Plan Review Details - Permit 15080784
Plan Review Stops For Permit 15080784
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-20 Cont ID  
Sent By   Date 2015-11-20 Time   Rev Time 0.00
Received By   Date 2015-11-20 Time 15:44 Sent To  
Notes
2015-11-20 16:35:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080784
 ADD: 330 CLEMATIS STREET # 110
 CONT: TBD
 TEL: (561)686-5853
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3D REVIEW
 DATE: THURS. FRI. NOV. 20/ 2015
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES
  
  
 1) PLEASE PROVIDE COMPLIANCE WITH THE BAR AREA IN THE
 EXTERIOR WALL. SHOW HOW COMPLIANCE WITH 2014
 ACCESSIBILITY CODE 226.2 DISPERSION. DINING SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES.
 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT, PLEASE SHOW
 HOW COMPLIANCE WITH THE HEIGHT OF THE BAR WILL BE
 ACHIEVED. THE TOP OF DINING SURFACES SHALL BE A MINIMUM
 OF 28 INCHES AND A MAXIMUM OF 34 INCHES ABOVE THE
 FINISH FLOOR.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-04 Cont ID  
Sent By jwitmer Date 2015-11-04 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-11-04 Time 07:30 Sent To  
Notes
2015-11-05 08:32:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080784
 ADD: 330 CLEMATIS STREET # 110
 CONT: TBD
 TEL: (561)686-5853
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 11/2015
 ACTION: BUILDING PROVISO
  
 1) DOOR NUMBER # 7 NEEDS TO BE REVERSED TO A OUTSWING
 DOOR, FOR COMPLIANCE WITH 2014 FBC-ACCESSIBLITY CODE
 404.2.4.1 MANEUVERING CLEARANCES, 18 INCHES ON THE
 LATCH SIDE OF THE DOOR.
  
 2) PLEASE PROVIDE COMPLIANCE WITH THE BAR AREA IN THE
 EXTERIOR WALL. SHOW HOW COMPLIANCE WITH 2014
 ACCESSIBILITY CODE 226.2 DISPERSION.DINING SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES.
 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT, PLEASE SHOW
 HOW COMPLIANCE WITH THE HEIGHT OF THE BAR WILL BE
 ACHIEVED. THE TOP OF DINING SURFACES SHALL BE A MINIMUM
 OF 28 INCHES AND A MAXIMUM OF 34 INCHES ABOVE THE
 FINISH FLOOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 11:57 Rev Time  
Received By jwitmer Date 2015-09-10 Time 09:03 Sent To  
Notes
2015-09-10 11:57:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080784
 ADD: 330 CLEMATIS STREET # 110
 CONT: TBD
 TEL: (561)686-5853
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 10/2014
 ACTION: DENIED
  
 1) MISSING CODE DESIGN, THE COVERSHEET INDICATES A
 BUILDING TYPE 3B. SPRINKLERED OR NOT. TABLE 503 & TABLE
 508.4. THE CONCERN IS NOT THE VERTICAL OCCUPANCY BUT
 THE HORIZONTAL OCCUPANCY SEPARATION, SEE 2014 FBC-B
 TABLE 707.3.10.
  
 2) THERE IS A DESCREPANCY IN PLANS BETWEEN SHEET C1 THE
 COVERSHEET AND SHEET 1.4 FOR THE WAY THE OCCUPANT LOAD
 IS COMPUTED, THERE IS A DISCREPANCY IN THE OCCUPANT
 LOAD. NOTE THE EXTERIOR SEASONAL SEATING WILL STILL
 NEED TO EXIT THROUGH A DOORWAY.
  
 3)THE COVERSHEET UNDER THE HEADING OF NUMBER OF SEATS
 LIST 52 PEOPLE UNDER THE EXTERIOR PATIO. PLEASE THE
 LIFE SAFETY PLAN DOES NOT SHOW 2 EXITS FROM THIS SPACE.
 PLEAASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1015.2.1.
 TABLE 1015.1 MAX 1 EXIT 49 FOR ASSEMBLY OCCUPANCY.
  
 4) THE LIFE SAFETY PLAN 1.4 DOES NOT IDENTIFY THE
 DOORS, SHEET 1.0A INDICATES THE DOOR IDENTIFICATION
 TAGS BUT NOT THE EXIT SIGNS. PLEASE IDENTIFY THE DOORS
 ON SHEET 1.4 THE LIFE SAFETY TO VERIFY THE EXITING. THE
 LIFE SAFETY PLANS DO NOT INDICATE THE EXITING PATERNS
 FOR THE OCCUPANTS.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 5) THE SHEET 1.4 LIFE SAFETY SHEET VERSES 2.0E DOES NOT
 MATCH UP WITH BATTERY EXIT SIGNS W/ FLOODS. DISCREPANCY
 IN PLANS. ADDITIONAL INFORMAION IS REQUIRED. DEPENDING
 ON THE FINAL VERSION OF PLANS ADDITIONAL COMMENTS MAY
 OCCUR.
  
 6) THE SHEET 1.4 THE LIFE SAFETY PLAN SHOWS A EXIT FROM
 THE KITCHEN, WITH THE EXIT DOOR OF THE KITCHEN YOU
 ENTER THE EXIT DISCHARGE. THE PLANS MUST MEET ALL OF
 THE REQUIREMENTS OF 2014 FBC-B 1027.1 NOTE THE WALLS DO
 NOT INDICATE AN Y RATING. ALSO NOTE THE EAST WALL OF
 THE EXTERIOR DINING ROOM APPEARS TO HAVE A DOOR OPENING
 WITHOUT A DOOR WAY. THE EXISTING SITE HAS A GATE AT THE
 END OF THE EXIT DISCHARGE NOT SHOWN ON THE PROPOSED
 PLANS, WILL THIS BE REMOVED, IF NOT IS IT LOCKABLE?
  
 7) THERE ARE NEW EXTERIOR ELEMENTS FOR COMPONENTS AND
 CLADDING PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS/
 EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA OR
 PRESSURES ASSOCIATED WITH THE NEW OPENINGS:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 9.2. RISK CATEGORY.
  
 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 9.4APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 9.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 10) SHEET 1.6 HAS A NOTE THAT IN THE NEW EXTERIOR
 DINING ROOM THE THERE IS AN ORIGINAL DROP CEILING,
 PLEASE PROVIDE WILL TYPE OF CEILING IS IT. WILL THE
 CEILING TAKE POSITIVE PRESSURES FROM A HIGH WIND EVENT.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) NEITHER DOES M2.2 OR M3.2 INDICATE IF THE EXISITNG
 EXHAUST DUCT AND ROOF TOP FAN ARE TO BE REUSED FOR THE
 HOOD EXHAUST, NOR IS THERE ANY INFORMATION HOW THE DUCT
 IS CHASED THROUGH THE 2ND FLOOR ASSEMBLY AND TO THE
 ROOF TOP? 107.2.1.3.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-03 Cont ID  
Sent By albarran Date 2015-12-03 Time 18:30 Rev Time 0.00
Received By albarran Date 2015-12-03 Time 17:47 Sent To I
Notes
2015-12-03 18:31:11ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 19:32 Rev Time 0.00
Received By albarran Date 2015-11-05 Time 18:02 Sent To Z
Notes
2015-11-05 19:33:36THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC,
 (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE
 DEFICIENCIES NOTED.
  
 THESE PLANS HAVE BEEN UNSUCCESSFULLY REVIEWED FOR
 COMPLIANCE A SECOND TIME. BE ADVISED THAT:
 PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE
  
 1. PLEASE NUMBER YOUR PAGES IN A USUAL AND CUSTOMARY
 MANNER WHERE THERE ARE SPECIFIC SECTIONS FOR THE
 VARIOUS TRADES; EACH OF WHICH COMMENCES WITH A SHEET 1
 SO AS NOT TO BE CONFUSED WITH WHAT APPEARS TO BE AN
 INCOMPLETE SET OF PLANS. AS IT IS, YOU ARE MISSING PAGE
 2.2E SUPPOSEDLY THE ROOF LAY OUT OF THE ELECTRICAL AND
 MECHANICAL EQUIPMENT.
 2. YOU SHALL PROVIDE BUILDING ELEVATIONS FOR BOTH THE
 FRONT AND BREEZEWAY FACADES TO ASCERTAIN WHAT IS
 SUPPOSEDLY A DOOR OR A WINDOW.
 3. PROVIDE WALL SECTIONS TO INDICATE WHICH ARE GLASS
 CURTAIN WALLS IF ANY.
 4. CONTRARY TO THE SUBMITTED RESPONSE, GENERAL NOTES 1,
 CONTINUE TO MAKE REFERENCE TO A NON-EXISTENT CODE.
 CORRECT THE NOTE ACCORDINGLY.
 5. NEC 300.5: AMBIENT CONDITIONS DICTATE CONDUCTOR
 INSULATION, NOT THE AWG GAUGE. PER CODE THWN INSULATION
 IS REQUIRED IN WET LOCATIONS. CORRECT YOUR ELECTRICAL
 NOTE 12 ACCORDINGLY.
 6. NEC 406.9(B): ALL OUTLETS IN WET LOCATIONS IN
 ADDITION TO HAVE WEATHER-PROOF COVERS SHALL BE LISTED
 ?WR? WEATHER-RESISTANT. CORRECT YOU ELECTRICAL NOTE 20
 ACCORDINGLY.
 7. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EVERY
 PEDESTRIAN ENTRY. THE PREVIOUS COMMENTS NEVER ASKED IF
 THE EXISTING SIGNS WERE LIT OR NOT, THEY ADDRESSED THE
 CODE REQUIREMENTS WHICH YOU FAILED TO ADHERE TO.
 8. NEC 210.62: CONTRARY TO YOUR RESPONSE TO MY
 COMMENTS, YOU FAIL TO SHOW THE ?SHOW WINDOW? OUTLETS
 YOU INDICATED ON THE NORTH ELEVATION.
 9. ALL CORRECTIONS SHALL BE CLOUDED FOR IDENTIFICATION
 AND AS INSTRUCTED BELOW THE NEW PAGES INSERTED INTO THE
 PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-06 Time 13:29 Rev Time 0.00
Received By albarran Date 2015-10-06 Time 12:05 Sent To I
Notes
2015-10-06 13:30:04PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU INCORRECTLY REFERENCE THE 2010 NEC. THE
 APPLICABLE EDITION IS THE 2011 NEC; THERE NEVER WAS A
 2010 EDITION.
 2. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ABOVE
 EVERY PEDESTRIAN ENTRY, AS REQUIRED PER NEC 600.5
 3. YOU SHALL PROVIDE A DEDICATED SHOW WINDOW RECEPTACLE
 FOR EVERY 12 LINEAR FT. OR PORTION THEREOF OF SHOW
 WINDOW, PER NEC 210.62
 4. YOU SHALL INDICATE ON THE LIGHTING PLAN WHAT FIXTURE
 ARRANGEMENTS OR PROVISIONS HAVE BEEN MADE THE REQUIRED
 EMERGENCY LIGHTING.
 5. YOU SHALL SUBMIT A LIGHT DENSITY CHART AND INDICATE
 COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE
 SECTION C405.
 6. THERE IS A MISSING EXIT LIGHT AS MARKED ON THE
 LIGHTING FLOOR PLAN.
 7. THERE IS AN EXIT LIGHT THAT HAS TO BE RELOCATED
 ABOVE THE CORRESPONDING DOOR.
 8. THE PANEL SCHEDULES DO NOT MATCH THE FLOOR PLAN
 CIRCUIT DESIGNATION.
 9. INDICATE THE LOCATION OF ALL THE HVAC EQUIPMENT ON
 THE FLOOR PLAN.
 10. IF THE ALARM CIRCUIT INDICATED ON PANEL A, 19 IS
 FOR A FIRE ALARM SYSTEM, ADDITIONAL REQUIREMENTS ARE
 NECESSARY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-11-18 Cont ID  
Sent By pleduc Date 2015-11-18 Time   Rev Time 0.00
Received By pleduc Date 2015-11-18 Time 10:07 Sent To  
Notes
2015-11-18 10:16:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET 1.4A, INDICATES AN OCCUPANCY LOAD AND SEAT
 LOAD OF 42 AT THE PATIO AREA. THE OCCUPNACY LOAD IS
 MEASURED AT 30 AND SHALL NOT BE EXTENDED BY A SEAT
 COUNT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-30 Cont ID  
Sent By pleduc Date 2015-10-30 Time   Rev Time 0.00
Received By pleduc Date 2015-10-29 Time 16:29 Sent To  
Notes
2015-10-30 10:22:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET 1.4A, INDICATES AN OCCUPANCY LOAD AND SEAT
 LOAD OF 42 AT THE PATIO AREA. THE OCCUPNACY LOAD IS
 MEASURED AT 30 AND SHALL NOT BE EXTENDED BY A SEAT
 COUNT.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-26 Cont ID  
Sent By pleduc Date 2015-08-26 Time   Rev Time 0.00
Received By pleduc Date 2015-08-26 Time 10:46 Sent To  
Notes
2015-08-26 11:20:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET 1.0A, DOOR SCHEDULE, THE DOOR SCHEDULE
 INDICATES DEADBOLTS ON THE EXIT DOOR. ALL EXIT DOOR
 HARDWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING
 CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
 A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 2) SHEET1.1A, ALL COOKING EQUIPMENT SHALL BE INSTALLED
 AND PROTECTED PER NFPA 96.
  
 3) SHEET 1.3A & 1.4A, ADD AN EXIT SIGN LEADING TO THE
 REAR EXIT (AS HAND WRITTEN/DRAWN ON THE SHEETS)
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-03 Cont ID  
Sent By albarran Date 2015-12-03 Time 18:34 Rev Time 0.00
Received By albarran Date 2015-11-13 Time 13:47 Sent To  
Notes
2015-12-03 18:33:5912/3/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE READY BIN "F". MA
2015-11-13 13:47:33B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-10 Cont ID  
Sent By cpuell Date 2015-11-10 Time 16:46 Rev Time 0.00
Received By cpuell Date 2015-10-22 Time 09:15 Sent To  
Notes
2015-10-23 09:15:35B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-06 Time 13:30 Rev Time 0.00
Received By albarran Date 2015-08-21 Time 12:57 Sent To  
Notes
2015-10-06 13:32:2110/6/15 FAILED EVERY TRADE REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "M". MA
2015-08-21 12:57:40B12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-20 Cont ID  
Sent By ccole Date 2015-11-20 Time 11:15 Rev Time 0.00
Received By ccole Date 2015-11-20 Time 10:18 Sent To  
Notes
2015-11-20 11:20:15MECHANICAL PROVISOS:
 PERMIT #15080784
 11/20/15
  
 1) HVAC CONTRACTOR SHALL ADJUST THE OUTSIDE AIR INTAKES
 OF THE AC SYSTEMS TO MATCH THE REDLINE VALUES SHOWN IN
 THE SCHEDULE ON SHEET 3.2M
 2) AC TEST AND BALANCE REPORT REQUIRED AT FINAL
 INSPECTION.
 3) MANUFACTURER'S SPECIFICATIONS FOR THE FIRE/SMOKE
 DAMPERS AND FIRE STOPPING SHALL BE ON-SITE AT TIME OF
 INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-11-04 Cont ID  
Sent By ccole Date 2015-11-04 Time 16:46 Rev Time 0.00
Received By ccole Date 2015-11-04 Time 16:46 Sent To  
Notes
2015-11-04 17:04:322ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080784
 11/4/2015
  
 1) SHEET 3.2M: THE O/A CALCULATIONS ARE INCORRECT.
 REFER TO TABLE 403.3: 7.5 CFM PER PERSON + .18 CFM PER
 SF. IS REQUIRED FOR THE DINING AREAS. PLEASE REVISE THE
 VENTILATION AND AIR BALANCE SCHEDULES ACCORDINGLY.
 2) 3.2M: THE REVISED AC EQUIPMENT SCHEDULE INDICATES A
 NEW 5-TON AC SYSTEM: REFER TO SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION AND SUBMIT COOLING AND HEATING LOAD
 CALCULATIONS IN ACCORDANCE WITH THE ASHRAE STANDARD 183
 OR ACCA MANUAL N.
 3) REFER TO SECTION C101.4.3 FBC-14 ENERGY CONSERVATION
 AND PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED
 RENOVATION. SEE SECTION C101.5 FOR COMPLIANCE SUBMITTAL
 INFORMATION.
 4) SHEETS 1.3A & 3.2M: INDICATE HOW ACCESS FOR SERVICE
 WILL BE PROVIDED TO THE NEW AHU-1 ABOVE THE MEN'S ROOM
 CEILING. THIS APPEARS TO BE A HARD CEILING ALTHOUGH IT
 IS NOT LABELED ON THE RCP. IT IS ALSO NOT CLEAR HOW
 ACCESS WILL BE PROVIDED FOR AHU'S 2 & 3. PLEASE NOTE
 THAT CLEAR OPENINGS FOR ACCESS PANELS SHALL BE LARGE
 ENOUGH TO REMOVE EQUIPMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION- SECTION 306.1.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE F/S
 DAMPER AT TTHE BOTTOM OF THE FIRE-RATED SHAFT WITH A
 REVIEW AND APPROVAL STAMP FROM THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-02 Cont ID  
Sent By ccole Date 2015-09-02 Time 07:59 Rev Time 0.00
Received By ccole Date 2015-09-02 Time 07:44 Sent To  
Notes
2015-09-02 08:31:221ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080784
 9/2/15
  
 1) SHEET 3.2M: REFER TO TABLE 403.3 FBC-14 MECHANICAL
 AND SHOW THE CALCULATIONS FOR THE OUTSIDE AIR CFM'S
 LISTED IN THE EQUIPMENT SCHEDULE, PROVIDE A SCHEDULE
 THAT LISTS THE REQUIRED AND PROVIDED CFM'S FOR EACH
 ROOM, SPACE, OR AREA.
 2) 3.2M: PROVIDE AN AIR BALANCE SCHEDULE.
 3) 3.2M: THE EF2 'S SHOWN IN THE TOILET ROOMS ARE
 LISTED AS HEAT HOOD EXHAUST FANS IN THE SCHEDULE-
 PLEASE CORRECT.
 4) 3.2M: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 PRESSURES FOR INSTALLATION OF THE ROOF-MOUNTED
 CONDENSER AND STAND- SECTION 301.15. SUBMIT TWO COPIES
 OF THE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR
 THE RM ENTERPRISES ROOF STAND.
 5) 3.2M: PROVIDE DUCT HANGING AND CONNECTION DETAILS.
 6) 3.2M: PLEASE ENLARGE THE SEPARATE PERMIT NOTE FOR
 THE KITCHEN HOODS-, AND ADD BOTH THE GREASE AND HEAT
 HOODS, AND THE WALK IN COOLER TO THE NOTE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-11-19 Cont ID  
Sent By gjohnson Date 2015-11-19 Time 08:16 Rev Time 0.00
Received By gjohnson Date 2015-11-19 Time 08:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-11-03 Cont ID  
Sent By gjohnson Date 2015-11-02 Time 08:29 Rev Time 0.00
Received By gjohnson Date 2015-11-02 Time 12:32 Sent To  
Notes
2015-11-02 12:36:172ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. TOILET CLEARANCE SHALL COMPLY WITH FBC ACC. 2014 SEC
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
 2. GRAB BARS SHALL COMPLY WITH FBC ACC. 2014 SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, AND 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 3.
 THE BTU LOADS LISTED ON THE EQUIPMENT SCHEDULE ARE NOT
 THE SAME AS THE ONES LISTED ON THE GAS LOAD CALCULATION
 DETAIL ON SHEET 3.1P AND THE BTU TOTALS ON THE RISER
 DON'T MATCH UP WITH THE GAS LOAD CALCULATION ALL BTU
 LOADS MUST MATCH BEFORE I CAN DO A COMPLETE GAS REVIEW.
 PER WPB AMEND. TO FBC SEC107.2.1
 4. SHEET 1.1A ON THE EQUIPMENT SCHEDULE # 12, 13 ARE
 MISSING THE GAS CONNECTION AND BTU PLEASE PROVIDE. PER
 WPB AMEND. TO FBC SEC107.2.1
 5. REGULATOR SHALL BE INSTALLED WITH VALVE AND CAP FOR
 FUTURE FIXTURES SHOW ON RISER. PER WPB AMEND. TO FBC
 SEC107.2.1
 6. TOILET IN MEN'S BATHROOM STILL MISSING FROM RISER.
 PER WPB AMEND. TO FBC SEC107.2.1
  
 7. VENT DETAIL FOR TANKLESS HEATER TO GENERIC PLEASE
 PROVIDE MANUFACTURE SPECS ALONG WITH SIZE LENGTH AND
 CONFIGURATION PER WPB AMEND. TO FBC SEC107.2.1
 8. SHEET 3.0P ON FLOOR PLAN IT SHOWS STORAGE TANK AS 50
 GAL ON WATER RISER IT'S SHOWN AS 40 GAL PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC107.2.1
 9. THE WATER RISER DIAGRAM IS MISSING HOT AND COLD STUB
 OUTS FOR HAND SINK #44 ON SHEET 1.1A AND #34 ON SHEET
 1.1A PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 08:45 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 06:19 Sent To  
Notes
2015-09-05 08:43:171) SHT.1.0 (A) - THE ACCESSIBILITIY FIGURES ARE FROM A
 PREVIOUS CODE EDITION. SUBMIT THE CORRECT FIGURES FROM
 THE 2014 FBC-ACCESSIBILITY.
 2) THE OCCUPANT LOAD IS SHOWN AS 156 PERSONS. THE
 NUMBER OF WATER CLOSETS IS DEFICIENT FOR THE OCCUPANT
 LOAD. COMPLY WITH 2014 FBC-PLUMBING TABLE 403.1.
 3) SHT.1.1 (A). SHOW THE BTU LOAD FOR EACH GAS
 APPLIANCE ON THE EQUIPMENT SCHEDULE.WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) SHT.3.1P - THE GAS TABLE REFERENCED IS FOR UNDILUTED
 PROPANE @10 PSI BUT THE PLAN NOTES 11 INCH WATER COLUMN
 WITH A .5 PRESSURE DROP SYSTEM. CLARIFY.
 5) A THOROUGH REVIEW OF THE GAS SYSTEM CANNOT BE DONE
 UNTIL THE THE CORRECT SIZING TABLE IS SUBMITTED.
 6) THE GAS LOAD CALC TABLE LISTS AN 1 1/2 INCH GAS LINE
 TO THE HOT PLATE AND THIS LINE IS FED BY A 1 INCH LINE?
 THIS DOES NOT MAKE SENSE. CLARIFY.
 7) SIZE ALL PIPE SECTION OF THE GAS RISER. WPB AMEND.
 TO FBC SEC. 107.2.1. THE ENTIRE SYSTEM SHALL BE SIZED
 USING THE 150 FEET COLUMN.
 8) THE HOT PLATE IS NOT SHOWN ON THE GAS RISER.
 CLARIFY.
 9) WHAT IS THE NUMBER "2138K ON THE GAS DRAWING?
 10) SHT. 3.1P NOTES THE GAS IS SIZED PER 2010 FUEL GAS
 CODE. IF THIS IS NEW PIPING, IT SHALL BE SIZED PER THE
 2014 FUEL GAS CODE.
 11) THE WATER CLOSET IN THE MEN'S RESTROOM IS MISSING
 FROM THE SANITARY RISER.
 12) THE SANITARY VENT FOR THE TOILET ROOMS GOES
 NOWHERE. CLARIFY.
 13) SHOW CONTINUATION POINT OF THE SANITARY VENT FOR
 THE MOP SINK.
 14) SUBMIT DETAILS FOR THE VENT FOR THE TANKLESS WATER
 HEATER.
 15) THE LAYOUT OF THE DRAIN FOR THE ICE BIN/ICE MAKER
 ON THE PLAN VIEW DOES NOT MATCH THE RISER DIAGRAM.
 CLARIFY.
 16) IF THE WASTE FROM THE ICE MAKER/ICE BIN IS CLEAR
 WATER WASTE, IT SHALL NOT BE DISCHARGED TO THE GREASY
 WASTE AS SHOWN. CLARIFY.2014 FPC SEC. 1003..2.
 17) SHT. 3.1P - SHOWS A RINSE FAUCET LABELED AS GW
 DISCHARGING TO THE SANITARY. CLARIFY.MY CALCULATIONS
 FOR THE GREASE INTERCEPTOR ARE 1856 NOT 1956. CORRECT
 THE CALCULATIONS ON THE PLANS.
 18) SHT. 3.1P - SHOWS THE SANITARY DISCHARGING TO THE
 GREASE INTERCEPTOR AND THE GREASY WASTE TO NOWHERE.
 CLARIFY.
 19) SHOW THE SIZE AND LOCATION OF THE LP TANK. INDICATE
 IF IT IS NEW OR EXISTING, ABOVE GROUND OR UNDERGROUND,
 NEAR A TRAFFIC AREA OR WHERE TRAFFIC COULD BE EXPECTED,
 ETC.
 20) SHOW THE DISTANCE OF THE LP TANK FROM THE
 STRUCTURE.
 21) SUBMIT WIND LOAD ENGINEERING FOR THE TANK IF IT IS
 ABOVEGROUND. 2014 FGC SEC.301.10.
 22) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-11-10 Cont ID  
Sent By aaponte Date 2015-11-10 Time 15:22 Rev Time 0.00
Received By aaponte Date 2015-11-10 Time 15:22 Sent To  
Notes
2015-11-10 15:23:21TILES ON FACADE ARE NOT NECESSARY, THEY CAN BE REMOVED
 IF DESIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-25 Cont ID  
Sent By aaponte Date 2015-09-25 Time 15:43 Rev Time 0.00
Received By aaponte Date 2015-09-25 Time 15:43 Sent To  
Notes
2015-09-25 15:49:141. PLEASE PROVIDE AN ELEVATION INDICATING THE CHANGES
 TO THE CLEMATIS STREET FACADE.
 2. THE REMOVAL OF THE STOREFRONT IS RECESSING THE
 BUILDING FACADE BEYOND THE REQUIRED SETBACK LINE. ALONG
 THE CLEMATIS CONSERVATION DISTRICT THE BUILDING
 FRONTAGE SHALL BE LOCATED MATCHING THE ADJACENT
 BUILDING. IF THE DESIRE IS TO HAVE OUTDOOR SEATING, THE
 USE OF FOLDABLE DOORS WILL ACCOMPLISH THE GOAL BUT
 MAINTAN THE CONTINUOUS BUILDING FRONTAGE ALONG THE
 STREET.
 FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved