| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15080380 |
| ADD: 801 S. OLIVE SUITE # 1409 |
| CONT: ANDERSON CONSTRUCTION GROUP, LLC |
| TEL: (561)255-5464 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. AUGUST 14/ 2015 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET A-1.0 : |
| 1A) LIST THE CODE DESIGN AS THE 2010 FBC- EXISTING |
| BUILDING. PLEASE BE AWARE THAT THE 2014 FBC-EXISTING |
| BUILDING WAS ADOPTED STATEWIDE ON JUNE 30, 2015. PLEASE |
| UPDATE PLANS. |
| |
| 1B) MINIMUM BLDG. TYPE IS LISTED AS A TYPE V. PLEASE |
| NOTE THIS IS A HIGH-RISE BLDG. THE 2014 FBC-B TABLE 503 |
| REQUIRES THIS TO BE A BLDG. TYPE 1A. |
| |
| 1C) THE COVERSHEET ALSO LIST THE OCCUPANCY TYPE AS A |
| R3. PLEASE NOTE THIS IS A SINGLE FAMILY DWELLING. |
| CONDOMINIUMS ARE CONSIDERED A R2 PLEASE SEE THE 2014 |
| FBC-B 310.4 RESIDENTIAL GROUP R-2. |
| |
| 2) SHEET A2.1; |
| |
| 2A) SHOWS A FIRE RATED WALL BEING FILLED IN, THERE IS |
| NO INFORMATION AS TO WHAT FRAMING MEMBERS ARE TO BE |
| USED FOR THE INSTALATION OR FOR THE TYPE OF MATERIAL |
| FOR A 1 HOUR FIRE RATED ASSEMBLY. 2014 FBC-B 708.3 |
| FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A |
| FIRERESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| |
| 2B) THE FIRE RATED WALL WILL HAVE PENETRATIONS THROUGH |
| THE DRYWALL, THERE HAS BEEN NO DETAILS SHOWING CODE |
| COMPLIANCE FOR 2014 FBC-B 708.7 PENETRATIONS. |
| PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH |
| SECTION 714. |
| 714.3 FIRE-RESISTANCE-RATED WALLS. |
| PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS, |
| SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY |
| WITH SECTIONS 714.3.1 THROUGH 714.3.3. PENETRATIONS IN |
| SMOKE BARRIER WALLS SHALL ALSO COMPLY WITH SECTION |
| 714.5. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |