Plan Review Details - Permit 15080344
Plan Review Stops For Permit 15080344
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-10 Cont ID  
Sent By kc Date 2015-11-10 Time   Rev Time 0.00
Received By   Date 2015-11-10 Time   Sent To I
Notes
2015-11-10 10:24:38MUST MAINTAIN A MINIMUM OF 2 EXITS FOR EACH FLOOR OF
 THE PARKING GARAGE PER THE FBC, SECTION 1021.1.2.
 NUMBER OF EXITS PER OCCUPANT LOAD SHALL BE PER THE FBC,
 SECTION 1021, TABLE 1021.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2015-10-13 Time   Rev Time 0.00
Received By   Date 2015-10-13 Time   Sent To I
Notes
2015-10-13 10:03:01CONSTRUCTION/OCCUPANCY SEPARATION PLAN FOR PHASE 1
 OCCUPANCY:
  
  
 1) PLEASE SUBMIT THE DIMENSIONS FOR ALL
 EGRESS/TEMPORARY EGRESS DOORS AT BARRIER WALLS.
  
 2) PLEASE INDICATE THE SQUARE FOOTAGE/OCCUPANT LOAD FOR
 EACH FLOOR.
  
 3) VERIFY THAT THERE ARE NO CONSTRUCTION EGRESS
 IMPEDAMENTS.
  
 4) ALL LIFE SAFETY AND ACCESSIBLE REQUIREMENT SHALL BE
 SATISFIED.
  
 5) THE BARRIER WALL AT STAIR ENCLOSURE #3 SHALL BE
 RATED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date 2015-08-12 Cont ID  
Sent By skennedy Date   Time 10:28 Rev Time  
Received By skennedy Date   Time   Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-27 Cont ID  
Sent By wjolin Date 2015-10-27 Time 15:38 Rev Time 0.00
Received By wjolin Date 2015-10-22 Time 10:59 Sent To  
Notes
2015-10-23 15:01:40705 NORTH OLIVE AVENUE - PHASED OCCUPANCY REQUEST
 TRACKING #15080344
 MASTER #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE DOORS WILL BE LOCKED AGAINST
 EGRESS UNTIL THE FIRE ALARM IS ACTIVATED. THIS
 ARRANGEMENT IS NOT PERMITTED BY THE FIRE CODE. PER
 SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS ARE
 PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 NOTE: ALL FIRE AND LIFE SAFETY SYSTEMS SHALL BE
 INSPECTED, TESTED AND APPROVED PRIOR TO OCCUPANCY. A
 "FIRE WATCH" IS NOT AN AVAILABLE OPTION FOR ALLOWING
 OCCUPANCY.
  
 JIM WALKER & WESLEY JOLIN
 FIRE MARSHAL'S OFFICE
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By wjolin Date 2015-08-26 Time 11:24 Rev Time 0.00
Received By wjolin Date 2015-08-26 Time 10:42 Sent To B
Notes
2015-08-26 11:24:29705 NORTH OLIVE AVENUE - PHASED OCCUPANCY REQUEST
 TRACKING #15080344
 MASTER #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE AND LIFE SAFETY SYSTEMS SHALL BE
 INSPECTED, TESTED AND APPROVED PRIOR TO OCCUPANCY. A
 "FIRE WATCH" IS NOT AN AVAILABLE OPTION FOR ALLOWING
 OCCUPANCY.
  
 PROVIDE AN ADDRESS ON THE PLANS.
  
 PLANS AFFECTING THE FIRE AND LIFE SAFETY DESIGN WILL
 NEED TO BE SIGNED/SEALED OR AT LEAST REVIEWED AND
 STAMPED BY THE DESIGN PROFESSIONAL ACCEPTING
 RESPONSIBILITY FOR THE MODIFIED DESIGN.
  
 STAIR #6 DISCHARGES INTO THE CONSTRUCTION STAGING AREA.
  
 FIRE ALARM CONTROL PANEL IS NOT LOCATED IN THE
 "COMPLETED" PORTION OF THE BUILDING BUT IS LOCATED IN
 THE HEART OF THE SECTOR B CONSTRUCTION ZONE. EXPLAIN
 HOW THE FIRE ALARM SYSTEM WIRING WILL BE PROTECTED AND
 THE INTEGRITY WILL BE MAINTAINED FOR THE WIRING THAT IS
 BEING ROUTED THROUGH THE CONSTRUCTION ZONE TO BE
 CONNECTED TO THE FACP.
  
 DETAILED DESCRIPTIONS AND PHASING DRAWINGS ARE NEEDED
 FOR THE FIRE ALARM AND FIRE SPRINKLER/PUMP SYSTEMS.
  
 TESTING OF THE FIRE ALARM SYSTEM IN SECTORS B & C WILL
 INITIATE THE GENERAL FIRE ALARM IN SECTOR A THAT MAY
 LAST FOR SEVERAL HOURS AND BE CONDUCTED OVER SEVERAL
 DAYS. HOW WILL RESIDENTS KNOW THE DIFFERENCE BETWEEN
 TEST ALARMS AND TRUE ALARMS?
  
 THE PLANS INDICATE THE BARRIER WALLS ARE TO HAVE
 SIGNAGE STATING, "NO ENTRY ALLOWED, CONSTRUCTION
 PERSONNEL ONLY." INDICATE HOW WILL THIS WILL BE
 REGULATED AND ENFORCED?
  
 INDICATE HOW FIRE DEPARTMENT VEHICLE ACCESS TO THE 20
 FOOT WIDE FIRE LANE WILL BE MAINTAINED ON EUCALYPTUS
 STREET AND 6TH STREET DURING CONSTRUCTION ACTVITIES
 WITH HALF THE BUILDING POTENTIALLY OCCUPIED AND THE
 OTHER HALF UNDER CONSTRUCTION.
  
 JIM WALKER & WESLEY JOLIN
 FIRE MARSHAL'S OFFICE
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2015-10-14 Time 13:08 Sent To FIRE
Notes
2015-11-02 15:29:2511/2 TO K CONRAD DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-13 Cont ID  
Sent By cpuell Date 2015-10-14 Time 13:08 Rev Time 0.00
Received By cpuell Date 2015-08-11 Time 10:27 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved