Plan Review Details - Permit 15080125
Plan Review Stops For Permit 15080125 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2015-08-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-08-19 |
Time |
18:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-08-19 |
Time |
18:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-08-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-08-17 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-08-17 |
Time |
10:21 |
Sent To |
|
|
Notes |
2015-08-17 10:21:46 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. | | CODE: FBC-5TH EDITION (2014) | | | | | | 1- RAS 117 CALCULATIONS SUBMITTED SHOW ENGINEER'S | | DIGITAL SIGNATURE. THIS IS NOT AN ELECTRONICALLY | | TRANSMITTED PROJECT. PROVIDE CALCULATIONS WITH | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | CHAPTER 471 F.S. | | | | 2- REVISE RAS 117 CALCULATIONS. ACCORDING TO SEC. | | 1609.4.1 THE BUILDING EXPOSURE IS "D" NOT "C". REVISE | | AS REQUIRED. OR PROVIDE COMPLETE WIND ANALYSIS FOR EACH | | WIND DIRECTION. SEC. 107.2.1.3 CITY AMENDMENTS. | | | | NOTE: ANY ROOF A/C EQUIPMENT REMOVAL REQUIRES SEPARATE | | PERMIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-08-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-08-05 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-08-05 |
Time |
16:03 |
Sent To |
|
|
Notes |
2015-08-05 17:37:59 | RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC-5TH EDITION (2014) | | | | 1- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105 OR ANSI | | /SPRI FX-1) AS REQUIRED BY NOTE #9 OF FLORIDA PRODUCT | | APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2 COPIES WITH | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | CHAPTER 471 F.S. | | | | 2- BASED ON THE RESULTS OF THE FASTENER WITHDRAWAL TEST | | REQUIRED BY ITEM #1 ABOVE, PROVIDE SIGNED AND SEALED | | RAS 117 (OR FM LPDS 1-29) AS REQUIRED BY NOTE #7 OF | | FLORIDA PRODUCT APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2 | | COPIES WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS | | REQUIRED BY CHAPTER 471 F.S. | | | | NOTE: ANY ROOF A/C EQUIPMENT REMOVAL REQUIRES SEPARATE | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-08-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-08-17 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-08-14 |
Time |
14:32 |
Sent To |
|
|
Notes |
2015-08-14 14:32:36 | RESUB ROUTED TO JGOMEZ |
|
|
|