Plan Review Details - Permit 15080218
Plan Review Stops For Permit 15080218
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-05 Cont ID  
Sent By shill Date 2015-12-05 Time 10:58 Rev Time 0.00
Received By shill Date 2015-12-05 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-20 Cont ID  
Sent By shill Date 2015-10-20 Time 14:32 Rev Time 0.00
Received By shill Date 2015-10-20 Time 14:11 Sent To  
Notes
2015-10-20 14:32:21****CORRECTIONS****
 REVISED 11/9/15 (SEE NEW COMMENT)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OPENING DIMENSIONS AND NOTES UNDER "GENERAL SCOPE OF
 WORK" ARE TOO SMALL TO BE LEGIBLE. INCREASE FONT SIZE
 FOR THESE ITEMS, FBC 107.
  
 2. REVISE THE INSTALLATION SCHEDULE AS FOLLOWS:
  
 A. SHUTTER MOUNTING CONNECTION TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS IN THE PRODUCT APPROVAL; FOR
 EXAMPLE, SEE SHEET 11. SECTIONS (CONNECTION TYPES) ARE
 NAMED 1(TOP), 1(BOTTOM), 2(TOP), 2(BOTTOM), ETC.
  
 B. IF INSTALLATION IS VERTICAL, SPANS SHOULD BE THE
 DIMENSION ANCHOR TO ANCHOR, SO SHOULD BE OPENING HEIGHT
 PLUS EDGE DISTANCE TOP AND BOTTOM. SPANS APPEAR TO
 CORRELATE WITH THE HORIZONTAL DIMENSION, THE WIDTH.
  
 WITHOUT THE CONNECTION TYPE AND SPAN, IT IS NOT
 POSSIBLE TO DETERMINE CODE COMPLIANCE.
  
 3. WHEN RESUBMITTING, REVISE THE APPLICATION TO BE
 CONSISTENT WITH THE SCOPE OF WORK STATED (STILL STATES
 WINDOW AND DOOR REPLACEMENT).
  
 4. WHEN RESUBMITTING, COLLATE TWO IDENTICAL SETS OF
 PERMIT DOCUMENTS FOR PERMIT ISSUANCE.
  
 ***NEW COMMENT***
  
 5. RESUBMITTAL FORM STATES THAT "EXISTING WINDOWS TO
 REMAIN." WINDOWS WERE REPLACED WITHOUT A PERMIT AND
 THEREFORE A CODE CASE WAS GENERATED. THE WINDOWS
 INSTALLED WITHOUT PERMIT REQUIRE A PERMIT. THEY ARE NOT
 CONSIDERED "EXISTING" AS THEY HAVE NOT BEEN PERMITTED
 AND INSPECTED AND THEY DO NOT COMPLY WITH FBC
 REQUIREMENTS (LACKING IMPACT PROTECTION).
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By shill Date 2015-08-26 Time 08:05 Rev Time 0.00
Received By shill Date 2015-08-26 Time 08:05 Sent To  
Notes
2015-08-26 08:27:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLANS PREPARED BY "DESIGNDRAFTING78" AND SEALED BY
 RICHARD BOYETTE, PE.
  
 1. SCOPE NOT CLEAR. APPLICATION IS FOR "REPLACE WINDOWS
 & DOORS." PRODUCT APPROVALS, REVIEWED BY ENGINEER OF
 RECORD, ARE FOR ROOF TILE AND ROOF TILE ADHESIVE. FLOOR
 PLAN DEMOLITION SHOWS ONE DOOR TO BE REPLACED. TWO
 WINDOWS ARE SHOWN AS BEING REPLACED WITH "24 S.H. CASE
 EGRESS." WHAT IS A S.H. CASE EGRESS?
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 WINDOWS. PLAN DOES NOT SHOW ANY ROOFING WORK.
  
 2. ONE WINDOW OPENING HAS A NOTE ON THE PLAN, "REPAIR
 SPALDING CONCRETE AROUND OPENING." SPALDING? REVISE
 PLAN TO CLARIFY AND PROVIDE A DETAIL / SPECIFICATION,
 FBC 107.
  
 3. REVISE PLAN TO DECLARE GOVERNING CODE, FS553, FBC
 107. CODE IS INCORRECT IN SEVERAL LOCATIONS ON THE
 PLAN.
  
 4. ENGINEER IS TO CLARIFY THE STATEMENT "ENGINEER
 CERTIFIES STRUCTURE COMPLIES WITH STRUCTURAL AND WIND
 LOAD REQUIREMENTS OF FBC 2010 RESIDENTIAL." PROVIDE A
 LETTER FROM THE ENGINEER WHICH EXPLAINS THIS STATEMENT.
 HOUSE WAS BUILT IN APPROXIMATELY 1949; WHAT TESTS OR
 STRUCTURAL ANALYSIS HAS THE ENGINEER PERFORMED TO
 JUSTIFY THIS STATEMENT ON THIS SIGNED AND SEALED PLAN
 (WHICH CONTRACTOR IS NOW REQUESTING TO BE APPROVED AND
 PUT ON FILE FOR PUBLIC RECORD)? FBC 107, FBC 5TH ED.
 RESIDENTIAL 301.
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-06 Cont ID  
Sent By cpuell Date 2015-12-06 Time 10:54 Rev Time 0.00
Received By cpuell Date 2015-12-02 Time 12:54 Sent To  
Notes
2015-12-02 12:54:30RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-20 Cont ID  
Sent By shill Date 2015-10-20 Time 14:32 Rev Time 0.00
Received By shill Date 2015-10-14 Time 13:18 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-26 Cont ID  
Sent By shill Date 2015-08-26 Time 08:27 Rev Time 0.00
Received By shill Date 2015-08-07 Time 09:38 Sent To  
Notes
2015-08-07 09:38:32BLDG <5K