Plan Review Details - Permit 15080251
Plan Review Stops For Permit 15080251
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-31 Cont ID  
Sent By albarran Date 2015-08-31 Time 14:54 Rev Time 0.00
Received By albarran Date 2015-08-31 Time 13:43 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By albarran Date 2015-08-25 Time 10:09 Rev Time 0.00
Received By albarran Date 2015-08-25 Time 09:52 Sent To  
Notes
2015-08-26 16:33:228/26/15 - GC CAME BACK WITH INCORRECT DRAWINGS ONCE
 AGAIN. THIS TIME I LITERALLY DREW OUT FOR HIM THE RISER
 AS IT IS SUPPOSED TO APPEAR ON THE PLANS AND PIN
 POINTED THE VARIOUS LOADS AS THEY ARE TO APPEAR ON THE
 PANELS AND CALCS.
2015-08-25 11:28:57I MET WITH THE CONTRACTOR I BELIEVE I WAS ABLE TO
 EXPLAIN TO HIM WHAT WAS LACKING ON THE DRAWINGS. HE
 WILL CORRECT AND RESUBMIT.
2015-08-25 10:12:42THIS HAS ONCE AGAIN FAILED ELECTRICAL REVIEW WITH SOME
 OF THE CORRECTIONS PROPERLY ADDRESSED BUT OTHERS
 INCORRECTLY. I CALLED TO SPEAK WITH THE CONTRACTOR TO
 TRY TO EXPLAIN AND HE WILL MEET WITH ME THIS MORNING AT
 11:30.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By albarran Date 2015-08-13 Time 14:53 Rev Time 0.00
Received By albarran Date 2015-08-13 Time 14:16 Sent To I
Notes
2015-08-13 15:03:06PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. DEFINE YOUR SCOPE OF WORK ON THE DRAWINGS FOR
 APPROVAL. THE APPLICABLE NEC IN EFFECT IS THE 2011
 EDITION.
 2. FROM LOOKING AT THE ELECTRICAL RISER AS SHOWN IT
 APPEARS THAT YOU HAVE TAPPED INTO THE 2/0 CU CONDUCTORS
 TO FEED THE 60 AMP SUB PANEL. YOU SHALL SUBMIT A
 CORRECTED AND SITE SPECIFIC RISER DIAGRAM.
 3. YOU SHALL SUBMIT AN ACCURATE CIRCUIT DIRECTORY AS
 DESCRIBED IN NEC 408.4 FOR BOTH THE MAIN AND THE SUB
 PANEL.
 4. YOU SHALL SUBMIT LOAD CALCS FOR THE SUB PANEL.
 5. FROM THE SUBMITTED DRAWING, IT APPEARS THAT THE
 TANKLESS WATER HEATER IS CLOSER TO THE GAS METER THAN
 THE MINIMUM 3' REQUIRED BY NFPA 54 SECTION 5.8.6.1
 6. DUE TO THE ATTACHED GARAGE AND THE GAS APPLIANCES,
 YOU SHALL COME INTO COMPLIANCE WITH FBC-R 315 CARBON
 MONOXIDE DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-31 Cont ID  
Sent By MALBARRA Date 2015-08-31 Time 14:56 Rev Time 0.00
Received By albarran Date 2015-08-28 Time 09:00 Sent To  
Notes
2015-08-31 14:56:198/31/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "I". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-26 Cont ID  
Sent By albarran Date 2015-08-25 Time 12:40 Rev Time 0.00
Received By albarran Date 2015-08-21 Time 12:38 Sent To  
Notes
2015-08-21 12:38:51RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By albarran Date 2015-08-13 Time 15:03 Rev Time 0.00
Received By albarran Date 2015-08-07 Time 14:33 Sent To  
Notes
2015-08-13 15:04:418/13/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "I". MA
2015-08-07 14:33:51REVISION ROUTED TO DHAYES