Plan Review Details - Permit 15080587
Plan Review Stops For Permit 15080587
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-10 Cont ID  
Sent By jwitmer Date 2015-11-10 Time 06:55 Rev Time 0.00
Received By jwitmer Date 2015-11-10 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-08 Cont ID  
Sent By jwitmer Date 2015-09-08 Time 15:36 Rev Time 0.00
Received By jwitmer Date 2015-09-08 Time 11:44 Sent To  
Notes
2015-09-08 15:36:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080587
 ADD: 201 CLEMATIS ST.
 CONT: BSA CORP.
 TEL: (561)272-6350
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 08/2015
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) THE PLANS SHOW WHITEOUT AND HAND WRITEN 2014
 FLORIDA BUILDING CODE, EXISTING BUILDING CODE.
  
 1B) THE COVERSHEET LIST THE 1994 FLORIDA ACCESSIBLITY
 CODE, UPDATE TO THE 2014 FLORIDA ACCESSIBILITY CODE,
 5TH EDITION
  
 2) SHEETS A003 & A004 BOTH SHOW RAISED PLATFORMS, NO
 DESIGN INFORMATION HAS BEEN PROVIDED FOR FLOOR LOADING.
 2014 FBC-B TABLE 1607.1.
  
 3) SHEETS A003 & A004 ALSO SHOW RAISED PLATFORMS BUT
 THE PLANS DO NOT SHOW COMPLIANCE WITH 2014 FLORIDA
 ACCESSIBILITY CODE 201.1.1. OR AN EXCEPTION.
  
 4) HE PLANS DO NOT PROVIDE THE HEIGHT OF THE STEPS AND
 LEVELS OF THE RAISED PLATFORMS. THE PLANS INDICATE THE
 PLATFORMS ARE DEMOUNTABLE. ARE THEY CONSIDERED,
 PERMANENT OR TEMPORARY? 2014 FBC-B 410.4 OR 410.4.1 .
  
 5) THE OTHER ISSUE IS THE PLANS MAY OR MAY NOT REQUIRE
 A GUARDRAIL DEPENDING ON THE HEIGTH OF THE TOP
 PLATFORM. DIMENSIONS WERE NOT PROVIDED FOR THE STAIRS
 AND LANDINGS. 2014 FBC-B 1013.1.
  
 6) THE PLANS ARE NOT CLEAR AT THE ENDS OF THE RAISED
 PLATFORMS IF THERE IS A WALL TO THE NORTH SIDE OF THE
 PLANTFORM? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 17:48 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 17:25 Sent To I
Notes
2015-11-24 17:49:52THIS PERMIT HAD BEEN APPROVED BACK ON 10/13/15 AND THE
 PREVIOUSLY STAMPED PAGES REMAIN IN THE SET. I
 RE-STAMPED THE FIRST SHEET ONLY WITH THE ORIGINAL DATE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-13 Cont ID  
Sent By albarran Date 2015-10-13 Time 17:07 Rev Time 0.00
Received By albarran Date 2015-10-13 Time 16:05 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-16 Cont ID  
Sent By pleduc Date 2015-11-16 Time   Rev Time 0.00
Received By pleduc Date 2015-11-16 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By pleduc Date 2015-08-21 Time   Rev Time 0.00
Received By pleduc Date 2015-08-20 Time 13:29 Sent To  
Notes
2015-08-21 10:19:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 2) CAREFUL ATTENTION IS STRONGLY RECOMMENDED IN THE
 DESIGN AND PLACEMENT OF CEILING MOUNTED ELECRTICAL
 EQUIPMENT AND THE DESIGN AND PLACEMENT OF SPRINKLER
 HEADS. SPRINKLER HEADS SHALL NOT BE OBSTRUCTED BY
 CEILING MOUNTED EQUIPMENT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 17:51 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 09:26 Sent To  
Notes
2015-11-24 17:53:0111/24/15 PASSED ALL REVIEWS. CONTRACTOR NOTIFIED VIA
 PHONE MESSAGE IN LIEU OF EMAIL. SENT TO LARGE READY BIN
 "B". MA
2015-11-05 09:26:24B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-13 Cont ID  
Sent By albarran Date 2015-10-13 Time 17:07 Rev Time 0.00
Received By albarran Date 2015-08-17 Time 13:23 Sent To  
Notes
2015-10-13 17:11:3610/13/15 PASSED ELECTRICAL REVIEW. IN LIEU OF EMAIL KIM
 WAS NOTIFIED VIA PHONE CALL. (NO EMAIL ON FILE FOR THIS
 CONTRACTOR) SENT TO SMALL DENIED BIN "B". MA
2015-08-17 13:23:50B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 15:46 Rev Time 0.00
Received By ccole Date 2015-11-13 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 16:54 Rev Time 0.00
Received By ccole Date 2015-08-26 Time 16:54 Sent To  
Notes
2015-08-26 17:09:501ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080587
 8/26/15
  
 1) SHEETS M000 & M200: CORRECT THE O/A CALCULATIONS TO
 INDICATE 475 CFM'S IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. THE TABLE INDICATES AN OCCUPANT
 DENSITY OF 70 PERSONS PER 1000 SQ. FT. (.07 X 360 SQ.
 FT.= 26 PERSONS) X 10 CFM EACH = 260 CFM + 215 CFM =
 475 CFM. PLEASE REVISE THE TABLE AND THE RTU SCHEDULE,
 AND PLACE DIMENSIONS ON THE FLOOR PLANS SO SQUARE
 FOOTAGE CALCULATIONS CAN BE VERIFIED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  