Plan Review Details - Permit 15080380
Plan Review Stops For Permit 15080380
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2015-09-21 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time   Rev Time 0.00
Received By jwitmer Date 2015-09-21 Time   Sent To  
Notes
2015-09-21 13:22:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080380
 ADD: 801 S. OLIVE SUITE # 1409
 CONT: ANDERSON CONSTRUCTION GROUP, LLC
 TEL: (561)255-5464
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 21/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SHEET A2.1;
  
 2A) 2ND REQUEST. THE RESPONSE INDICATES SEE UPPER RIGHT
 HAND CORNER OF THE SHEET, THE RESPONSE ALSO INDICATES
 THEY ARE FILLING IN A RECESS IN A EXISTING FIRE RATED
 WALL OUR WORK DOES NOT HAVE TO BE FIRE RATED. IF THE
 WALL IS A FIRE RATED WALL THEN YES IT NEEDS A ASSEMBLY
 NUMBER, EITHER A UL LISTING OR GYPSUM ASSOCIATION
 NUMBER FOR A FIRE RATING FOR THE WALL.
 IS THE WALL YOU ARE WORKING ON S METAL STUD WALL AND
 THEN THE FIRE RATED WALL BEHIND IT? IF SO PROVIDE THE
 DETAIL AS SUCH.
  
 SHOWS A FIRE RATED WALL BEING FILLED IN, THERE IS NO
 INFORMATION AS TO WHAT FRAMING MEMBERS ARE TO BE USED
 FOR THE INSTALATION OR FOR THE TYPE OF MATERIAL FOR A 1
 HOUR FIRE RATED ASSEMBLY. 2014 FBC-B 708.3
 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A
 FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
  
 2B) THE FIRE RATED WALL WILL HAVE PENETRATIONS THROUGH
 THE DRYWALL, THERE HAS BEEN NO DETAILS SHOWING CODE
 COMPLIANCE FOR 2014 FBC-B 708.7 PENETRATIONS.
 PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH
 SECTION 714.
 714.3 FIRE-RESISTANCE-RATED WALLS.
 PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS,
 SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY
 WITH SECTIONS 714.3.1 THROUGH 714.3.3. PENETRATIONS IN
 SMOKE BARRIER WALLS SHALL ALSO COMPLY WITH SECTION
 714.5.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By jwitmer Date 2015-08-14 Time 11:28 Rev Time  
Received By jwitmer Date 2015-08-14 Time 10:01 Sent To  
Notes
2015-08-14 11:28:33 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080380
 ADD: 801 S. OLIVE SUITE # 1409
 CONT: ANDERSON CONSTRUCTION GROUP, LLC
 TEL: (561)255-5464
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 14/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0 :
 1A) LIST THE CODE DESIGN AS THE 2010 FBC- EXISTING
 BUILDING. PLEASE BE AWARE THAT THE 2014 FBC-EXISTING
 BUILDING WAS ADOPTED STATEWIDE ON JUNE 30, 2015. PLEASE
 UPDATE PLANS.
  
 1B) MINIMUM BLDG. TYPE IS LISTED AS A TYPE V. PLEASE
 NOTE THIS IS A HIGH-RISE BLDG. THE 2014 FBC-B TABLE 503
 REQUIRES THIS TO BE A BLDG. TYPE 1A.
  
 1C) THE COVERSHEET ALSO LIST THE OCCUPANCY TYPE AS A
 R3. PLEASE NOTE THIS IS A SINGLE FAMILY DWELLING.
 CONDOMINIUMS ARE CONSIDERED A R2 PLEASE SEE THE 2014
 FBC-B 310.4 RESIDENTIAL GROUP R-2.
  
 2) SHEET A2.1;
  
 2A) SHOWS A FIRE RATED WALL BEING FILLED IN, THERE IS
 NO INFORMATION AS TO WHAT FRAMING MEMBERS ARE TO BE
 USED FOR THE INSTALATION OR FOR THE TYPE OF MATERIAL
 FOR A 1 HOUR FIRE RATED ASSEMBLY. 2014 FBC-B 708.3
 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A
 FIRERESISTANCE RATING OF NOT LESS THAN 1 HOUR.
  
 2B) THE FIRE RATED WALL WILL HAVE PENETRATIONS THROUGH
 THE DRYWALL, THERE HAS BEEN NO DETAILS SHOWING CODE
 COMPLIANCE FOR 2014 FBC-B 708.7 PENETRATIONS.
 PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH
 SECTION 714.
 714.3 FIRE-RESISTANCE-RATED WALLS.
 PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS,
 SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY
 WITH SECTIONS 714.3.1 THROUGH 714.3.3. PENETRATIONS IN
 SMOKE BARRIER WALLS SHALL ALSO COMPLY WITH SECTION
 714.5.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-17 Cont ID  
Sent By skennedy Date 2015-09-17 Time 17:07 Rev Time 0.00
Received By skennedy Date 2015-09-17 Time 17:07 Sent To  
Notes
2015-09-17 17:08:12TO TKLARGE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 15:15 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 15:12 Sent To  
Notes
2015-09-10 15:17:221ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 THE NEC CODE VERSION REFERENCED IS INCORRECT, SHOULD BE
 NEC 2011. OTHERWISE OK. PLEASE REVISE WHEN REVISING
 OTHER SHEETS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2015-09-17 Time 13:56 Sent To  
Notes
2015-09-17 13:56:15RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 15:15 Rev Time 0.00
Received By skennedy Date 2015-08-11 Time 07:59 Sent To  
Notes
2015-08-12 08:02:13B36

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By tklarge Date 2015-09-18 Time 06:47 Rev Time 0.00
Received By tklarge Date 2015-09-18 Time 06:06 Sent To B
Notes
2015-09-18 06:48:52PLACED IN J.WITMER'S CUBICLE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By tklarge Date 2015-08-18 Time 04:03 Rev Time 0.00
Received By tklarge Date 2015-08-18 Time 02:57 Sent To  
Notes
2015-08-18 03:57:251) SUBMIT A FLOOR PLAN FOR THE ENTIRE UNIT SHOWING ALL
 THE BATHROOMS /.WPB AMEND. TO FBC SEC.107.3.5.1.
 2) SUBMIT FIRE SAFING DETAILS FOR ANY PIPING THAT
 PENETRATES A FIRE RATED PARTITION OF SMOKE
 PARTITION.COMPLY WITH 2014 FBC SEC. 714.
 3) SHT.A-1.0 - THE PLANS REFER TO THE 2010 FBC AND IN
 GENERAL NOTE #9, THE 2007/2009 CODES ARE REFERENCED.
 DELETE THESE REFERENCES AND INSERT THE 2014 FBC FAMILY
 OF CODES.
 4) THE PLANS LIST THE OCCUPANCY TYPE OF THIS STRUCTURE
 AS AN R-3 WHEN IT IS CLEARLY AN R-2 OCCUPANCY.CHANGE
 THE OCCUPANCY TYPE TO READ R-2.
 5) THE PLANS ARE VAGUE AS TO THE SCOPE OF PLUMBING WORK
 TO BE DONE. IS THE WATER HEATER BEING REPLACED?
 IDENTIFY IT ON THE PLANS.IDENTIFY ON THE PLANS WHAT
 EXACTLY IS BEING REPLACED AND WHAT IS EXISTING TO
 REMAIN.
 6) SHT A2.1.-DETAIL #4 - THERE IS A NOTE STATING "NEW
 WASTE LINE TO EXISTING WASTE STACK" BUT THERE IS NO
 PIPING SHOWN. CLARIFY.
 7) INDICATE ON THE PLANS IF ANY WORK IS TO BE DONE IN
 THE OTHER BATHROOM. WPB AMEND, TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  