2015-08-25 07:02:21 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:15080378 |
| ADD: 777 S. FLAGLER DR. SUITE # 1001E |
| CONT: BUTLER |
| TEL: (561)832-9700 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W |
| * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| |
| 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 25/2015 |
| ACTION: DENIED |
| |
| 1) SHEET A-2.2 ROOM 1006 ADAPTABLE: PLEASE REVIEW THE |
| 2014 FL ACCESSIBLITY CODE RESTROOMS IN PRIVATE OFFICES |
| AND WHEN THE EXCEPTION CAN BE APPLIED. THIS CODE IS |
| CODE ARTICLE SPECIFIC. NOTE SECTION 603 .2.3 DOOR SWING |
| EXCEPTION # 1 IS SPECIFIC TO TOLIET ROOMS WITHIN |
| PRIVATE OFFICES, THE DOOR CAN SWING INTO RESTROOMS IN |
| PRIVATE OFFICE. |
| |
| 1A) THE CODE IS ALSO SPECIFIC TO THE REQUIRED OVERLAP |
| IN 604.3.2. THE CODE DOES NOT GIVE ANY EXCEPTIONS. |
| PLEASE NOTE THE CODE DOES ALLOW FOR |
| THE TOLIET SEAT HEIGHT NOT NEEDING TO BE 17- TO 19 |
| INCHES WITH THE EXCEPTION TOLIET ROOMS IN PRIVATE |
| OFFICES 604.4. |
| |
| 1B) THE CODE DOES ALLOW FOR NOT INSTALLING GRAB BARS IN |
| A PRIVATE OFFICE BUT THE REINFORCEMENT THAT IS REQUIRED |
| BY 604.5 DOES NEED TO BE INSTALLED, PLEASE PROVIDE A |
| DETAIL SHOWING CODE COMPLIANCE WITH 604.5 & 609.8 |
| STRUCTURAL STRENGTH OF 250 LBS WHEN APPLIED AT ANY |
| POINT OF THE GRAB BAR. |
| |
| 2) SHEET M2.2 INDICATES THE USE OF A WALL MOUNTED MIAMI |
| TECH WIND RATED CONDENSING UNIT BRAKET AND STAND. |
| PLEASE PROVIDE A PRODUCT APPROVAL OR ENGINEERING FOR A |
| SITE SPECIFIC USE. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31) (G) PRE-ENGINEERED A/C STANDS |
| |
| 3) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |