Plan Review Details - Permit 15080469
Plan Review Stops For Permit 15080469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-15 Cont ID  
Sent By aclange Date 2015-09-15 Time 16:16 Rev Time 0.00
Received By aclange Date 2015-09-15 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By aclange Date 2015-09-01 Time 16:43 Rev Time 0.00
Received By aclange Date 2015-09-01 Time 16:43 Sent To  
Notes
2015-09-01 16:53:47****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 9/1/15
  
  
 1. FBC 3105.4 AND FBC 3105.1 LOADS. PROVIDE DESIGN
 CRITERIA. THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
  
 1. MINIMUM WIND SPEED 105 MPH.
  
 2. EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER
 16. PROVIDE WIND DESIGN CRITERIA.
  
 2. PROVIDE AWNING HEIGHT FROM GRADE. FBC 3105.3.1.1
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-15 Cont ID  
Sent By aclange Date 2015-09-15 Time 16:16 Rev Time 0.00
Received By aclange Date 2015-09-09 Time 08:38 Sent To  
Notes
2015-09-10 08:38:14RESUB ROUTED TO ALANGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-01 Cont ID  
Sent By aclange Date 2015-09-01 Time 16:53 Rev Time 0.00
Received By aclange Date 2015-08-13 Time 11:52 Sent To  
Notes
2015-08-18 17:53:32TO MISC 2 BOX.
2015-08-13 11:52:58ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-18 Cont ID  
Sent By aaponte Date 2015-08-18 Time 17:53 Rev Time 0.00
Received By aaponte Date 2015-08-18 Time 17:53 Sent To  
Notes
***NONE***