Plan Review Details - Permit 15080661
Plan Review Stops For Permit 15080661
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-12-15 Cont ID  
Sent By shill Date 2015-12-15 Time 09:39 Rev Time 0.00
Received By shill Date 2015-12-15 Time 09:39 Sent To  
Notes
2015-12-15 09:44:03****PROVISO****
 ****REVISION MAY BE REQUIRED SUBJECT TO INSPECTOR'S
 DISCRETION****
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. UPON BUILDING INSPECTION, THE DCA/DBPR INSIGNIA WILL
 BE REMOVED AND RETURNED TO DBPR
  
 2. A DOOR IS TO BE REMOVED AND WALL INFILL INSTALLED.
 PROVIDE A STRUCTURAL DETAIL WHICH INCLUDES WIND DESIGN
 CRITERIA (FBC 1603.1.4) AT INSPECTION.
  
 3. THE PLANS FOR STAIRS, RAMP, LANDING, RAILING ARE
 DEFICIENT. IT REFERS TO THE WRONG CODE, AN OLD VERSION
 OF ASCE7, AND IS LACKING THE DIMENSIONS WHICH SHOULD
 SHOW COMPLIANCE. REVISE PLANS TO SHOW COMPLIANCE WITH
 ALL REQUIREMENTS OF FBC 5TH EDITION ACCESSIBILITY
 (DIMENSIONS). DETAILS NOT NEEDED FOR THIS JOB CAN BE
 CROSSED OUT AND DO NOT NEED TO DEMONSTRATE COMPLIANCE.
  
 4. SEPARATE PERMIT FOR SHUTTERS REQUIRED WITH A
 SEPARATE APPLICATION, PLANS AND FEES. A PRODUCT
 APPROVAL AND THE FOLLOWING FORM ARE TO BE SUBMITTED:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-30 Cont ID  
Sent By shill Date 2015-10-30 Time 17:13 Rev Time 0.00
Received By shill Date 2015-10-27 Time 15:17 Sent To  
Notes
2015-10-28 09:33:06****CORRECTIONS****
  
 A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH
 MODIFICATIONS - PERMIT WILL BE ISSUED WITH PROVISO
 THAT, UPON BUILDING INSPECTION, THE DCA/DBPR INSIGNIA
 WILL BE REMOVED AND RETURNED TO DBPR.
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1 OK
 2 OK
  
 3. A DOOR IS TO BE REMOVED AND WALL INFILL INSTALLED.
 PROVIDE A STRUCTURAL DETAIL AND INCLUDE WIND DESIGN
 CRITERIA FBC 1603.1.4.
  
 4. OK
  
 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED
 ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2
 SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3.
 2ND REVIEW, DISTANCE TO TOP OF LID (NOT SEAT) IS SHOWN
 AS BOTH 1FT4IN AND 1FT5IN WHICH WOULD BE 16 AND 17
 INCHES, SO SEAT WOULD BE LOWER, BUT SEAT IS REQUIRED TO
 BE BETWEEN 17 AND 19 INCHES. THIS CAN BE A REDLINED
 ITEM UPON REQUEST.
  
 5. THE PLANS FOR STAIRS, RAMP, LANDING, RAILING ARE
 DEFICIENT. IT REFERS TO THE WRONG CODE, AN OLD VERSION
 OF ASCE7, AND IS LACKING THE DIMENSIONS WHICH SHOULD
 SHOW COMPLIANCE. REVISE PLANS TO SHOW COMPLIANCE WITH
 ALL REQUIREMENTS OF FBC 5TH EDITION ACCESSIBILITY
 (DIMENSIONS). DETAILS NOT NEEDED FOR THIS JOB CAN BE
 CROSSED OUT AND DO NOT NEED TO DEMONSTRATE COMPLIANCE.
  
 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE
 TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND
 SHOW COMPLIANCE WITH FBC TABLES 602, 705.8.
  
 2ND REVIEW, PAGE WAS REVISED TO SHOW A DISTANCE OF 28.8
 BUT THE ASSUMED PROPERTY LINE, DISTANCE FROM EACH
 BUILDING TO THE ASSUMED PROPERTY LINE, COMPLIANCE WITH
 TABLES 602, 705.8 NOT SHOWN. PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS.
  
 7. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED,
 OR PROVIDE REMOVAL AGREEMENT REQUESTED BY WILLIE SWOPE,
 561 233 5025.
  
 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED
 ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE
 THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED. A
 PRODUCT APPROVAL WAS PROVIDED BUT THE FORM WAS NOT
 INCLUDED.
  
 9. SHEET A4 IS NOT A PART OF THE MODULAR STATE
 APPROVAL. REVISE TO UPDATE TO CURRENT CODE, REVISE
 PLANS TO COMPLY WITH CURRENT CODE, AND ALSO SEE FBC
 1809.4 REGARDING FOOTING DEPTH.
  
  
 WHEN RESUBMITTING, PLEASE REMOVE THE OLD SHEETS FROM
 THE COLLATED PERMIT DOCUMENTS BUT RETAIN IN THE
 SUBMITTAL FOR REFERENCE. PLEASE RETAIN THE VOIDED
 REFERENCE ONLY 2010 MODULAR PLANS. PLEASE SEE ME OR
 STEVE KENNEDY IF YOU NEED ASSISTANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-18 Cont ID  
Sent By shill Date 2015-09-18 Time 12:59 Rev Time 0.00
Received By shill Date 2015-09-18 Time 12:54 Sent To  
Notes
2015-09-18 13:34:34****CORRECTIONS****
 COURTESY REVIEW - SCOPE CLARIFIED
 A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH
 MODIFICATIONS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED
 GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE
 FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE
 PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC
 107.
  
 2. FS 553.80, PROVIDE THE STATE APPROVED PLANS AND
 STATE APPROVAL COVER SHEET WHICH SHOWS THE APPROVAL
 NUMBER. THIS SHOULD BE ON THE INSIGNIA.
  
 ADVISORY ONLY, PLANS PREPARED BY REBECCA M. GATES WERE
 NOT YET REVIEWED BY FIRE (FIRE HAD PLANS CHECKED OUT
 WHEN THESE SHEETS WERE SUBMITTED) BUT WILL BE REVIEWED
 WHEN PLANS ARE RESUBMITTED.
  
 PERMIT WILL BE ISSUED WITH PROVISO THAT, UPON BUILDING
 INSPECTION, THE DCA/DBPR INSIGNIA WILL BE REMOVED AND
 RETURNED TO DBPR.
  
 REVISE PLANS PREPARED BY REBECCA M. GATES TO INCLUDE
 GOVERNING CODE.
  
 IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS
 THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS
 PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A
 STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF
 RECORD REQUIRED.
  
 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II
 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE
 SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN
 EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A
 NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH
 THE WIND SPEED OF THE NEW LOCATION.
  
 THE MANUFACTURED BUILDING PLANS AS SUBMITTED DO NOT
 COMPLY WITH THE WIND SPEED REQUIREMENT FOR THE
 LOCATION. PLEASE ADDRESS, EITHER BY PROVIDING A NEW
 MANUFACTURED BUILDING WHICH COMPLIES WITH 167MPH WIND
 SPEED, OR BY PROVIDING ENGINEERING TO INCREASE THE
 LIMITATION FOR THE BUILDING PROPOSED FROM 165MPH TO
 167MPH.
  
 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL
 SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5.
  
 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED
 ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2
 SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3.
  
 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED,
 FBC CHAPTER 10, FBC ACCESSIBILITY.
  
 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE
 TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND
 SHOW COMPLIANCE WITH FBC TABLES 602, 705.8.
  
 7. FOR IMPACT FEES, EITHER:
  
 A. PROVIDE THE REMOVAL AGREEMENT WHEREIN OWNER AGREES
 THAT THE PROPOSED TEMPORARY SALES TRAILER WILL BE
 REMOVED BY A CERTAIN DATE (PER WILLIE SWOPE), OR
  
 B. AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. 561-233-5025 FOR MORE INFORMATION; PROVIDE
 THE STAMPED PLAN AND RECEIPT SHOWING FEES WERE PAID, IF
 APPLICABLE.
  
 IF CONTRACTOR DOES NOT UNDERSTAND ITEM A, TAKE PLANS TO
 PALM BEACH COUNTY FOR IMPACT FEE ASSESSMENT.
  
 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED
 ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE
 THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED.
  
 9. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE
 MARKED "VOID" AND LEFT IN THE PERMIT APPLICATION
 PACKAGE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By shill Date 2015-09-14 Time 12:49 Rev Time 0.00
Received By shill Date 2015-09-11 Time 12:58 Sent To  
Notes
2015-09-12 14:26:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED
 GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE
 FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE
 PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC
 107.
  
 2. SCOPE NOT CLEAR, FBC 107.
  
 COMPLETE PLANS WERE SUBMITTED FOR A "MODULAR
 STRUCTURE." PLEASE SEE FS 553.80, MODULAR STRUCTURES
 REQUIRE PLAN REVIEW AND APPROVAL BY THE STATE. IF THE
 MODULAR INSTALLATION IS PROPOSED, PROVIDE THE STATE
 APPROVED PLANS AND STATE APPROVAL COVER SHEET WHICH
 SHOWS THE APPROVAL NUMBER. THIS SHOULD BE ON THE
 INSIGNIA.
  
 SOMEONE ADDED PAGES AT SOME POINT IN THE REVIEW
 PROCESS. IF THESE PAGES WERE SUBMITTED AFTER OTHER
 REVIEWS WERE COMPLETE, RE-REVIEW BY THOSE TRADES IS
 REQUIRED. NO RESUBMITTAL FORM WAS PROVIDED.
  
 IF THE PLANS PREPARED BY REBECCA M. GATES ARE PROPOSED
 RATHER THAN THE PLAN WHICH APPEARS TO BE A DCA APPROVED
 MODULAR, PLEASE NOTE THE FOLLOWING PER STATE OF
 FLORIDA:
  
 CAN AN EXISTING MODULAR BUILDING BE MODIFIED OR
 RENOVATED?
  
 YES. ONSITE MODIFICATIONS TO EXISTING MODULAR BUILDINGS
 MUST BE PERMITTED AND INSPECTED BY THE JURISDICTION
 HAVING AUTHORITY (LOCAL BUILDING DEPARTMENT). ORIGINAL
 PLANS (OR ?AS-BUILT? PLANS) AND ANY MODIFICATIONS MUST
 BE PROVIDED TO THE LOCAL BUILDING DEPARTMENT. WHEN
 INSPECTED BY THE LOCAL BUILDING DEPARTMENT, THE
 DCA/DBPR INSIGNIA SHALL BE REMOVED AND RETURNED TO
 DBPR, AND A CERTIFICATE OF OCCUPANCY BE ISSUED IN LIEU
 OF THE DCA/DBPR INSIGNIA. RECERTIFICATION BY THE LOCAL
 JURISDICTION IS ONLY APPLICABLE FOR THAT JURISDICTION
 (NOT STATEWIDE).
  
 PLANS PREPARED BY REBECCA M. GATES SHOULD INCLUDE
 GOVERNING CODE. THE MODULAR PLANS ARE REQUIRED TO BE
 UPDATED TO CURRENT CODE.
  
 IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS
 THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS
 PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A
 STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF
 RECORD REQUIRED.
  
 A COMPLETE CHECKLIST CANNOT BE PROVIDED AS INTENT IS
 NOT ENTIRELY CLEAR.
  
 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II
 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE
 SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN
 EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A
 NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH
 THE WIND SPEED OF THE NEW LOCATION.
  
 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL
 SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5.
  
 5. FOR THE NEW FLOOR PLAN, PROVIDE DETAILS WHICH SHOW
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC 5TH EDITION
 ACCESSILIBITY.
  
 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED,
 FBC CHAPTER 10, FBC ACCESSIBILITY.
  
 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE
 TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND
 SHOW COMPLIANCE WITH FBC TABLES 602, 705.8.
  
 7. FOR IMPACT FEE PURPOSES, PROVIDE THE REMOVAL
 AGREEMENT WHEREIN OWNER AGREES THAT THE PROPOSED
 TEMPORARY SALES TRAILER WILL BE REMOVED BY A CERTAIN
 DATE (PER WILLIE SWOPE). IF THIS DOCUMENT CANNOT BE
 PROVIDED, AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 IS REQUIRED. 561-233-5025 FOR MORE INFORMATION.
  
 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED
 ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE
 THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 16:53 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 16:26 Sent To  
Notes
2016-04-05 17:47:42ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. THE RISER DIAGRAM SHOWS THE SERVICE AS 277/480 3
 PHASE GOING INTO A STEP DOWN TRANSFORMER TO 120/208 BUT
 THE SERVICE REQUIREMENT AS PER THE PANEL SCHEDULE IS
 120/240 3 PHASE GOING INTO A 3 PHASE DISC. OF WHICH TWO
 PHASES ARE BEING USED.
 2. THE PANEL SCHEDULE ON THE PRIMARY PERMIT HAS A
 DEMAND LOAD OF 54.8 AMP AND THE PANEL SCHEDULE ON THE
 NEW PLANS HAVE A CONNECTED DEMAND LOAD OF 73.6 AMP.
 SUBMIT SPECS
 3. THE RISER DOES NOT INDICATE THE CONDUCTOR INSULATION
 RATING THEREFORE ASSUMING IT IS 60 DEGREE, THE MAXIMUM
 DISTANCE BETWEEN THE MAIN DISC AND THE TRAILERS DISC IS
 ONLY 136'.
 4. PHYSICAL PROTECTION AS REQUIRED IN NEC 110.27(B)
 SHALL BE PROVIDED AND INDICATED ON PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-16 Cont ID  
Sent By albarran Date 2015-12-16 Time 14:46 Rev Time 0.00
Received By albarran Date 2015-12-16 Time 13:36 Sent To Z
Notes
2015-12-16 14:48:12CONDITIONAL APPROVAL OF THIS PERMIT IS ISSUED SUBJECT
 TO FIELD INSPECTOR APPROVAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 17:47 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 17:47 Sent To I
Notes
2015-10-05 18:11:03AFTER A TELEPHONE CALL FROM RYAN TEMPONE I WENT BACK TO
 TAKE A SECOND LOOK AT THE DISARRAY SUBMITTED AND FOUND
 THE TWO OTHER SHEETS WHICH ADDRESSED THE DEFICIENCIES I
 HAD NOTED PREVIOUSLY. I TOOK ALL THE ELECTRICAL PAGES
 AND STAPLED THEM TOGETHER. I WAS ALSO INFORMED BY MR.
 TEMPONE OF THEIR INTENT TO REARRANGE THE INTERIOR
 LAYOUT OF THE TRAILERS, TO WHICH I TOLD HIM TO REVISE
 THE SCOPE OF THE PERMIT APPLICATION TO REFLECT THAT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 14:46 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 13:54 Sent To I
Notes
2015-10-05 14:55:14THIS SET OF DRAWINGS WAS SO SLOPPY THAT I ACCIDENTLY
 STAMPED THE PLANS AS PASSED. PLEASE NOTE THAT .I
 COMPARED THE PANEL SCHEDULES SUBMITTED I NOTICED A
 MISMATCH. CORRECT THE SUBMITTAL SO THAT THE LOAD CALCS
 AND THE PANEL SCHEDULES MATCH ON BOTH SET OF DRAWINGS.
 FURTHERMORE, PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE SOURCE OF POWER AND MAIN DISCONNECT.
 WHEN YOU RESUBMIT, PLEASE STAPLE ALL THE SHEETS OF EACH
 SET AND ATTACH THEM TO THE MANUFACTURERS DRAWINGS FOR
 COMPARISON.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-05 Cont ID  
Sent By pleduc Date 2015-11-05 Time   Rev Time 0.00
Received By pleduc Date 2015-11-05 Time 08:24 Sent To Z
Notes
2015-11-05 09:22:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 CONSIDER THE PREVIOUS COMMENTS AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-26 Cont ID  
Sent By pleduc Date 2015-08-26 Time   Rev Time 0.00
Received By pleduc Date 2015-08-26 Time 0900 Sent To  
Notes
2015-11-05 09:21:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 CONSIDER THE PREVIOUS COMMENTS AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
2015-08-26 09:18:108/26/2015 PASSED WITH PROVISO:
  
 1. PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 2. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 3. PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL
 BE PROVIDED WITH CLEARANCES OF 7?-6? TO THE FRONT AND
 SIDES AND 4? TO THE BACKSIDE.
  
 4. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 STAIRS FOR TRAILERS
  
 5. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED
 AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 STAIRS SHALL HAVE LANDINGS AT DOOR OPENINGS.
  
 STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE LIFE
 SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 FLORIDA
 2012 EDITION.
  
 6. PROVIDE ILLUMINATED EXIT SIGNS FOR ALL EXIT DOORS.
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
 GJT
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-08 Cont ID  
Sent By cpuell Date 2016-01-08 Time 08:17 Rev Time 0.00
Received By cpuell Date 2016-01-05 Time 16:00 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-17 Cont ID  
Sent By eschneid Date 2015-12-17 Time 09:59 Rev Time 0.00
Received By eschneid Date 2015-12-03 Time 13:12 Sent To  
Notes
2015-12-03 13:12:22B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By eschneid Date 2015-11-24 Time 13:44 Rev Time 0.00
Received By eschneid Date 2015-10-15 Time 07:42 Sent To  
Notes
2015-10-15 16:25:27B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 14:55 Rev Time 0.00
Received By albarran Date 2015-08-18 Time 09:19 Sent To  
Notes
2015-10-05 14:58:2910/5/15 FAILED REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL.
 SENT TO LARGE DENIED BIN "W". MA
2015-08-19 09:19:29B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2016-01-08 Cont ID  
Sent By shill Date 2016-01-08 Time 12:11 Rev Time 0.00
Received By shill Date 2016-01-08 Time 12:11 Sent To  
Notes
2016-01-08 12:11:42TEMPORARY SALES TRAILER - IMPACT FEES NOT REQUIRED PER
 WILLIE SWOPE; SEE EMAIL
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-12-15 Cont ID  
Sent By shill Date 2015-12-15 Time 11:15 Rev Time 0.00
Received By shill Date 2015-12-15 Time 11:15 Sent To  
Notes
2015-12-15 11:15:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 561-233-5025
  
 WHEN RESUBMITTING, PLEASE COLLATE TWO IDENTICAL SETS OF
 PLANS WITH ALL VOIDED SHEETS REMOVED. THE VOIDED SHEETS
 SHOULD BE RETAINED IN THE PACKAGE BUT BOUND SEPARATELY
 FROM THE PLANS FOR ISSUANCE.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-30 Cont ID  
Sent By shill Date 2015-10-30 Time 17:17 Rev Time 0.00
Received By shill Date 2015-10-27 Time 16:15 Sent To  
Notes
2015-10-30 17:18:08IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 561-233-5025
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-09-12 Cont ID  
Sent By shill Date 2015-09-12 Time 16:21 Rev Time 0.00
Received By shill Date 2015-09-12 Time 16:21 Sent To  
Notes
2015-09-12 16:22:10SEE BUILDING COMMENTS
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-05 Cont ID  
Sent By ccole Date 2015-11-03 Time 12:09 Rev Time 0.00
Received By ccole Date 2015-11-03 Time 12:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By ccole Date 2015-09-03 Time 15:50 Rev Time 0.00
Received By ccole Date 2015-09-03 Time 15:50 Sent To  
Notes
2015-09-14 08:30:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080661
 9/14/15
  
 1) PLEASE SUBMIT REVISED HVAC PLANS, DETAILS, AND
 SPECIFICATIONS TO MATCH THE NEW SALES OFFICE PLANS BY
 ARCHITECT GATES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-26 Cont ID  
Sent By gjohnson Date 2015-10-26 Time 15:23 Rev Time 0.00
Received By gjohnson Date 2015-10-26 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-03 Cont ID  
Sent By tklarge Date 2015-09-03 Time 07:27 Rev Time 0.00
Received By tklarge Date 2015-09-03 Time 06:23 Sent To  
Notes
2015-09-03 06:06:161) PLEASE BIND ALL THE PLANS INTO TWO COMPLETE SETS FOR
 REVIEW.
 2) SHT. SK-2 THE STAFF ROOM SINK SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.212.1, 606.
 3) SHT. SK-5 - SHOW THE HEIGHT OF THE WATER CLOSET TO
 THE TOP OF THE SEAT. COMPLY WITH 2014 FBC-ACCESSIBILITY
 SEC. 604.4.
 4) SHT. SK-5 - SHOW THE DIMENSIONSTO THE BOTTOM & TOP
 OF THE LAVATORY FROM THE FINISH FLOOR. COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.606.2,606.3.
 5) SHOW THE DIMENSIONS OF THE TOILET ROOM ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT.P0.1 - A BACKFLOW PREVENTION DEVICE SHALL BE
 INSTALLED ON THE WATER SERVICE PER FBC-P SEC.608.1
 7) THE FLOOR PLAN ON THE SK DRAWINGS DOES NOT CORRELATE
 WITH THE FLOOR PLAN OF THE MODULAR BUILDING.CLARIFY.
 8) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FFOR THE
 EEMAX WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 COOLER.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHOW THE LOCATION OF THE WATER COOLER ON THE FLOOR
 PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-01-07 Cont ID  
Sent By cpuell Date 2016-01-08 Time 08:17 Rev Time 0.25
Received By eschneid Date 2016-01-07 Time 10:07 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-12-17 Cont ID  
Sent By eschneid Date 2015-12-17 Time 09:03 Rev Time 0.25
Received By eschneid Date 2015-12-16 Time 17:21 Sent To  
Notes
2015-12-17 09:58:58FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE CIVIL SITE PLAN DOES NOT MATCH
 THE COTLEUR & HEARING SITE PLAN. ALL PLANS SHALL SHOW
 SAME CONDITION.
  
 2) REPEAT COMMENT: PRIOR TO ZONING APPROVAL OF THIS
 PERMIT, THE LANDSCAPE PLAN SHALL BE SUBMITTED AS A
 SEPARATE PERMIT, WITH PLANS. THE LANDSCAPE PLAN SHALL
 REFLECT THE RAMP AND STAIRS FOR THE PUBLIC TO ACCESS
 THE SALES TRAILER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-11-23 Cont ID  
Sent By eschneid Date 2015-11-23 Time 17:27 Rev Time 0.50
Received By eschneid Date 2015-11-23 Time 17:27 Sent To  
Notes
2015-11-23 17:32:17FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE CIVIL SITE PLAN DOES NOT MATCH THE COTLEUR &
 HEARING SITE PLAN. ALL PLANS SHALL SHOW SAME CONDITION.
  
 2) PRIOR TO ZONING APPROVAL OF THIS PERMIT, THE
 LANDSCAPE PLAN SHALL BE SUBMITTED AS A SEPARATE PERMIT,
 WITH PLANS. THE LANDSCAPE PLAN SHALL REFLECT THE RAMP
 AND STAIRS FOR THE PUBLIC TO ACCESS THE SALES TRAILER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By eschneid Date 2015-09-11 Time 17:12 Rev Time 1.00
Received By eschneid Date 2015-09-11 Time 17:12 Sent To B
Notes
2015-09-11 17:18:21FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PROVIDE A REVISED SITE PLAN THAT SHOWS THE ADA RAMPS
 AND THE STAIRS THAT ARE REQUIRED FOR THE PUBLIC TO
 ACCESS THE SALES TRAILER.
  
 2) PRIOR TO ZONING APPROVAL OF THIS PERMIT, THE
 LANDSCAPE PLAN SHALL BE SUBMITTED AS A SEPARATE PERMIT,
 WITH PLANS. THE LANDSCAPE PLAN SHALL REFLECT THE RAMP
 AND STAIRS FOR THE PUBLIC TO ACCESS THE SALES TRAILER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2015-08-31 11:19:238/31/15