2015-08-13 15:03:06 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| |
| 1. DEFINE YOUR SCOPE OF WORK ON THE DRAWINGS FOR |
| APPROVAL. THE APPLICABLE NEC IN EFFECT IS THE 2011 |
| EDITION. |
| 2. FROM LOOKING AT THE ELECTRICAL RISER AS SHOWN IT |
| APPEARS THAT YOU HAVE TAPPED INTO THE 2/0 CU CONDUCTORS |
| TO FEED THE 60 AMP SUB PANEL. YOU SHALL SUBMIT A |
| CORRECTED AND SITE SPECIFIC RISER DIAGRAM. |
| 3. YOU SHALL SUBMIT AN ACCURATE CIRCUIT DIRECTORY AS |
| DESCRIBED IN NEC 408.4 FOR BOTH THE MAIN AND THE SUB |
| PANEL. |
| 4. YOU SHALL SUBMIT LOAD CALCS FOR THE SUB PANEL. |
| 5. FROM THE SUBMITTED DRAWING, IT APPEARS THAT THE |
| TANKLESS WATER HEATER IS CLOSER TO THE GAS METER THAN |
| THE MINIMUM 3' REQUIRED BY NFPA 54 SECTION 5.8.6.1 |
| 6. DUE TO THE ATTACHED GARAGE AND THE GAS APPLIANCES, |
| YOU SHALL COME INTO COMPLIANCE WITH FBC-R 315 CARBON |
| MONOXIDE DETECTORS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |