-5853 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: THURS. NOV. 11/2015 | | ACTION: BUILDING PROVISO | | | | 1) DOOR NUMBER # 7 NEEDS TO BE REVERSED TO A OUTSWING | | DOOR, FOR COMPLIANCE WITH 2014 FBC-ACCESSIBLITY CODE | | 404.2.4.1 MANEUVERING CLEARANCES, 18 INCHES ON THE | | LATCH SIDE OF THE DOOR. | | | | 2) PLEASE PROVIDE COMPLIANCE WITH THE BAR AREA IN THE | | EXTERIOR WALL. SHOW HOW COMPLIANCE WITH 2014 | | ACCESSIBILITY CODE 226.2 DISPERSION.DINING SURFACES | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | SURFACES. | | 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT, PLEASE SHOW | | HOW COMPLIANCE WITH THE HEIGHT OF THE BAR WILL BE | | ACHIEVED. THE TOP OF DINING SURFACES SHALL BE A MINIMUM | | OF 28 INCHES AND A MAXIMUM OF 34 INCHES ABOVE THE | | FINISH FLOOR. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | DEVELOPMENT SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-09-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-09-10 |
Time |
11:57 |
Rev Time |
|
Received By |
jwitmer |
Date |
2015-09-10 |
Time |
09:03 |
Sent To |
|
|
Notes |
2015-09-10 11:57:36 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15080784 | | ADD: 330 CLEMATIS STREET # 110 | | CONT: TBD | | TEL: (561)686-5853 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: THURS. SEPT. 10/2014 | | ACTION: DENIED | | | | 1) MISSING CODE DESIGN, THE COVERSHEET INDICATES A | | BUILDING TYPE 3B. SPRINKLERED OR NOT. TABLE 503 & TABLE | | 508.4. THE CONCERN IS NOT THE VERTICAL OCCUPANCY BUT | | THE HORIZONTAL OCCUPANCY SEPARATION, SEE 2014 FBC-B | | TABLE 707.3.10. | | | | 2) THERE IS A DESCREPANCY IN PLANS BETWEEN SHEET C1 THE | | COVERSHEET AND SHEET 1.4 FOR THE WAY THE OCCUPANT LOAD | | IS COMPUTED, THERE IS A DISCREPANCY IN THE OCCUPANT | | LOAD. NOTE THE EXTERIOR SEASONAL SEATING WILL STILL | | NEED TO EXIT THROUGH A DOORWAY. | | | | 3)THE COVERSHEET UNDER THE HEADING OF NUMBER OF SEATS | | LIST 52 PEOPLE UNDER THE EXTERIOR PATIO. PLEASE THE | | LIFE SAFETY PLAN DOES NOT SHOW 2 EXITS FROM THIS SPACE. | | PLEAASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1015.2.1. | | TABLE 1015.1 MAX 1 EXIT 49 FOR ASSEMBLY OCCUPANCY. | | | | 4) THE LIFE SAFETY PLAN 1.4 DOES NOT IDENTIFY THE | | DOORS, SHEET 1.0A INDICATES THE DOOR IDENTIFICATION | | TAGS BUT NOT THE EXIT SIGNS. PLEASE IDENTIFY THE DOORS | | ON SHEET 1.4 THE LIFE SAFETY TO VERIFY THE EXITING. THE | | LIFE SAFETY PLANS DO NOT INDICATE THE EXITING PATERNS | | FOR THE OCCUPANTS. | | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | BUILDINGS | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | OCCUPANCY LOAD | | GROSS | | NET | | MEANS OF EGRESS | | EXIT ACCESS | | EXIT | | EXIT DISCHARGE | | DOORS | | EMERGENCY LIGHTING AND EXIT SIGNS | | | | 5) THE SHEET 1.4 LIFE SAFETY SHEET VERSES 2.0E DOES NOT | | MATCH UP WITH BATTERY EXIT SIGNS W/ FLOODS. DISCREPANCY | | IN PLANS. ADDITIONAL INFORMAION IS REQUIRED. DEPENDING | | ON THE FINAL VERSION OF PLANS ADDITIONAL COMMENTS MAY | | OCCUR. | | | | 6) THE SHEET 1.4 THE LIFE SAFETY PLAN SHOWS A EXIT FROM | | THE KITCHEN, WITH THE EXIT DOOR OF THE KITCHEN YOU | | ENTER THE EXIT DISCHARGE. THE PLANS MUST MEET ALL OF | | THE REQUIREMENTS OF 2014 FBC-B 1027.1 NOTE THE WALLS DO | | NOT INDICATE AN Y RATING. ALSO NOTE THE EAST WALL OF | | THE EXTERIOR DINING ROOM APPEARS TO HAVE A DOOR OPENING | | WITHOUT A DOOR WAY. THE EXISTING SITE HAS A GATE AT THE | | END OF THE EXIT DISCHARGE NOT SHOWN ON THE PROPOSED | | PLANS, WILL THIS BE REMOVED, IF NOT IS IT LOCKABLE? | | | | 7) THERE ARE NEW EXTERIOR ELEMENTS FOR COMPONENTS AND | | CLADDING PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF | | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) WALL LOUVERS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS/ | | EXHAUST FANS | | (G) PRE-ENGINEERED A/C STANDS | | | | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 9) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA OR | | PRESSURES ASSOCIATED WITH THE NEW OPENINGS: | | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | STRUCTURE: | | | | 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | 1609.3.1. | | | | 9.2. RISK CATEGORY. | | | | 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | THAN ONE WIND EXPOSURE IS UTILIZED. | | | | 9.4APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | 9.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | M2). | | | | 10) SHEET 1.6 HAS A NOTE THAT IN THE NEW EXTERIOR | | DINING ROOM THE THERE IS AN ORIGINAL DROP CEILING, | | PLEASE PROVIDE WILL TYPE OF CEILING IS IT. WILL THE | | CEILING TAKE POSITIVE PRESSURES FROM A HIGH WIND EVENT. | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | 11) NEITHER DOES M2.2 OR M3.2 INDICATE IF THE EXISITNG | | EXHAUST DUCT AND ROOF TOP FAN ARE TO BE REUSED FOR THE | | HOOD EXHAUST, NOR IS THERE ANY INFORMATION HOW THE DUCT | | IS CHASED THROUGH THE 2ND FLOOR ASSEMBLY AND TO THE | | ROOF TOP? 107.2.1.3. | | | | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-12-03 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-12-03 |
Time |
18:30 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-12-03 |
Time |
17:47 |
Sent To |
I |
|
Notes |
2015-12-03 18:31:11 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | SATISFACTORILY ADDRESSED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-11-05 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-05 |
Time |
19:32 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-11-05 |
Time |
18:02 |
Sent To |
Z |
|
Notes |
2015-11-05 19:33:36 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION | | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC, | | (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE | | DEFICIENCIES NOTED. | | | | THESE PLANS HAVE BEEN UNSUCCESSFULLY REVIEWED FOR | | COMPLIANCE A SECOND TIME. BE ADVISED THAT: | | PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT | | WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY | | PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON | | ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A | | PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO | | THE NORMAL FEE | | | | 1. PLEASE NUMBER YOUR PAGES IN A USUAL AND CUSTOMARY | | MANNER WHERE THERE ARE SPECIFIC SECTIONS FOR THE | | VARIOUS TRADES; EACH OF WHICH COMMENCES WITH A SHEET 1 | | SO AS NOT TO BE CONFUSED WITH WHAT APPEARS TO BE AN | | INCOMPLETE SET OF PLANS. AS IT IS, YOU ARE MISSING PAGE | | 2.2E SUPPOSEDLY THE ROOF LAY OUT OF THE ELECTRICAL AND | | MECHANICAL EQUIPMENT. | | 2. YOU SHALL PROVIDE BUILDING ELEVATIONS FOR BOTH THE | | FRONT AND BREEZEWAY FACADES TO ASCERTAIN WHAT IS | | SUPPOSEDLY A DOOR OR A WINDOW. | | 3. PROVIDE WALL SECTIONS TO INDICATE WHICH ARE GLASS | | CURTAIN WALLS IF ANY. | | 4. CONTRARY TO THE SUBMITTED RESPONSE, GENERAL NOTES 1, | | CONTINUE TO MAKE REFERENCE TO A NON-EXISTENT CODE. | | CORRECT THE NOTE ACCORDINGLY. | | 5. NEC 300.5: AMBIENT CONDITIONS DICTATE CONDUCTOR | | INSULATION, NOT THE AWG GAUGE. PER CODE THWN INSULATION | | IS REQUIRED IN WET LOCATIONS. CORRECT YOUR ELECTRICAL | | NOTE 12 ACCORDINGLY. | | 6. NEC 406.9(B): ALL OUTLETS IN WET LOCATIONS IN | | ADDITION TO HAVE WEATHER-PROOF COVERS SHALL BE LISTED | | ?WR? WEATHER-RESISTANT. CORRECT YOU ELECTRICAL NOTE 20 | | ACCORDINGLY. | | 7. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EVERY | | PEDESTRIAN ENTRY. THE PREVIOUS COMMENTS NEVER ASKED IF | | THE EXISTING SIGNS WERE LIT OR NOT, THEY ADDRESSED THE | | CODE REQUIREMENTS WHICH YOU FAILED TO ADHERE TO. | | 8. NEC 210.62: CONTRARY TO YOUR RESPONSE TO MY | | COMMENTS, YOU FAIL TO SHOW THE ?SHOW WINDOW? OUTLETS | | YOU INDICATED ON THE NORTH ELEVATION. | | 9. ALL CORRECTIONS SHALL BE CLOUDED FOR IDENTIFICATION | | AND AS INSTRUCTED BELOW THE NEW PAGES INSERTED INTO THE | | PLANS. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-10-06 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-06 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-10-06 |
Time |
12:05 |
Sent To |
I |
|
Notes |
2015-10-06 13:30:04 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. YOU INCORRECTLY REFERENCE THE 2010 NEC. THE | | APPLICABLE EDITION IS THE 2011 NEC; THERE NEVER WAS A | | 2010 EDITION. | | 2. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ABOVE | | EVERY PEDESTRIAN ENTRY, AS REQUIRED PER NEC 600.5 | | 3. YOU SHALL PROVIDE A DEDICATED SHOW WINDOW RECEPTACLE | | FOR EVERY 12 LINEAR FT. OR PORTION THEREOF OF SHOW | | WINDOW, PER NEC 210.62 | | 4. YOU SHALL INDICATE ON THE LIGHTING PLAN WHAT FIXTURE | | ARRANGEMENTS OR PROVISIONS HAVE BEEN MADE THE REQUIRED | | EMERGENCY LIGHTING. | | 5. YOU SHALL SUBMIT A LIGHT DENSITY CHART AND INDICATE | | COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE | | SECTION C405. | | 6. THERE IS A MISSING EXIT LIGHT AS MARKED ON THE | | LIGHTING FLOOR PLAN. | | 7. THERE IS AN EXIT LIGHT THAT HAS TO BE RELOCATED | | ABOVE THE CORRESPONDING DOOR. | | 8. THE PANEL SCHEDULES DO NOT MATCH THE FLOOR PLAN | | CIRCUIT DESIGNATION. | | 9. INDICATE THE LOCATION OF ALL THE HVAC EQUIPMENT ON | | THE FLOOR PLAN. | | 10. IF THE ALARM CIRCUIT INDICATED ON PANEL A, 19 IS | | FOR A FIRE ALARM SYSTEM, ADDITIONAL REQUIREMENTS ARE | | NECESSARY. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2015-11-18 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-11-18 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-11-18 |
Time |
10:07 |
Sent To |
|
|
Notes |
2015-11-18 10:16:54 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. SHEET 1.4A, INDICATES AN OCCUPANCY LOAD AND SEAT | | LOAD OF 42 AT THE PATIO AREA. THE OCCUPNACY LOAD IS | | MEASURED AT 30 AND SHALL NOT BE EXTENDED BY A SEAT | | COUNT. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-10-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-10-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-10-29 |
Time |
16:29 |
Sent To |
|
|
Notes |
2015-10-30 10:22:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. SHEET 1.4A, INDICATES AN OCCUPANCY LOAD AND SEAT | | LOAD OF 42 AT THE PATIO AREA. THE OCCUPNACY LOAD IS | | MEASURED AT 30 AND SHALL NOT BE EXTENDED BY A SEAT | | COUNT. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2015-08-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-08-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-08-26 |
Time |
10:46 |
Sent To |
|
|
Notes |
2015-08-26 11:20:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | 1) SHEET 1.0A, DOOR SCHEDULE, THE DOOR SCHEDULE | | INDICATES DEADBOLTS ON THE EXIT DOOR. ALL EXIT DOOR | | HARDWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7. | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | EGRESS SIDE. | | | | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING | | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT | | MORE THAN ONE RELEASING OPERATION. THE RELEASING | | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING | | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT | | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO | | OPERATE. | | | | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY | | DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS | | PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH | | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE | | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO | | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. | | | | THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? | | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). | | | | FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 | | OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING | | CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO | | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE | | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC | | HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN | | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR | | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING | | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS | | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN | | HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? | | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). | | A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE | | SUBSTITUTED FOR A KEYED LOCK. | | | | 2) SHEET1.1A, ALL COOKING EQUIPMENT SHALL BE INSTALLED | | AND PROTECTED PER NFPA 96. | | | | 3) SHEET 1.3A & 1.4A, ADD AN EXIT SIGN LEADING TO THE | | REAR EXIT (AS HAND WRITTEN/DRAWN ON THE SHEETS) | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-12-03 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-12-03 |
Time |
18:34 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-11-13 |
Time |
13:47 |
Sent To |
|
|
Notes |
2015-12-03 18:33:59 | 12/3/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO LARGE READY BIN "F". MA | 2015-11-13 13:47:33 | B11 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-11-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2015-11-10 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2015-10-22 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-10-06 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-06 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-21 |
Time |
12:57 |
Sent To |
|
|
Notes |
2015-10-06 13:32:21 | 10/6/15 FAILED EVERY TRADE REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO LARGE DENIED BIN "M". MA | 2015-08-21 12:57:40 | B12 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-11-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-11-20 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-11-20 |
Time |
10:18 |
Sent To |
|
|
Notes |
2015-11-20 11:20:15 | MECHANICAL PROVISOS: | | PERMIT #15080784 | | 11/20/15 | | | | 1) HVAC CONTRACTOR SHALL ADJUST THE OUTSIDE AIR INTAKES | | OF THE AC SYSTEMS TO MATCH THE REDLINE VALUES SHOWN IN | | THE SCHEDULE ON SHEET 3.2M | | 2) AC TEST AND BALANCE REPORT REQUIRED AT FINAL | | INSPECTION. | | 3) MANUFACTURER'S SPECIFICATIONS FOR THE FIRE/SMOKE | | DAMPERS AND FIRE STOPPING SHALL BE ON-SITE AT TIME OF | | INSPECTION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-11-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-11-04 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-11-04 |
Time |
16:46 |
Sent To |
|
|
Notes |
2015-11-04 17:04:32 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080784 | | 11/4/2015 | | | | 1) SHEET 3.2M: THE O/A CALCULATIONS ARE INCORRECT. | | REFER TO TABLE 403.3: 7.5 CFM PER PERSON + .18 CFM PER | | SF. IS REQUIRED FOR THE DINING AREAS. PLEASE REVISE THE | | VENTILATION AND AIR BALANCE SCHEDULES ACCORDINGLY. | | 2) 3.2M: THE REVISED AC EQUIPMENT SCHEDULE INDICATES A | | NEW 5-TON AC SYSTEM: REFER TO SECTION C403.2.1 FBC-14 | | ENERGY CONSERVATION AND SUBMIT COOLING AND HEATING LOAD | | CALCULATIONS IN ACCORDANCE WITH THE ASHRAE STANDARD 183 | | OR ACCA MANUAL N. | | 3) REFER TO SECTION C101.4.3 FBC-14 ENERGY CONSERVATION | | AND PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED | | RENOVATION. SEE SECTION C101.5 FOR COMPLIANCE SUBMITTAL | | INFORMATION. | | 4) SHEETS 1.3A & 3.2M: INDICATE HOW ACCESS FOR SERVICE | | WILL BE PROVIDED TO THE NEW AHU-1 ABOVE THE MEN'S ROOM | | CEILING. THIS APPEARS TO BE A HARD CEILING ALTHOUGH IT | | IS NOT LABELED ON THE RCP. IT IS ALSO NOT CLEAR HOW | | ACCESS WILL BE PROVIDED FOR AHU'S 2 & 3. PLEASE NOTE | | THAT CLEAR OPENINGS FOR ACCESS PANELS SHALL BE LARGE | | ENOUGH TO REMOVE EQUIPMENT WITHOUT REMOVING PERMANENT | | CONSTRUCTION- SECTION 306.1. | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE F/S | | DAMPER AT TTHE BOTTOM OF THE FIRE-RATED SHAFT WITH A | | REVIEW AND APPROVAL STAMP FROM THE ENGINEER OF RECORD. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-09-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-09-02 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-09-02 |
Time |
07:44 |
Sent To |
|
|
Notes |
2015-09-02 08:31:22 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080784 | | 9/2/15 | | | | 1) SHEET 3.2M: REFER TO TABLE 403.3 FBC-14 MECHANICAL | | AND SHOW THE CALCULATIONS FOR THE OUTSIDE AIR CFM'S | | LISTED IN THE EQUIPMENT SCHEDULE, PROVIDE A SCHEDULE | | THAT LISTS THE REQUIRED AND PROVIDED CFM'S FOR EACH | | ROOM, SPACE, OR AREA. | | 2) 3.2M: PROVIDE AN AIR BALANCE SCHEDULE. | | 3) 3.2M: THE EF2 'S SHOWN IN THE TOILET ROOMS ARE | | LISTED AS HEAT HOOD EXHAUST FANS IN THE SCHEDULE- | | PLEASE CORRECT. | | 4) 3.2M: PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | PRESSURES FOR INSTALLATION OF THE ROOF-MOUNTED | | CONDENSER AND STAND- SECTION 301.15. SUBMIT TWO COPIES | | OF THE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR | | THE RM ENTERPRISES ROOF STAND. | | 5) 3.2M: PROVIDE DUCT HANGING AND CONNECTION DETAILS. | | 6) 3.2M: PLEASE ENLARGE THE SEPARATE PERMIT NOTE FOR | | THE KITCHEN HOODS-, AND ADD BOTH THE GREASE AND HEAT | | HOODS, AND THE WALK IN COOLER TO THE NOTE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2015-11-19 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2015-11-19 |
Time |
08:16 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2015-11-19 |
Time |
08:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2015-11-02 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2015-11-02 |
Time |
12:32 |
Sent To |
|
|
Notes |
2015-11-02 12:36:17 | 2ND REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1. TOILET CLEARANCE SHALL COMPLY WITH FBC ACC. 2014 SEC | | 604.2 LOCATION. | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR | | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY | | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. | | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR | | RIGHT-HAND APPROACH. | | 2. GRAB BARS SHALL COMPLY WITH FBC ACC. 2014 SEC 609.4 | | POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, AND 604.5.2 REAR WALL. | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | 3. | | THE BTU LOADS LISTED ON THE EQUIPMENT SCHEDULE ARE NOT | | THE SAME AS THE ONES LISTED ON THE GAS LOAD CALCULATION | | DETAIL ON SHEET 3.1P AND THE BTU TOTALS ON THE RISER | | DON'T MATCH UP WITH THE GAS LOAD CALCULATION ALL BTU | | LOADS MUST MATCH BEFORE I CAN DO A COMPLETE GAS REVIEW. | | PER WPB AMEND. TO FBC SEC107.2.1 | | 4. SHEET 1.1A ON THE EQUIPMENT SCHEDULE # 12, 13 ARE | | MISSING THE GAS CONNECTION AND BTU PLEASE PROVIDE. PER | | WPB AMEND. TO FBC SEC107.2.1 | | 5. REGULATOR SHALL BE INSTALLED WITH VALVE AND CAP FOR | | FUTURE FIXTURES SHOW ON RISER. PER WPB AMEND. TO FBC | | SEC107.2.1 | | 6. TOILET IN MEN'S BATHROOM STILL MISSING FROM RISER. | | PER WPB AMEND. TO FBC SEC107.2.1 | | | | 7. VENT DETAIL FOR TANKLESS HEATER TO GENERIC PLEASE | | PROVIDE MANUFACTURE SPECS ALONG WITH SIZE LENGTH AND | | CONFIGURATION PER WPB AMEND. TO FBC SEC107.2.1 | | 8. SHEET 3.0P ON FLOOR PLAN IT SHOWS STORAGE TANK AS 50 | | GAL ON WATER RISER IT'S SHOWN AS 40 GAL PLEASE CLARIFY. | | PER WPB AMEND. TO FBC SEC107.2.1 | | 9. THE WATER RISER DIAGRAM IS MISSING HOT AND COLD STUB | | OUTS FOR HAND SINK #44 ON SHEET 1.1A AND #34 ON SHEET | | 1.1A PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC107.2.1 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-09-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-09-05 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-05 |
Time |
06:19 |
Sent To |
|
|
Notes |
2015-09-05 08:43:17 | 1) SHT.1.0 (A) - THE ACCESSIBILITIY FIGURES ARE FROM A | | PREVIOUS CODE EDITION. SUBMIT THE CORRECT FIGURES FROM | | THE 2014 FBC-ACCESSIBILITY. | | 2) THE OCCUPANT LOAD IS SHOWN AS 156 PERSONS. THE | | NUMBER OF WATER CLOSETS IS DEFICIENT FOR THE OCCUPANT | | LOAD. COMPLY WITH 2014 FBC-PLUMBING TABLE 403.1. | | 3) SHT.1.1 (A). SHOW THE BTU LOAD FOR EACH GAS | | APPLIANCE ON THE EQUIPMENT SCHEDULE.WPB AMEND. TO FBC | | SEC. 107.2.1. | | 4) SHT.3.1P - THE GAS TABLE REFERENCED IS FOR UNDILUTED | | PROPANE @10 PSI BUT THE PLAN NOTES 11 INCH WATER COLUMN | | WITH A .5 PRESSURE DROP SYSTEM. CLARIFY. | | 5) A THOROUGH REVIEW OF THE GAS SYSTEM CANNOT BE DONE | | UNTIL THE THE CORRECT SIZING TABLE IS SUBMITTED. | | 6) THE GAS LOAD CALC TABLE LISTS AN 1 1/2 INCH GAS LINE | | TO THE HOT PLATE AND THIS LINE IS FED BY A 1 INCH LINE? | | THIS DOES NOT MAKE SENSE. CLARIFY. | | 7) SIZE ALL PIPE SECTION OF THE GAS RISER. WPB AMEND. | | TO FBC SEC. 107.2.1. THE ENTIRE SYSTEM SHALL BE SIZED | | USING THE 150 FEET COLUMN. | | 8) THE HOT PLATE IS NOT SHOWN ON THE GAS RISER. | | CLARIFY. | | 9) WHAT IS THE NUMBER "2138K ON THE GAS DRAWING? | | 10) SHT. 3.1P NOTES THE GAS IS SIZED PER 2010 FUEL GAS | | CODE. IF THIS IS NEW PIPING, IT SHALL BE SIZED PER THE | | 2014 FUEL GAS CODE. | | 11) THE WATER CLOSET IN THE MEN'S RESTROOM IS MISSING | | FROM THE SANITARY RISER. | | 12) THE SANITARY VENT FOR THE TOILET ROOMS GOES | | NOWHERE. CLARIFY. | | 13) SHOW CONTINUATION POINT OF THE SANITARY VENT FOR | | THE MOP SINK. | | 14) SUBMIT DETAILS FOR THE VENT FOR THE TANKLESS WATER | | HEATER. | | 15) THE LAYOUT OF THE DRAIN FOR THE ICE BIN/ICE MAKER | | ON THE PLAN VIEW DOES NOT MATCH THE RISER DIAGRAM. | | CLARIFY. | | 16) IF THE WASTE FROM THE ICE MAKER/ICE BIN IS CLEAR | | WATER WASTE, IT SHALL NOT BE DISCHARGED TO THE GREASY | | WASTE AS SHOWN. CLARIFY.2014 FPC SEC. 1003..2. | | 17) SHT. 3.1P - SHOWS A RINSE FAUCET LABELED AS GW | | DISCHARGING TO THE SANITARY. CLARIFY.MY CALCULATIONS | | FOR THE GREASE INTERCEPTOR ARE 1856 NOT 1956. CORRECT | | THE CALCULATIONS ON THE PLANS. | | 18) SHT. 3.1P - SHOWS THE SANITARY DISCHARGING TO THE | | GREASE INTERCEPTOR AND THE GREASY WASTE TO NOWHERE. | | CLARIFY. | | 19) SHOW THE SIZE AND LOCATION OF THE LP TANK. INDICATE | | IF IT IS NEW OR EXISTING, ABOVE GROUND OR UNDERGROUND, | | NEAR A TRAFFIC AREA OR WHERE TRAFFIC COULD BE EXPECTED, | | ETC. | | 20) SHOW THE DISTANCE OF THE LP TANK FROM THE | | STRUCTURE. | | 21) SUBMIT WIND LOAD ENGINEERING FOR THE TANK IF IT IS | | ABOVEGROUND. 2014 FGC SEC.301.10. | | 22) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. | | TO FBC SEC. 107.3.5.1.3. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2015-11-10 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2015-11-10 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2015-11-10 |
Time |
15:22 |
Sent To |
|
|
Notes |
2015-11-10 15:23:21 | TILES ON FACADE ARE NOT NECESSARY, THEY CAN BE REMOVED | | IF DESIRED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-09-25 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2015-09-25 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2015-09-25 |
Time |
15:43 |
Sent To |
|
|
Notes |
2015-09-25 15:49:14 | 1. PLEASE PROVIDE AN ELEVATION INDICATING THE CHANGES | | TO THE CLEMATIS STREET FACADE. | | 2. THE REMOVAL OF THE STOREFRONT IS RECESSING THE | | BUILDING FACADE BEYOND THE REQUIRED SETBACK LINE. ALONG | | THE CLEMATIS CONSERVATION DISTRICT THE BUILDING | | FRONTAGE SHALL BE LOCATED MATCHING THE ADJACENT | | BUILDING. IF THE DESIRE IS TO HAVE OUTDOOR SEATING, THE | | USE OF FOLDABLE DOORS WILL ACCOMPLISH THE GOAL BUT | | MAINTAN THE CONTINUOUS BUILDING FRONTAGE ALONG THE | | STREET. | | FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|