Plan Review Details - Permit 15080369
Plan Review Stops For Permit 15080369
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By albarran Date 2015-09-22 Time 16:45 Rev Time 0.00
Received By albarran Date 2015-09-22 Time 16:21 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By albarran Date 2015-09-10 Time 13:08 Rev Time 0.00
Received By albarran Date 2015-09-10 Time 11:06 Sent To I
Notes
2015-09-10 13:39:59PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PER NFPA 72 SECTION 17.14.6, YOU SHALL HAVE A MANUAL
 PULL STATION WITHIN 5' OF THE EXIT. THERE IS NO PULL
 STATION BY THE EXIT IN THE RECEPTION AREA. IF THIS
 SYSTEM IS EXEMPT FROM THIS REQUIREMENT DUE TO BEING A
 FULLY SPRINKLED BLDG. YOU SHALL STATE SO ON THE PLANS.
 2. PER FBC-C SECTION 907.1.2, THE SHOP DRAWINGS SHALL
 INCLUDE CONDUCTOR TYPE AND SIZE ALONG WITH VOLTAGE DROP
 CALCS.
 3. THIS SAME SECTION REQUIRES THAT YOU SUBMIT
 MANUFACTURERS SPEC SHEETS FOR ALL EQUIPMENT AND DEVICES
 BEING USED ON THE SYSTEM. YOU TRIED TO COMPLY WITH THIS
 BY SENDING LITERATURE ON A POWER SUPPLY BUT THIS POWER
 SUPPLY DIFFERS FROM THE ONE INDICATED ON THE DRAWINGS.
 4. WHILE AT IT, YOU MAY WANT TO EDIT THE HEADING LABEL
 ON THE CURRENT DRAW CHART TO READ BOTH ALARM & NON
 ALARM CURRENT DRAWS.
 5. THE RISER DIAGRAM REFLECTS THE MAIN FACP AND AN
 EXISTING NAC PANEL BUT IT FAILS TO INCLUDE THE NEW
 POWER SUPPLY INDICATED PER YOUR SUBMITTED SPEC SHEET
 AND LOCATED IN THE WIRE ROOM. YOU SHALL INDICATE THE
 LOCATIONS OF THE FACP AND ALL POWER SUPPLIES HAVING
 ANYTHING TO DO WITH THIS PORTION OF THE SYSTEM.
 6. I COULDN'T HELP BUT NOTICE THAT YOU MAKE REFERENCE
 TO NFPA 2, SECTION 5.14.5.8. PLEASE HELP ME UNDERSTAND
 WHAT DOE HYDROGEN HAVE TO DO WITH THIS PROJECT.
 FURTHERMORE, HELP ME FIND THAT SECTION. MY VERSION OF
 THIS BOOK DOES NOT GO UP THAT HIGH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By pleduc Date 2015-09-18 Time   Rev Time 0.00
Received By pleduc Date 2015-09-18 Time 13:52 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-17 Cont ID  
Sent By pleduc Date 2015-08-17 Time   Rev Time 0.00
Received By pleduc Date 2015-08-17 Time 13:00 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-22 Cont ID  
Sent By albarran Date 2015-09-22 Time 16:48 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 08:22 Sent To  
Notes
2015-09-22 16:47:549/22/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "K". MA
2015-09-18 08:22:35RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By albarran Date 2015-09-10 Time 13:41 Rev Time 0.00
Received By albarran Date 2015-08-11 Time 13:55 Sent To  
Notes
2015-09-10 13:42:459/10/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "K". MA
2015-08-11 13:55:24ROUTED TO FIRE