Plan Review Details - Permit 15080368
Plan Review Stops For Permit 15080368
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-20 Cont ID  
Sent By jgomez Date 2015-08-20 Time 10:11 Rev Time 0.00
Received By jgomez Date 2015-08-20 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By jgomez Date 2015-08-13 Time 17:37 Rev Time 0.00
Received By jgomez Date 2015-08-13 Time 16:07 Sent To  
Notes
2015-08-13 18:46:59RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- METAL ROOFING PRODUCT APPROVAL FL11175-R2 SUBMITTED:
 DESIGN PRESSURES SHOWN ON PAGE 3 OF 17 DON'T MEET THE
 DESIGN PRESSURES FOR THE ROOF ZONE #3 ON THE MAIN HOUSE
 AS REQUIRED BY SEC. R301. THE DESIGN PRESSURES SHOWN ON
 THE SELECTED ASSEMBLY ARE OK FOR ROOF ZONES #1 (-71
 PSF) AND #2 (-93.5 PSF). THE DESIGN PRESSURES FOR ROOF
 ZONE # 3 ON A 6:12 PITCH WITH A MEAN ROOF HEIGHT OF 25'
 ON A BUILDING EXPOSURE "C" IS GREATER THAN -93.5 PSF
 (SEE TABLE R301.2(2). NEED TO SELECT ANOTHER ASSEMBLY
 THAT MEETS THE DESIGN PRESSURES OF ALL ROOF ZONES
 INCLUDING ZONE #3 OR PROVIDE ANOTHER PRODUCT APPROVAL
 THAT DOES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-08-20 Cont ID  
Sent By fmittner Date 2015-08-20 Time 09:24 Rev Time 0.00
Received By fmittner Date 2015-08-20 Time 09:24 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-08-13 Cont ID  
Sent By llouie Date 2015-08-11 Time   Rev Time 0.00
Received By fmittner Date 2015-08-11 Time   Sent To  
Notes
2015-08-13 14:48:01DETERMINED ARCHITECTURAL STYLE WAS PER POLICY FOR
 ADMINISTRATIVE APPROVAL.
2015-08-11 14:02:44CERTIFICATE OF APPROPRIATENESS REQUIRED - PROPOSING
 CHANGE IN MATERIAL FROM ASPHALT SHINGLES TO METAL ROOF.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By jgomez Date 2015-08-13 Time 16:07 Rev Time 0.00
Received By jgomez Date 2015-08-11 Time 16:03 Sent To  
Notes
2015-08-13 16:04:35JGOMEZ