Plan Review Details - Permit 15080732
Plan Review Stops For Permit 15080732 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-09-18 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-09-18 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-18 |
Time |
11:00 |
Sent To |
I |
|
Notes |
2015-09-18 11:49:14 | ALL COMMENTS HAVE BEEN SATISFACTORILY ADDRESSED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-09-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-09-08 |
Time |
17:32 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-08 |
Time |
16:45 |
Sent To |
I |
|
Notes |
2015-09-08 17:42:58 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. INDICATE IF THE S/D INSIDE THE 1ST FLR. ELECTRIC | | ROOM NEW OR EXISTING? IT IS NOT MARKED AS EXISTING NOR | | INCLUDED ON THE RISER DIAGRAM. | | 2. INDICATE IF THE S/D INSIDE THE 1ST FLR. CORRIDOR, | | ADJACENT TO THE EVAC PANEL NEW OR EXISTING? IT IS NOT | | MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. | | 3. INDICATE IF THE D/D, RT & CM FOR RTU 4 ON THE ROOF | | ARE NEW OR EXISTING? THEY'RE NOT MARKED AS EXISTING NOR | | INCLUDED ON THE RISER DIAGRAM. | | 4. INDICATE IF THE D/D, RT & CM IN THE BALCONY ARE FOR | | RTU 3 AND IF THEY ARE NEW OR EXISTING? THEY'RE NOT | | MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. | | 5. IDENTIFY YOUR LINE WEIGHT/STYLE ON THE RISER DIAGRAM | | TO INDICATE THE NEW VS. THE EXISTING RUNS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-09-16 |
|
|
Cont ID |
|
Sent By |
GJT |
Date |
2015-09-16 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2015-09-16 |
Time |
|
Sent To |
E |
|
Notes |
2015-09-16 15:32:11 | PROVISO: ENSURE THAT THE SPACING, VISIBILITY, AND | | VOLUME OF ALL ACTIVATION AND NOTIFICATION APPLIANCES | | ARE COMPLIANT WITH NFPA 72. GJT |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2015-08-25 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2015-08-25 |
Time |
1600 |
Sent To |
E |
|
Notes |
2015-08-26 08:23:04 | PROVISO: ENSURE THAT THE SPACING, VISIBILITY, AND | | VOLUME OF ALL ACTIVATION AND NOTIFICATION APPLIANCES | | ARE COMPLIANT WITH NFPA 72. GJT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-09-18 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-09-18 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-14 |
Time |
13:52 |
Sent To |
|
|
Notes |
2015-09-18 11:52:38 | 9/18/15 -PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO SMALL READY BIN "K". MA | 2015-09-14 13:52:49 | RESUB ROUTED TO FIRE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-09-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-09-08 |
Time |
18:06 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-20 |
Time |
10:02 |
Sent To |
|
|
Notes |
2015-09-08 18:11:40 | 9/8/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "K". MA | 2015-08-20 10:02:43 | ROUTED TO FIRE |
|
|
|