Plan Review Details - Permit 15080417
Plan Review Stops For Permit 15080417
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-08-19 Cont ID  
Sent By gjohnson Date 2015-08-19 Time 16:03 Rev Time 0.00
Received By gjohnson Date 2015-08-19 Time 16:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By gjohnson Date 2015-08-12 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2015-08-12 Time 16:33 Sent To  
Notes
2015-08-12 16:47:551ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
 1. CSST PIPING TO WATER HEATER SIZED WRONG SHALL BE
 1IN. TABLE 402.4[15]
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-19 Cont ID  
Sent By gjohnson Date 2015-08-19 Time 16:03 Rev Time 0.00
Received By gjohnson Date 2015-08-19 Time 16:03 Sent To  
Notes
2015-08-19 14:32:17RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-19 Cont ID  
Sent By lmarchan Date 2015-08-12 Time   Rev Time 0.00
Received By lmarchan Date 2015-08-12 Time 13:33 Sent To  
Notes
2015-08-12 13:33:36ROUTED TO PLUMBING $5000 & UNDER