Plan Review Details - Permit 15080255
Plan Review Stops For Permit 15080255
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time   Rev Time 0.00
Received By jwitmer Date 2015-09-11 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-17 Cont ID  
Sent By jwitmer Date 2015-08-17 Time 16:54 Rev Time  
Received By jwitmer Date 2015-08-17 Time   Sent To  
Notes
2015-08-17 16:44:30BUILDING PLAN REVIEW
 REVISION: 15080255
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. AUG.17/2015
 ACTION: DENIED
  
 ROOF SUBMITTALS;
  
 1) FLAT ROOF:
 1A) THE ENGINEERING FROM FORENSIC ENGINEERING IS A COPY
 NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON
 ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE
 ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY
 NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS.
  
 1B) THE FORENSIC ENGINEERING SHEET WIND DESIGN CRITERIA
 IS 170 MPH AND EXPOSURE D. PLEASE REVIEW THE STRUCTURAL
 SHEET S6 THE WIND DESIGN
 IS 180 MPH, EXPOSURE C RISK CATEGORY III. PLEASE
 RE-CALCULATE THE PRESSURES AND ANCHORING TO THE CORRECT
 CRITERIA. 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION
 OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 2) SLOPED ROOFS METAL
 2A) THE ENGINEERING SHEET FROM GFA CARLOS MERCADO P.E.
 IS A COPY NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON
 ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE
 ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY
 NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS.
  
 2B) PLEASE NOT THE GFA ENGINEEREING INCLUDES METAL ROOF
 SYSTEMS FOR 2 BUILDINGS;
 1) CLUBHOUSE
 2) TOWER ROOF
  
 PLEASE NOTE THERE WILL BE (2) DESIGN CRITERIA REQUIRED.
 THE CLUBHOUSE IS DESIGNED TO 180 MPH EXPOSURE C
 BUILDING CATEGORY III, WHERE AS THE TOWER ROOF IS ONLY
 A BUILDING CATEGORY II THE WIND DESIGN AT 170 MPH.
 PLEASE ALSO NOTE THERE WILL BE 2 DIFFERENT MEAN ROOF
 HEIGHTS INVOLVED.
 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10. PLEASE RECALCULATE TO
 THE APPROPRIATE WIND DESIGN FOR EACH OF THE BUILDINGS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-11 Cont ID  
Sent By   Date 2015-09-11 Time   Rev Time 0.00
Received By lmarchan Date 2015-08-28 Time 10:26 Sent To  
Notes
2015-08-28 10:26:34RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-17 Cont ID  
Sent By jwitmer Date 2015-08-17 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2015-08-07 Time 15:09 Sent To  
Notes
2015-08-07 15:09:33JWITMER DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved