Plan Review Details - Permit 15080427
Plan Review Stops For Permit 15080427
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-10-08 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By jwitmer Date 2015-08-25 Time 15:48 Rev Time  
Received By jwitmer Date 2015-08-25 Time   Sent To  
Notes
2015-08-25 15:48:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080427
 ADD: 1645 PALM BEACH LAKES SUITES, 210,220, 230 & 240
 CONT: CHANDLER
 TEL: (561)791-6934
 E-MAIL: JOHN@BUILDCCC. COM
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 25/2015
 ACTION: DENIED
  
 1) SHEET A2 SHOWS AN EXISTING ATRIUM BUT THE SHARED
 ATRIUM WALL BETWEEN THE TENANCY 210 & 240 DOES NOT
 INDICATE ANY WALL RATING. 2014 FBC-B 404.6 ATRIUM
 SPACES SHALL BE SEPARATED FROM ADJACENT SPACES BY A
 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707.
  
 2) DISCREPANCY IN PLANS. FOR THE TENANT SPEARATION WALL
 SHEET A2 INDICATES A DETAIL # 1/ A2 THERE IS NO SUCH
 DETAIL, TYPO IT APPEARS THAT THE DETAIL IS FOUND ON
 SHEET A3. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) DISCREPANCY IN PLANS SHEET A2 VERSES A5 THE DOOR
 LEADING TO THE STAIRWELL CLOSEST TO UNIT # 240. THE 90
 MINUTE STAIRWELL DOOR SHOULD BE A INSWING DOOR INTHE
 DIRECTION OF EXIT TRAVEL WITH OCCUPANT LOADS OF 50 OR
 MORE PERSONS. 2014 FBC-B 1008.1.2
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 11:28 Rev Time 0.00
Received By skennedy Date 2015-09-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-20 Cont ID  
Sent By scaldero Date 2015-08-20 Time 14:01 Rev Time 0.00
Received By scaldero Date 2015-08-20 Time 13:50 Sent To  
Notes
2015-08-20 14:04:03PERMIT # 15080427
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED WITH COMMENTS:
  
 1) THE STAIRWELL EGRESS CLOSEST TO RESTROOMS SHOWS THE
 DOOR OPENING IN DIFFERENT DIRECTIONS, DEPENDING ON
 WHICH SHEET YOU ARE LOOKING AT.
 THIS DOOR SHOULD OPEN TOWARDS THE PATH OF EGRESS (I.E.
 PUSH OPEN TOWARDS THE STAIRWELL).
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-08 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-10-05 Time 08:04 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 11:28 Rev Time 0.00
Received By skennedy Date 2015-08-12 Time 13:36 Sent To  
Notes
2015-08-12 13:36:33C08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By ccole Date 2015-10-06 Time 10:35 Rev Time 0.00
Received By ccole Date 2015-10-06 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-17 Cont ID  
Sent By ccole Date 2015-08-17 Time 15:08 Rev Time 0.00
Received By ccole Date 2015-08-17 Time 15:08 Sent To  
Notes
2015-08-17 15:20:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080427
 8/17/15
  
 1) SHEET M2.1: FIRE DAMPERS MISSING FOR DUCTS
 PENETRATING RATED WALLS AT: (OPEN OFFICE 100/MECHANICAL
 ROOM), (COMMON CORRIDOR/MECHANICAL ROOM), (OPEN OFFICE
 110/COMMON CORRIDOR), (OPEN OFFICE 130/COMMON
 CORRIDOR), AND (ATRIUM/COMMON CORRIDOR).
 2) M2.1: PLEASE INCLUDE THE DAMPERS IN THE KEY NOTES,
 AND PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION
 DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-19 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 07:10 Rev Time 0.00
Received By gjohnson Date 2015-08-19 Time 17:01 Sent To  
Notes
***NONE***