Plan Review Details - Permit 15080117
Plan Review Stops For Permit 15080117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-25 Cont ID  
Sent By jgomez Date 2015-11-24 Time 17:30 Rev Time 0.00
Received By jgomez Date 2015-11-24 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-23 Cont ID  
Sent By jgomez Date 2015-09-23 Time 14:35 Rev Time 0.00
Received By jgomez Date 2015-09-23 Time 13:35 Sent To  
Notes
2015-09-23 14:38:30RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- BUILDING IS LOCATED IN FLOOD ZONE A5 WITH A BASE
 FLOOD ELEVATION OF 7'-0". ACCORDING TO ELEVATION
 CERTIFICATE ON CITY RECORDS THE FINISH FLOOR ELEVATION
 OF THE GARAGE IS 6.6'. THE FINISHED FLOOR ELEVATION
 NEEDS TO BE AT LEAST 6" ABOVE THE BASED FLOOR ELEVATION
 (7'-6"MIN.) OR THE CONSTRUCTION OF THE NEW ADDITION
 NEEDS TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. R322
 OF FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH
 ITEM #3(C) AND #3(D) BELOW.
  
 2- SHEET A-1:
 A) NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF
 EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) REVISE THE GENERAL NOTES: REFERENCE THE CURRENT CODE
 IN EFFECT 2014 NOT 2010. CHAPTER 553 F.S.
  
 C) SPECIFY FLOOD RESISTANT MATERIALS AS REQUIRED BY
 SEC. R322.1.8.
  
 D) PROVIDE COMPLETE INFORMATION FOR THE FLOOD VENTS
 SHOWING COMPLIANCE WITH SEC. R322.2.2. CHECK REQUIRED
 NUMBER OF VENTS PER SIDE, LOCATION AND SIZE OF VENTS
 REQUIRED. NOTE: COORDINATE WITH FLOOD VENT PRODUCT
 APPROVAL.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR FLOOD VENTS. NOTE: COORDINATE
 WITH ITEM #3(D) ABOVE.
  
 4- DESIGNER OF RECORD TO APPROVE FLOOD VENTS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE
 PLACE REVIEW STAMP ON THE COVER OF THE PRODUCT APPROVAL
 NOT ON THE BACK. THIS WILL FACILITATE THE SCANNING OF
 ALL DOCUMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected].

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 10:23 Rev Time 0.00
Received By albarran Date 2015-11-18 Time 09:46 Sent To B
Notes
2015-11-18 10:24:43APPROVED WITH THE FOLLOWING PROVISOS: ELECTRICAL
 PROVISO FOR PERMIT 15080117
  
 1. RECESSED LIGHTING SHALL COMPLY WITH FBC-E SECTION
 R402.4.4 RECESSED LIGHTING INSTALLED IN BUILDING?S
 THERMAL ENVELOPE SHALL IC RATED AND BE SEALED TO LIMIT
 AIR LEAKAGE BETWEEN CONDITIONED AND NON-CONDITIONED AIR
 SPACE.
 2. THE ADDITION OF AN ATTACHED GARAGE FORCES YOU TO
 COME INTO COMPLIANCE WITH THE FBC-R SECTION 314 & 315.
 YOU SHALL INSTALL INTER-CONNECTED SMOKE DETECTORS
 THROUGH-OUT THE ENTIRE AS IN NEW CONSTRUCTIONS. YOU
 SHALL FURTHER INSTALL A CARBON MONOXIDE DETECTOR WITH
 10? OF THE DOOR TO EACH AREA USED FOR SLEEPING.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 09:03 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 08:44 Sent To  
Notes
2015-09-17 09:04:35NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-25 Cont ID  
Sent By jgomez Date 2015-11-24 Time 08:01 Rev Time 0.00
Received By jgomez Date 2015-11-16 Time 11:44 Sent To  
Notes
2015-11-17 11:44:12RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-23 Cont ID  
Sent By jgomez Date 2015-09-23 Time 16:46 Rev Time 0.00
Received By jgomez Date 2015-08-05 Time 13:03 Sent To  
Notes
2015-08-21 09:40:39R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-11-24 Cont ID  
Sent By jgomez Date 2015-09-23 Time 14:38 Rev Time 0.00
Received By jgomez Date 2015-09-23 Time 14:38 Sent To  
Notes
2015-09-23 14:39:00NO IMPACT FEES. GARAGE AREA ADDITION ONLY. NO
 ADDITIONAL LIVING SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-09-23 Cont ID  
Sent By jgomez Date 2015-09-23 Time 16:45 Rev Time 0.00
Received By jgomez Date 2015-09-23 Time 16:45 Sent To  
Notes
2015-09-23 16:46:06NO MECHANICAL WORK.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2015-09-23 Cont ID  
Sent By jgomez Date 2015-09-23 Time 14:13 Rev Time 0.00
Received By jgomez Date 2015-09-23 Time 14:13 Sent To  
Notes
2015-09-23 14:13:37PLEASE E-MAIL SAMANTHA HILL WHEN PERMIT IS ISSUED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-08-18 Cont ID  
Sent By tklarge Date 2015-08-18 Time 04:37 Rev Time 0.00
Received By tklarge Date 2015-08-18 Time 04:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-09-23 Cont ID  
Sent By jgomez Date 2015-09-23 Time 16:44 Rev Time 0.00
Received By jgomez Date 2015-09-23 Time 16:44 Sent To  
Notes
2015-09-23 16:45:141- CEDAR SHAKES AND SHINGLES NOA 11-1018.06.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-18 Cont ID  
Sent By dkittred Date 2015-08-18 Time 15:17 Rev Time 0.00
Received By dkittred Date 2015-08-18 Time 09:10 Sent To  
Notes
2015-08-18 15:17:45ZBA 3306 - FRONT SETBACK VARIANCE GRANTED. DK