Plan Review Details - Permit 15080680
Plan Review Stops For Permit 15080680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-03-23 Time 11:45 Rev Time 0.00
Received By   Date 2016-03-23 Time 09:00 Sent To  
Notes
2016-03-23 11:50:45SEE PROVISOS LISTED ON SHEET LS1.1.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By jwitmer Date 2015-10-07 Time 08:37 Rev Time  
Received By jwitmer Date 2015-10-07 Time 05:32 Sent To  
Notes
2015-10-07 08:36:05BUILDING PLAN REVIEW
 W. P. B. REVISION: 15080680
 W. P. B. PERMIT: 13060638
 ADD: 114 S. OLIVE AVE.
 CONT: DWYOR CONSTRUCTION & DEVELOPMENT
 TEL: (561)856-6655
 E-MAIL: ?????????????????????
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 07/2015
 ACTION: DENIED
  
 1) SHEET A1.1. THE FRONT ENTRY INDICATES THAT THERE IS
 NO A SLOPED PORTION OF THE FLOOR LESS THAN OR EQUAL TO
 1:20. THE PLANS DO NOT PROVIDE WHAT THE ELEVATION
 CHANGE FROM THE STREET TO THE FLAT FINISH FLOOR AND AT
 WHAT DISTANCE THIS SLOPED AREA OF THE FLOOR IS TO
 DETERMINE IF THIS IS A RAMP OR JUST A SLOPED SURFACE OF
 THE FLOOR. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED
 TO DETERMINE CODE COMPLIANCE WITH EITHER GRADE OR RAMP.
 2010 FBC-ACCESSIBLITY DEFITIONS 106 RAMP : RUNNING
 SLOPE STEEPER THAN 1:20.
  
 2) SHEET A1.1. NEW FIRE SPRINKLER ROOM 106 DOES NOT
 INDICATE WALL TAGS IDENTIFYING THE TYPE OF WALL
 CONSTRUCTION FOR THIS SPACE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED FOR CODE COMPLIANCE.
  
 3) SHEET A1.1 THE SECOND FLOOR PLAN WITH THE NEW FLOOR
 PLAN AND SEATING ARRANGEMENT AND COLUMN LAYOUT PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-B 1014.3 EXCEPTION #5.
 WHERE A TENANT SPACE IN A GROUP A OCCUPANCY HAS AN
 OCCUPANT LOAD OF MORETHAN 50, THE LENGTH OF A COMMON
 PATH OF TRAVEL SHALL NOT BE MORE THAN 20 FT. NOTE ALSO
 PROVIDE THE ACCESS AISLES SHOWING COMPLIANCE WITH
 1017.4.3 AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM
 ANY SEAT TO THE POINT WHERE A PERSON HAS 2 OR MORE
 PATHS OF EGRESS TRAVEL TO SEPARATE EXITS.
  
 4) SHEET A1.1 THE 3RD FLOOR PLAN THE NORTH EAST CORNER
 OF THE SEATING AREA SHOW COMPLIANCE WITH 1017.4.3
 AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM ANY SEAT
 TO THE POINT WHERE A PERSON HAS 2 OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS.
  
 5) SHEET A1.2. ROOM 209 THE ELEVAOR EQUIPMENT ROOM DOES
 NOT HAVE WALL TAGS IDENTIFYING THE TYPE OF WALL
 CONSTRUCTION IN ACCORDANCE WITH 2010 FBC-B 3006.4
 MACHINE ROOMS 1 HOUR FIRE BARRIER.
  
 6) SHEET A1.2 ROOM # 208 THE UNISEX RESTROOM DOOR #
 208.01 THE WAY THIS DOOR SWINGS REQUIRES 42 INCHES OF
 WALL ON THE LATCH SIDE OF THE DOOR. PLEASE REVIEW 2010
 ACCESSIBILITY CODE FIGURE 404.2.4.1 (E).
  
 7) SHEET A1.3, DOOR 304.01 DOES NOT HAVE THE REQUIRED
 18 INCHES CLEAR WIDTH ON THE LATCH SIDE OF THE DOOR.
 2010 FBC-ACCESSIBLITY CODE. 404.2.4 MAEUVERING
 CLEARENCES, AND FIGURE 404.2.4.1( A) .
  
 8) SHEET A1.1 THE 3RD FLOOR. THE STANDING ROOM ONLY
 NEXT TO THE PROPERTY LINE WALL. SHEET A5.2 NOTE CON A.
 CONCRETE BLOCK RAILING TO 48 INCHES AFF. PLEASE NOTE
 THIS IS A REVISION FROM WHAT IS SHOWN ON A7.1.1
 SECTIONS 02 & 03. THE DETAILS 02 & 03 SHOW A BLOCK WALL
 2 FOOT 3 INCHES ABOVE THE 3RD FLOOR WITH A GLASS
 RAILING TO THE HEIGTH OF 3 FOOT 8 INCHES. PLEASE UPDATE
 SHEET A7.1.1.
  
 NOTE THE 3 FOOT 8 INCHES BLOCK WALL/ GUARDRAIL IS MORE
 RESTRICTIVE THAN THE REQUIRED 42 INCHES, SHEET A1.1 THE
 3RD FLOOR PLAN SHOWS THE SOFA SEATING 4 FOOT 6 INCHES
 AWAY FROM THE BLOCK WALL/ GUARD RAIL, THERE IS NO
 ADJACENT FIXED SEATING FBC-B 1013.2) TO BE COMPLIED
 WITH!!!!!!!
  
 9A) SHEET A5.1 THE SOUTH ELEVATION DOES NOT SHOW
 WINDOWS ON THE 3RD OR 4 THE FLOORS IN THE ADJACENT
 BUILDING, JUST A BLANK WALL. INSPECTORS ON THE JOBSITE
 HAVE VERIFIED THERE ARE WINDOWS IN THESE WALLS. PLEASE
 SHOW HOW COMPLIANCE WITH STEPPED BUILDING 2010 FBC-B
 706.6.1. WHERE A FIRE WALL SERVES AS AN EXTERIOR WALL
 FOR A BUILDING AND SEPARATES BUILDINGS HAVING DIFFERENT
 ROOF LEVELS, SUCH WALL SHALL TERMINATE AT A POINT NOT
 LESS THAN 30 INCHES (762 MM) ABOVE THE LOWER ROOF
 LEVEL, PROVIDED THE EXTERIOR WALL FOR A HEIGHT OF 15
 FEET (4572 MM) ABOVE THE LOWER ROOF IS NOT LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION FROM BOTH
 SIDES WITH OPENINGS PROTECTED BY FIRE ASSEMBLIES HAVING
 A FIRE PROTECTION RATING OF NOT LESS THAN 3/4 HOUR.
 EXCEPTION: WHERE THE FIRE WALL TERMINATES AT THE
 UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE
 LOWER ROOF, PROVIDED: 1. THE LOWER ROOF ASSEMBLY WITHIN
 10 FEET (3048 MM) OF THE WALL HAS NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING AND THE ENTIRE LENGTH AND
 SPAN OF SUPPORTING ELEMENTS FOR THE RATED ROOF ASSEMBLY
 HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 2. OPENINGS IN THE LOWER ROOF SHALL NOT BE LOCATED
 WITHIN 10 FEET (3048 MM) OF THE FIRE WALL.
  
 9B) 2010 FBC-B 706.8 OPENINGS. EACH OPENING THROUGH A
 FIRE WALL SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 716.5 AND SHALL NOT EXCEED 156 SQUARE FEET (15 M2). THE
 AGGREGATE WIDTH OF OPENINGS AT ANY FLOOR LEVEL SHALL
 NOT EXCEED 25 PERCENT OF THE LENGTH OF THE WALL.
 EXCEPTIONS:
 1. OPENINGS ARE NOT PERMITTED IN PARTY WALLS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 706.1.1.
 2. OPENINGS SHALL NOT BE LIMITED TO 156 SQUARE FEET (15
 M2) WHERE BOTH BUILDINGS ARE EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1.1.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 15:46 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 12:28 Sent To  
Notes
2016-04-05 15:47:59ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 12:01 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 09:27 Sent To I
Notes
2015-11-04 12:02:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT
 W/SEPARATE SUBMITTAL DOCUMENTS.
 2. NEC 210.8(B): ALL 15 -20 AMP 125 VOLT OUTLETS IN
 KITCHEN AND PREP AREAS SHALL BE ON GFI CIRCUIT. THIS
 APPLIES TO ALL LEVELS THROUGHOUT THE PREMISES.
 3. NEC 210.62: THERE SHALL BE A SHOW WINDOW OUTLET FOR
 EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF.
 4. ALL LIGHTING SHALL COMPLY WITH THE MANDATORY
 REQUIREMENTS OF 2010 FBC-ENERGY CONSERVATION SECTION
 505.
 5. YOU SHALL PROVIDE A FIXTURE SCHEDULE IDENTIFYING
 FIXTURE. INDICATE WHICH OF THOSE HAS A BACKUP BATTERY
 FOR EMERGENCY OPERATIONS OF EGRESS LIGHTING.
 6. YOU SHALL SUBMIT A 3RD FLOOR LIGHTING PLAN.
 7. EXIT LIGHTS SHALL BE AS INDICATED IN 2010 FBC
 SECTION 1006.3.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 09:20 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-10-09 Cont ID  
Sent By wjolin Date 2015-10-09 Time 14:24 Rev Time 0.00
Received By wjolin Date 2015-10-09 Time 11:21 Sent To  
Notes
2015-10-09 13:54:25114 SOUTH OLIVE AVENUE
 TRACKING #15080680
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.3: OCCUPANTS SHALL NOT BE REQUIRED TO EGRESS
 THROUGH A STORAGE OCCUPANCY (DRY STORAGE #308).
  
 SHEET P2.3: THERE APPEARS TO BE STORM DRAIN PIPING
 ROUTED THROUGH STAIR #1.
  
 NO SHEET E2.3 SUBMITTED SHOWING THE ELECTRICAL CHANGES
 TO THE THIRD FLOOR.
  
 A SITE VISIT TO THE THIRD FLOOR OF THE REVEALED THAT
 THERE IS AN EXISTING BUILDING WITH WINDOW EXPOSURES
 ABUTTING THE ROOFTOP SEATING AND STAIR #1. HOW WILL
 THIS BE PROTECTED FROM FIRE?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-04-18 Cont ID  
Sent By destabro Date 2016-04-18 Time 11:30 Rev Time 0.00
Received By destabro Date 2016-04-18 Time 11:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 11:38 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 11:38 Sent To  
Notes
2015-08-24 10:51:118/24/15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-25 Cont ID  
Sent By tklarge Date 2016-04-25 Time 11:28 Rev Time 0.00
Received By tklarge Date 2016-03-09 Time 11:12 Sent To  
Notes
2016-03-15 11:12:34C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 12:02 Rev Time 0.00
Received By albarran Date 2015-08-19 Time 13:20 Sent To  
Notes
2015-11-04 12:05:4011/4/15 FAILED ALL TRADE REVIEWS. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "D". MA
2015-08-19 13:20:30C24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-23 Cont ID  
Sent By ccole Date 2016-03-23 Time 12:56 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 07:31 Sent To  
Notes
2016-03-23 13:48:14MECHANICAL PROVISO:
 MASTER PERMIT #13060638
 REVISION #15080680
 3/23/16
  
 1) AN EXHAUST SYSTEM IS REQUIRED FOR THE 3RD FLOOR
 LOCKER ROOM. REVISE THE PLANS ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-04 Cont ID  
Sent By ccole Date 2015-09-04 Time 09:30 Rev Time 0.00
Received By ccole Date 2015-09-04 Time 09:30 Sent To  
Notes
2015-09-04 09:36:231ST REVIEW: FBC 2014 MECHANICAL
 REVISION TRACKING #15080680
 MASTER #13060638
  
 1) THE SUBMITTED REVISION NARRATIVE FROM ROBERT IBARRA
 ARCHITECT DOES NOT LIST AND CLARIFY MANY OF THE
 MECHANICAL CHANGES THAT ARE SHOWN ON THE REVISED PLANS.
 PLEASE INCLUDE THE FOLLOWING PLAN REVISIONS IN THE
 NARRATIVE AND CLARIFY WHY THE CHANGES WERE MADE.
 SHEET M0.1- A) A NEW SUPPLY REGISTER HAS BEEN ADDED
 (AD-6) TO THE AIR DISTRIBUTION SCHEDULE. B) AHU-4 HAS A
 REVISION CLOUD AROUND IT IN THE SCHEDULE, BUT IT IS THE
 SAME UNIT THAT WAS SHOWN IN THE MASTER PLANS. C) THE
 F-2 HAS BEEN CHANGED TO A LARGER SIZE CAPACITY AND
 MODEL.
 M1.1 & M1.2: THE AD-2 SUPPLY DIFFUSERS HAVE BEEN
 CHANGED TO A DIFFERENT MODEL AND TYPE- THE AIR
 DISTRUBUTION SCHEDULE ON M0.1 DOES NOT SHOW THIS
 CHANGE.
 M1.2: THE PREP 2 ROOM HAS BEEN REDUCED IN WIDTH-
 CLARIFY WHY THE ROOM SIZE WAS CHANGED, WHAT EQUIPMENT
 WAS REMOVED OR RELOCATED, AND WHAT AIR DISTRIBUTION
 (DUCTWORK) ALTERATIONS HAVE BEEN MADE.
 M1.3: THE RESTROOMS HAVE ENLARGED IN SIZE AND AN
 ELECTRICAL ROOM HAS BEEN EITHER REMOVED OR BEEN
 RELOCATED- ALONG WITH OTHER FLOOR PLAN CHANGES.
 ADDITIONALLY THE RTU-1 HAS BEEN RELOCATED AND
 ALTERATIONS TO THE AIR DISTRIBUTION SYSTEM HAVE BEEN
 MADE.
 M1.4: A NEW EQUIPMENT PLATFORM FOR SUPPORT OF THE AC
 CONDENSERS IS SHOWN ON THE PLAN WITH A NOTE REFERENCING
 THE ARCHITECTURAL DRAWINGS. REVIEW OF THE
 ARCHITECTRURAL DRAWINGS INDICATES THAT FURTHER DETAILS
 ARE REQUIRED. PLEASE PROVIDE: A) SHOP DRAWINGS WITH
 REVIEW AND APPROVAL STAMPS BY THE ENGINEER OF RECORD.
 B) REVISED STRUCTURAL DRAWINGS INCLUDING DESIGN
 CRITERIA AND CALCULATIONS, ASSEMBLY AND ATTACHMENT
 DETAILS, TIE DOWN ENGINEERING FOR MOUNTING THE
 CONDENSERS TO THE PLATFORM, A PERMANENT MEANS OF ACCESS
 FOR SERVICE OF THE EQUIPMENT, AND DRAWINGS AND DETAILS
 FOR GUARDS (REFER TO SECTION 304.11 FBC-10 MECHANICAL).
 M1.5: INDICATE THE TYPE AND THICKNESS OF REFRIGERANT
 PIPING INSULATION AND HOW THE INSULATION AND PIPING
 WILL BE PROTECTED FROM WEATHERING AND UV DEGRADATION.
 2) PLEASE NOTE THAT REVISIONS TO THE KITCHEN HOOD
 SYSTEMS, AND THE WALK-IN COOLER AND FREEZER BOXES ARE
 TO BE SUBMITTED UNDER A SEPARATE PERMIT AS REQUIRED BY
 THE CITY OF WPB BUILDING DEPARTMENT. REVIEWS ON THOSE
 PLAN REVISIONS ARE ON HOLD UNTIL THOSE APPLICATIONS AND
 PLAN REVISIONS HAVE BEEN RECEIVED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-04-25 Cont ID  
Sent By tklarge Date 2016-04-25 Time 11:28 Rev Time 0.00
Received By tklarge Date 2016-04-25 Time 11:26 Sent To  
Notes
2016-04-25 11:28:16SIGNED AND SEALED LETTER FROM ENGINEER OF RECORD ON
 FILE ADDRESSING PLUMBING COMMENTS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 05:22 Rev Time 0.00
Received By tklarge Date 2016-03-27 Time 04:10 Sent To  
Notes
2016-03-27 05:02:151) THE RESPONSE TO PLUMBING PLAN REVIEW COMMENT #5 FROM
 THE 8/31/15 REVIEW IS VAGUE. THE RESPONSE FROM EMERALD
 ENGINEERING REGARDING THE DISPOSAL OF THE GREASE WASTE
 FROM THE GRILL & GRIDDLE ON THE 3RD FLOOR LACKS
 SPECIFICS. EXPLAIN HOW THIS WASTE WILL BE ENTERED INTO
 THE GREASE INTERCEPTOR.WHAT PROCEDURES WILL BE IN PLACE
 TO ENSURE THIS WASTE IS DISCHARGED INTO THE GREASE
 INTERCEPTOR AND HOW?
 2) CLARIFY THE GREASE INTERCEPTOR SIZING ON SHT.P2.1 -
 THE PLANS NOTE "3 COMP.SINK POT SINK EACH COMPT. 20 X16
 X12 " AND THEN IT ALSO STATES THAT EACH COMPARTMENT IS
 20 X 16 X 9. WHICH IS IT? FBC 107.1.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By gjohnson Date 2015-08-31 Time 11:31 Rev Time 0.00
Received By gjohnson Date 2015-08-31 Time 16:15 Sent To  
Notes
2015-09-02 16:27:151ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
  
 PLUMBING COMMENTS:
  
 1. ON SHEET P2.1 YOU HAVE 1ST FLOOR BAR FLOOR SINKS
 TIED INTO THE GREASE WASTE. IS THERE GREASE LADEN WASTE
 BEING DUMPED INTO THESE DRAINS. IF NOT IT CANNOT BE
 TIED INTO GREASE WASTE SYSTEM.
 PER. FBCP 2010 SEC. 1003.2
 2. ON SHEET P2.1 YOU SHOW 2 GREASE INTERCEPTORS YOU
 LIST SCHIER GB 75 WITH A 750 GPM ACCORDING TO THE SPECS
 FROM SCHIER A GB75 HAS 75 GPM PLEASE CLARIFY.
 WPB AMEND. 107.2.1
 3. SHEET P2.1 YOUR CALCULATIONS FOR THE GREASE
 INTERCEPTOR ONLY APPEAR TO HAVE KITCHEN FIXTURES. ALL
 FIXTURES INCLUDING FLOOR DRAINS THAT ARE CONNECTED TO
 GREASE WASTE MUST BE INCLUDED IN CALCULATIONS. WPB
 AMEND. 107.2.1
 4. IF THE FIRST FLOOR BAR FLOOR SINKS ARE RECEIVING
 GREASE LADEN WASTE. ARE THE SECOND AND THIRD FLOOR BARS
 ALSO RECEIVING GREASE LADEN WASTE. WPB AMEND. 107.2.1
 5. ON THE THIRD FLOOR YOUR SHOWING A GRILL AND GRIDDLE,
 WILL THE GREASE FROM CLEANING THE APPLIANCE BE BROUGHT
 DOWN TO THE FIRST FLOOR AND DUMPED INTO THE GREASE
 SYSTEM PLEASE CLARIFY.
 WPB AMEND. 107.2.1
 5. SEPARATE GAS PERMIT REQUIERED. FOR COMPLETE GAS
 REVIEW THE FOLLOWING ITEMS ARE REQUIRED. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL CUT SECTIONS
 OF PIPE AND CORRESPONDING LENGTHS PER FBC-2014 FUEL
 GAS, SECS. 402.4.1, 402.4.2.
  
 SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL PIPE
 SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 TYPE OF GAS, (LP OR NATURAL).
  
 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER),
 TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM
 PER THE FBC-2014 FUEL GAS APPENDIX A ? USE OF CAPACITY
 SECTION A.3.1(4) & 2014 FUEL GAS CODE SEC. 402.4.1.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304.
  
 INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 FUEL
 GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS
  