Plan Review Details - Permit 15080378
Plan Review Stops For Permit 15080378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 08:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By jwitmer Date 2015-08-25 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2015-08-25 Time 06:02 Sent To  
Notes
2015-08-25 07:02:21BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080378
 ADD: 777 S. FLAGLER DR. SUITE # 1001E
 CONT: BUTLER
 TEL: (561)832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 25/2015
 ACTION: DENIED
  
 1) SHEET A-2.2 ROOM 1006 ADAPTABLE: PLEASE REVIEW THE
 2014 FL ACCESSIBLITY CODE RESTROOMS IN PRIVATE OFFICES
 AND WHEN THE EXCEPTION CAN BE APPLIED. THIS CODE IS
 CODE ARTICLE SPECIFIC. NOTE SECTION 603 .2.3 DOOR SWING
 EXCEPTION # 1 IS SPECIFIC TO TOLIET ROOMS WITHIN
 PRIVATE OFFICES, THE DOOR CAN SWING INTO RESTROOMS IN
 PRIVATE OFFICE.
  
 1A) THE CODE IS ALSO SPECIFIC TO THE REQUIRED OVERLAP
 IN 604.3.2. THE CODE DOES NOT GIVE ANY EXCEPTIONS.
 PLEASE NOTE THE CODE DOES ALLOW FOR
 THE TOLIET SEAT HEIGHT NOT NEEDING TO BE 17- TO 19
 INCHES WITH THE EXCEPTION TOLIET ROOMS IN PRIVATE
 OFFICES 604.4.
  
 1B) THE CODE DOES ALLOW FOR NOT INSTALLING GRAB BARS IN
 A PRIVATE OFFICE BUT THE REINFORCEMENT THAT IS REQUIRED
 BY 604.5 DOES NEED TO BE INSTALLED, PLEASE PROVIDE A
 DETAIL SHOWING CODE COMPLIANCE WITH 604.5 & 609.8
 STRUCTURAL STRENGTH OF 250 LBS WHEN APPLIED AT ANY
 POINT OF THE GRAB BAR.
  
 2) SHEET M2.2 INDICATES THE USE OF A WALL MOUNTED MIAMI
 TECH WIND RATED CONDENSING UNIT BRAKET AND STAND.
 PLEASE PROVIDE A PRODUCT APPROVAL OR ENGINEERING FOR A
 SITE SPECIFIC USE.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 3) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-03 Time 09:14 Rev Time 0.00
Received By albarran Date 2015-11-03 Time 08:57 Sent To I
Notes
2015-11-03 09:15:05ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 18:46 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 18:20 Sent To I
Notes
2015-10-05 18:49:26PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. CORRECT ENLARGED INSET 3, ROUTING OF ELECTRICAL VS.
 IT WIRE LINES.
 2. NIGHT LIGHTING OR EMERGENCY LIGHT IS NOT CLEARLY
 DEFINED.
 3. INDICATE THE LOCATION OF THE ELECTRICAL PANELS AND
 THE STEP DOWN TRANSFORMER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-19 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-03 Time 09:18 Rev Time 0.00
Received By albarran Date 2015-10-15 Time 15:35 Sent To  
Notes
2015-11-03 09:20:2811/3/15 THIS PERMIT HAS SUCCESSFULLY BEEN THROUGH ALL
 REVIEWS AND IS READY FOR ISSUANCE. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE READY BIN :"B". MA
2015-10-15 15:36:15C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 18:49 Rev Time 0.00
Received By albarran Date 2015-08-11 Time 16:24 Sent To  
Notes
2015-10-05 18:52:3410/5/15 FAILED ELECTRICAL AND OTHER REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "B". MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-23 Cont ID  
Sent By ccole Date 2015-10-23 Time 15:20 Rev Time 0.00
Received By ccole Date 2015-10-23 Time 15:20 Sent To  
Notes
2015-10-23 15:22:24PERMIT #15080378
 10/23/15
 PROVISO:
  
 SITE SPECIFIC ENGINEERING FOR TIE-DOWN OF THE CONDENSER
 TO THE WALL BRACKET SHALL BE ON-SITE AT TIME OF
 INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By ccole Date 2015-08-14 Time 14:28 Rev Time 0.00
Received By ccole Date 2015-08-14 Time 14:28 Sent To  
Notes
2015-08-14 14:39:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080378
 8/14/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION, AND PROVIDE HEAT LOAD CALCULATIONS FOR
 THE NEW MITSUBISHI MINI-SPLIT AC SYSTEM
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) SHEET M0.1: CORRECT THE HVAC DESIGN CONDITIONS IN
 ACCORDANCE WITH ACCA MANUAL N, TABLE 1A: OUTDOOR- 90
 DB, 78 WB.
 3) M1.1: REFERENCE SECTION 301.15 FBC-14 MECHANICAL AND
 PROVIDE THE DESIGN WIND PRESSURES FOR THE ROOF TOP
 MIAMI TECH CU AND CU BRACKET INSTALLATION. SUBMIT TWO
 COPIES OF A CURRENT FLORIDA PRODUCT APPROVAL FOR THE
 BRACKET REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD. THE ENGINEER SHALL CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL DETAILS, NOTES, ANCHOR AND FASTENER
 SCHEDULES APPLICABLE TO THE PROPOSED INSTALLATION.
 4) M4.1, VENTILATION CALCULATIONS: UPDATE THE ASHRAE
 62.1 REFERENCE TO 2010. REFER TO SECTION 809.2 FBC-14
 EXISITING BUILDING CODE AND SHOW COMPLIANCE- ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 5) COMMISSSIONING OF THE BUILDING MECHANICAL AND
 ELECTRICAL POWER AND LIGHT SYSTEMS ARE REQUIRED IN
 ACCORDANCE WITH SECTION C408 FBC-14 ENERGY COMPLIANCE.
 PLEASE PROVIDE A NARRATIVE ON THE PLAN DESCRIBING THE
 PROPOSED COMMISSIONING PROCEDURE AS OUTLINED IN SECTION
 C408.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By gjohnson Date 2015-10-21 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2015-10-21 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By gjohnson Date 2015-08-19 Time 13:38 Rev Time 0.00
Received By gjohnson Date 2015-08-19 Time 13:38 Sent To  
Notes
2015-08-19 13:48:551ST REVIEW: FBC 2014
  
 COMMENTS:
  
 1.PLEASE SHOW BREAKROOM SINK TO COMPLY WITH KNEE AND
 TOE SPACE . FBCA SEC 306.2 AND 306.3
 2. VANITY CAN NOT OVERLAP INTO TOILET CLEARANCE IN
 TOILET ROOM 1006 SHEET A-2.2 DETAIL C. FBCA SEC 604.3.1
 AND 604.3.2
 3. BACKFLOW PROTECTION SHALL BE PROVIDE FOR COFFEE
 MACHINE AND ICE MAKER. FBCPSEC. 608.16.10
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  