Plan Review Details - Permit 15080156
Plan Review Stops For Permit 15080156
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-08-10 Cont ID  
Sent By jwitmer Date 2015-08-10 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2015-08-10 Time 13:55 Sent To  
Notes
2015-08-10 14:28:48BUILDING PROVISO:
 DOORS 100, 100A & 105 TO HAVE ELECTRO-MAGNETIC LOCKS
 SHOW COMPLIANCE WITH:
 2010 FBC-B 1008.1.9.8 ELECTROMAGNETICALLY LOCKED EGRESS
 DOORS.
 DOORS IN THE MEANS OF EGRESS IN BUILDINGS WITH AN
 OCCUPANCY IN GROUP A, B, E, M, R-1 OR R-2,
 AND DOORS TO TENANT SPACES IN GROUP A, B, E, M, R-1 OR
 R-2, SHALL BE PERMITTED TO BE
 ELECTROMAGNETICALLY LOCKED IF EQUIPPED WITH LISTED
 HARDWARE THAT INCORPORATES A BUILT-IN SWITCH
 AND MEET THE REQUIREMENTS BELOW:
  
 1. THE LISTED HARDWARE THAT IS AFFIXED TO THE DOOR LEAF
 HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
  
 2. THE LISTED HARDWARE IS CAPABLE OF BEING OPERATED
 WITH ONE HAND.
  
 3. OPERATION OF THE LISTED HARDWARE DIRECTLY INTERRUPTS
 THE POWER TO THE ELECTROMAGNETIC LOCK
 AND UNLOCKS THE DOOR IMMEDIATELY.
  
 4. LOSS OF POWER TO THE LISTED HARDWARE AUTOMATICALLY
 UNLOCKS THE DOOR.
  
 5. WHERE PANIC OR FIRE EXIT HARDWARE IS REQUIRED BY
 SECTION 1008.1.10, OPERATION OF THE LISTED
 PANIC OR FIRE EXIT HARDWARE ALSO RELEASES THE
 ELECTROMAGNETIC LOCK.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By skennedy Date 2015-08-31 Time 16:50 Rev Time 0.00
Received By skennedy Date 2015-08-31 Time 16:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-19 Time 08:45 Sent To  
Notes
2015-08-19 08:55:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ALL MAG LOCKS SHALL COMPLY WITH NFPA 101, CHAPTER 7.
  
 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
  
  
 PER SECTION 7.2.1.5.5, ELECTRICALLY CONTROLLED EGRESS
 DOOR ASSEMBLIES ARE PERMITTED IF EQUIPPED WITH APPROVED
 LISTED HARDWARE THAT INCORPORATES A BUILT-IN SWITCH AND
 THE FOLLOWING FIVE CRITERIA ARE MET:
 1. THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 2. THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION THAT
 IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 3. THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 4. OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 5. LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS
 THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE
 REQUIREMENTS OF FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT
 SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED IN ON THE
 EGRESS SIDE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By skennedy Date 2015-08-31 Time 16:51 Rev Time 0.00
Received By skennedy Date 2015-08-05 Time 16:30 Sent To  
Notes
2015-08-05 16:30:44B24

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-13 Cont ID  
Sent By gjohnson Date 2015-08-13 Time 14:43 Rev Time 0.00
Received By gjohnson Date 2015-08-13 Time 14:43 Sent To  
Notes
***NONE***