Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By ccole Date 2015-08-12 Time 09:48 Rev Time 0.00
Received By ccole Date 2015-08-12 Time 09:48 Sent To  
Notes
2015-08-12 10:58:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080353
 8/12/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: PROVIDE COOLING AND HEATING LOAD
 CALCULATIONS FOR THE NEW AC SYSTEMS IN ACCORDANCE WITH
 ACCA MANUAL N OR THE ACCA/ASHRAE STANDARD 183. THE
 SUBMITTED RHEEM DESIGN STAR LOAD CALCULATION IS NOT AN
 ACCA APPROVED CALCULATION METHOD.
 2) REFERENCE SECTION C101.4.5 FBC-14 ENERGY
 CONSERVATION: "ANY NONCONDITIONED SPACE THAT IS ALTERED
 TO BECOME CONDITIONED SPACE SHALL BE REQUIRED TO BE
 BROUGHT INTO FULL COMPLIANCE WITH THIS CODE". THE PLAN
 INDICATES NEW AC IN THE STORAGE ROOM WHICH PREVIOUSLY
 HAD NO AC SYSTEM. PLEASE REVIEW CHAPTER 4 FOR
 COMPLIANCE REQUIREMENTS, AND SUBMIT ENERGY CALCULATIONS
 USING FLORIDA BUILDING COMMISION SOFTWARE AS NOTED IN
 SECTION C101.5.1. PLEASE NOTE THAT MODIFICATIONS TO THE
 BUILDING FOR IMPROVED ENERGY PERFORMANCE MAY BE
 REQUIRED.
 3) THE AIR CONDITIONING SYSTEM GENERAL NOTES, AND THE
 AHU INSTALLATION DETAIL NOTES HAVE PRINT THAT IS TOO
 FAINT TO READ. PLEASE ENLARGE AND DARKEN THE PRINT TO
 EXPEDITIE THE REVIEW- WPB AMENDMENTS TO SECTION 107.2
 FBC-14 BUILDING CODE.
 4) INDICATE CLEARLY HOW AIR IS BEING RETURNED TO THE
 AHU. THE AHU DETAIL HAS A NOTE INDICATING A RETURN DUCT
 ATTACHED TO A RETURN PLENUM BOX UNDER THE UNIT, BUT THE
 PLAN IS NOT INDICATING RETURN DUCTWORK. IS THERE A
 RETURN GRILL IN THE PLENUM BOX? IF SO, PLEASE INDICATE
 THE DIMENSIONS.
 5) THE PLAN INDICATES A "SMOKE DETECTOR" AT THE AIR
 HANDLER: PLEASE CLARIFY THE CONTROL OPERATION OF THE
 DEVICE PERTAINING TO THE NEW AND EXISITNG AC SYSTEMS-
 REFER TO SECTION 606.4 AND 606.4.1 FBC-14 MECHANICAL.
 6) PROVIDE VENTILATION CALCULATIONS FOR THE NEW
 CONDITIONED SPACE IN COMPLIANCE WITH TABLE 403.3.
 INDICATE ON THE PLAN THE REQUIRED AND PROVIDED CFM'S OF
 O/A AIR.
 7) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND INDICATE COMPLIANCE WITH SHUTOFF
 DAMPER CONTROLS FOR THE O/A INTAKE.
 8) CORRECT THE NOTE INDICATING 26 GAUGE HANGING STRAPS
 FOR THE FIBERGLASS DUCT WORK- 22 GAUGE IS REQUIRED PER
 FIGUTRE 6-1 SMACNA- FIBROUS GLASS DUCT CONSTRUCTION
 STANDARDS- 2010.
 9) SUBMIT AN ELECTRICAL PLAN AND AN ELECTRICAL
 SUB-PERMIT FOR REVIEW; OR INDICATE ON THE PLAN THAT THE
 ELECTRICAL WILL BE DONE UNDER A SEPARATE PRIMARY
 PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER