Plan Review Details - Permit 15080504
Plan Review Stops For Permit 15080504
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 12:40 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 12:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-19 Cont ID  
Sent By skennedy Date 2015-10-19 Time 09:08 Rev Time 0.00
Received By skennedy Date 2015-10-19 Time 09:08 Sent To  
Notes
2015-10-19 09:17:421ST REVIEW: FBC 2014 5TH ED.
  
 AS INDICATED ON THE FIRST REVIEW, THE SCOPE OF WORK IS
 STILL NOT FULLY CLEAR. PROVIDE CLARITY PER FBC 107 AS
 PREVIOUSLY REQUESTED.
  
 PLEASE CLARIFY WETHER THE DOORS & WINDOWS ARE TO BE
 REPLACED OR ARE EXISTING. THE PLAN INDICATES BOTH.
  
 PROVIDE DETAIL FOR THE INFILL CBS WALL AT THE LOCATION
 OF THE 96" SGD.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 10:59 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 10:59 Sent To Z
Notes
2015-08-14 11:07:351ST REVIEW: FBC 2014 5TH ED.
  
 THE CODE IN EFFECT CITED IS OUTDATED. THIS APPEARS TO
 BE A LEVEL I ALTERATION OF A SFD PER THE FBC EXISTING
 BUILDING CODE 5TH EDITION.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 THERE IS A LACK OF DETAIL AND SCOPE OF WORK INDICATED
 AND ONLY GENERAL PARAMETERS GIVEN. PROVIDE ADDITIONAL
 DETAIL TO DEMONSTARTE THE FOLLOWING:
  
 INTERIOR WALL TYPICAL DETAIL, FURRING AND DRYWALL
 DETAIL, SPECIFY ROOF JOIST THAT MAY BE REPLACED,
 SPECIFY IF NEW OPENING IN WALL REQUIRES STRUCTURAL
 SUPPORT TO THE ROOF MEMBERS.
  
 PLEASE NOTE A COMPLETE REVIEW CANNOT BE PERFORMED DUE
 TO THE LACK OF INFORMATION PROVIDED.
  
 ADDITIONALLY, THE SCOPE OF WORK IN DICATES WORK THAT
 MAY EXCEED THE THE CLAIMED VALUE OF $7,000.00. PER FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PROVIDE A COPY OF YOUR CONTRACT TO DETERMINE THE SCOPE
 OF WORK AND VALUE OF THE JOB.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 12:08 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-19 Cont ID  
Sent By skennedy Date 2015-10-06 Time 15:13 Rev Time 0.00
Received By skennedy Date 2015-10-06 Time 15:13 Sent To  
Notes
2015-10-06 15:17:132ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 REVISE THE PLAN TO COMPLY WITH THE FOLLOWING SECTION:
 FBCR-E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 09:31 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 09:31 Sent To  
Notes
2015-08-14 10:14:331ST REVIEW: FBC 2014 5TH ED./ NEC2011
  
 NO ELECTRICAL DETAILS ARE PROVIDED; ELECTRICAL
 MODIFICATIONS ARE REQUIRED IN THE NEWLY ARRANGED
 KITCHEN, BEDROOMS, AND THE BATHROOM AND TO FOR THE A/C
 CONDENSER RELOCATION AND FOR ASSURANCE OF SMOKE AND CO
 DETECTORS. PROVIIDE AN ELECTRICAL PLAN PER THE MINIMUM
 CRITERIA OF FBC 107 AND DEMONSTRATE COMPLIANCE WITH THE
 FOLLOWING:
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET WHERE
 WALLS ARE BEING MODIFIED.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2015-10-08 Cont ID  
Sent By tklarge Date 2015-10-08 Time 12:15 Rev Time 0.00
Received By tklarge Date 2015-10-08 Time 12:15 Sent To  
Notes
2015-10-08 12:16:34GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By gjohnson Date 2015-10-05 Time 15:59 Rev Time 0.00
Received By tklarge Date 2015-10-05 Time 15:59 Sent To  
Notes
2015-10-05 15:58:451ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 GAS COMMENTS:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-01 Cont ID  
Sent By fmittner Date 2015-10-01 Time 10:09 Rev Time 0.00
Received By fmittner Date 2015-10-01 Time 10:09 Sent To  
Notes
2015-10-01 10:10:01WINDOW GRID PATTERN TO BE CONSISTENT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 12:40 Rev Time 0.00
Received By skennedy Date 2015-10-22 Time 09:56 Sent To  
Notes
2015-10-22 09:56:27RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-19 Cont ID  
Sent By skennedy Date 2015-10-19 Time 09:17 Rev Time 0.00
Received By skennedy Date 2015-09-18 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 10:34 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 09:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-11-02 Cont ID  
Sent By skennedy Date 2015-11-02 Time 14:58 Rev Time 0.00
Received By skennedy Date 2015-11-02 Time 14:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By skennedy Date 2015-10-05 Time 15:22 Rev Time 0.00
Received By skennedy Date 2015-10-05 Time 15:22 Sent To P
Notes
2015-10-05 15:23:251ST REVIEW: FBC 2014 5TH ED.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 12:08 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 12:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-19 Cont ID  
Sent By skennedy Date 2015-10-19 Time 08:51 Rev Time 0.00
Received By skennedy Date 2015-10-19 Time 08:13 Sent To  
Notes
2015-10-19 09:07:283RD REVIEW: FBC 2014 5TH ED.
  
 A PLAN AND PARTIALLY COMPLETED ENERGY FORM HAS BEEN
 SUPPLIED. THE IS NOT ACCEPTABLE AS THE DUCT MATERIAL
 AND DIMENSIONS OF VARIOUS PORTIONS OF THE DUCT SYSTEM
 ARE NOT IDENTIFIED. THE ENERGY SUBMITTAL IS NOT FILLED
 OUT, THERE IS NO EQUIPMENT SIZING CALCULATION PROVIDED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN
  
 FBC-ER403.6.1 PROVIDE A SIZING CALCULATION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-05 Cont ID  
Sent By skennedy Date 2015-10-05 Time 15:20 Rev Time 0.00
Received By skennedy Date 2015-10-05 Time 15:20 Sent To  
Notes
2015-10-05 15:21:112ND REVIEW: FBC 2014 5TH ED.
  
 THERE WAS NO MECHANICAL OR IN THE ORIGINAL NOR THE
 RE-SUBMITTAL. THE COMMENTS BELOW ARE REPEAT COMMENTS.
  
 THERE IS A LACK OF DETAIL AND INFORMATION TO DETERRMINE
 COMPLIANCE WITH THE MECHANICAL CODE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 WHAT ARE YOU DOING IN TERMS OF RELOCATING THE AHU? IF
 PLACING IN THE ATTIC, PROVIDE DETAIL TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 10:20 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 10:20 Sent To  
Notes
2015-08-14 10:49:591ST REVIEW: FBC 2014 5TH ED.
  
 THERE IS A LACK OF DETAIL AND INFORMATION TO DETERRMINE
 COMPLIANCE WITH THE MECHANICAL CODE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 WHAT ARE YOU DOING IN TERMS OF RELOCATING THE AHU? IF
 PLACING IN THE ATTIC, PROVIDE DETAIL TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 12:09 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 12:09 Sent To  
Notes
2015-10-31 12:14:41SEE 15100140

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-08 Cont ID  
Sent By tklarge Date 2015-10-08 Time 11:15 Rev Time 0.00
Received By tklarge Date 2015-10-08 Time 11:15 Sent To  
Notes
2015-10-08 11:18:13PLUMBING APPROVED.SEE PERMIT APPLICATION # 15100140 FOR
 PLUMBING FOR THIS STRUCTURE.PLUMBING SUB-PERMIT NOT
 REQUIRED UNDER THIS PERMIT. A SEPARATE PERMIT IS
 REQUIRED FOR THE GAS. T.LARGE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-05 Cont ID  
Sent By gjohnson Date 2015-10-05 Time 15:46 Rev Time 0.00
Received By gjohnson Date 2015-10-05 Time 15:46 Sent To  
Notes
2015-10-05 15:55:221ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. LAUNDRY STACK SHALL CONNECT DOWN STREAM OFF BATHROOM
 GROUP.ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS
 SHALL CONNECT TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE HORIZONTAL WET VENT.
 PER FBC P SEC 912.1
 2. PROVIDE WATER RISER DIGRAM PER WPB AMEND. SEC
 107.3.5.3(11)

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 10:14 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 10:14 Sent To  
Notes
2015-08-14 10:52:57THERE DOES NOT APPEAR TO BE PLUMBING REQUIRING A PERMIT
 IN THE SCOPE OF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-10-05 Cont ID  
Sent By skennedy Date 2015-10-05 Time 15:31 Rev Time 0.00
Received By skennedy Date 2015-10-05 Time 15:31 Sent To  
Notes
2015-10-05 15:19:19ROOFING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By fmittner Date 2015-10-01 Time 10:09 Rev Time 0.00
Received By fmittner Date 2015-10-01 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By fmittner Date 2015-08-21 Time 16:59 Rev Time 0.00
Received By fmittner Date 2015-08-21 Time 16:59 Sent To  
Notes
***NONE***