Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-18 Cont ID  
Sent By jwitmer Date 2015-12-18 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2015-12-18 Time 09:01 Sent To  
Notes
2015-12-18 14:07:10 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080007
 ADD: 4335 EASLEY DR.
 CONT: RALPH DELLA-PIETRA INC.
 TEL: (561)745-8555
 E-MAIL: JOSH @RDPCONST.COM
  
 2014 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION.
  
 3RD REVIEW
 DATE: FRI. DEC. 18/ 2015
  
 ACTION: PROVISO
  
 1) THIS BUILDING REQUIRES A RESIDENT INSPECTOR PER 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION; SECTION 110.39(7)
 EITHER BOLTED OR WELDED CONNECTIONS. ALL RESIDENT
 INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES WORK IS
 UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE BUILDING.
 SUCH INSPECTORS SHALL BE A REGISTERED ARCHITECT, OR
 ENGINEER, OR A PERSON LICENSED UNDER CHAPTER 468, PART
 XII, FLORIDA STATUTES,(BUILDING INSPECTOR). SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-17 Cont ID  
Sent By jwitmer Date 2015-11-17 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2015-11-16 Time 06:00 Sent To  
Notes
2015-11-17 09:32:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080007
 ADD: 4335 EASLEY DR.
 CONT: RALPH DELLA-PIETRA INC.
 TEL: (561)745-8555
 E-MAIL: JOSH @RDPCONST.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 17/ 2015
 ACTION: DENIED
  
 1) NOTE NOT ONLY IS THE PERMIT APPLICATION BUT THE
 PLANS AS WELL HAVE THE ADDRESS OF 4335 EASLEY DR. SINCE
 THE E-MAIL WAS SENT 1/23/2015 IN REGAURDS TO ADDRESSING
 AND ESTABLISHING NEW ADDRESSES, IT HAS BECOME A MAJOR
 PLAYER IN GETTING ADDRESSES UPDATED SO FIRE/RESCUE CAN
 IDENTIFY AND LOCATE FACILITIES QUICKLY FOR QUICK
 RESPONCE TIMES.
  
 THE NEW ADDRESS FOR THIS PROPOSED BUILING IS 6010
 RECLAIMED LAKES. EITHER LABELS CAN BE PLACED ON ALL
 PRINTED SHEETS WITH THE NEW ADDRESS OR NEW SHEETS
 PRINTED. THIS WILL BE UP TO THE DESIGNER OF RECORD AND
 OR CONTRACTOR TO DECIDE HOW PROCEDE. NOTE ALL DOCUMENTS
 WILL NEED TO BE UPDATED.
  
 2) COMPLIED. 12/03/2015 BECAUSE OF THE BOLTED AND
 WELDED CONNECTIONS OF THE STRUCTURAL STEEL PORTION OF
 THIS BUILDING, THE BUILDING DEPARTMENT WILL REQUIRE 3RD
 PARTY INSPECTION OF THE ELEMENTS, OTHERWISE A RESIDENT
 INSPECTOR WILL BE REQUIRED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES.
 PLEASE CONTACT KEN CONRAD FOR FURTHER INFORMATION:
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By jwitmer Date 2015-08-12 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2015-08-12 Time 06:30 Sent To  
Notes
2015-08-12 10:16:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080007
 ADD: 4335 EASLEY DR.
 CONT: RALPH DELLA-PIETRA INC.
 TEL: (561)745-8555
 E-MAIL: JOSH @RDPCONST.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 12/ 2015
 ACTION: DENIED
  
 1) SHEET LS1 & STRUCTURAL SHEET S-1 BOTH INDICATE THE
 PLANS WERE DEVELOPED UNDER THE 2010 FBC. PLEASE NOTE
 THE 5TH EDITION OF THE FLORIDA BUILDING CODE (2014 FBC)
 WAS ADOPTED STATEWIDE ON JUNE 30, 2015. PLEASE REVISE
 PLANS AND CODE SECTIONS.
  
 2) BUILDING PROVISO: BECAUSE OF THE BOLTED AND WELDED
 CONNECTIONS OF THE STRUCTURAL STEEL PORTION OF THIS
 BUILDING, THE BUILDING DEPARTMENT WILL REQUIRE 3RD
 PARTY INSPECTION OF THE ELEMENTS, OTHERWISE A RESIDENT
 INSPECTOR WILL BE REQUIRED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES.
 PLEASE CONTACT KEN CONRAD FOR FURTHER INFORMATION:
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) DISCREPANCY IN PLANS LS-1 VERSES S-2 AND THE ROOF
 HEIGHT 23 FT. VERSES 21 FT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) SHEET S-1 INDICATES THE MINIMUM SOILS BEARING
 PRESSURE OF 2,500 PSF. THE PLANS DO NOT INDICATE THAT A
 SOILS REPORT HAS BEEN COMPLETED. PLEASE PROVIDE SOILS
 REPORT PER: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) SHEET S-2 SHOWS THE PRESSURES FOR COMPONENTS &
 CLADDING IN WHAT IS ASSUMED VULT. NOTE ALL PRODUCT
 APPROVALS ARE IN VASD, PLEASE CONVERT PRESSURES INTO
 VASD TO COINCIDE WITH THE PRODUCT APPROVALS. 1609.3.1.
  
 6) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. EXTERIOR HINGED DOORS, OVERHEAD
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) PLEASE PROVIDE THE MANUFACTURERS SHOP DRAWINGS FOR
 THE ENGINEERED METAL BUILDING. PART OF THE MWFRS (MAIN
 WIND FORCE RESISSTING SYSTEM AS WELL AS COMPONENTS AND
 CLADDING. 2014 FBC-B 1609.6.3 / 1609.6.4.4.1.
  
 9) SHEET S-4:
  
 9A) SHEET S-4 VERSES S-7. SHEET S-4 SHOWS A FOUNDATION
 CUT SECTION THROUGH THE EXTERIOR BLOCK WALL, DETAIL #
 1/ S-7. SHEET S-12 SHOWS THE EXTERIOR BLOCK WALL WITH A
 STEM WALL FOUNDATION. SHEET S-7 DETAIL # 1 SHOWS THE
 INTERIOR BLOCK WALL AND THE NOTE BENEATH INDICATES THE
 WIDTH VARIES? 107.2.1.3 ADITIONAL INFORMATION IS
 REQUIRED.
  
 9B) SHEET S-4 THE UPPER LEFT CORNER OF THE STEEL
 UILDING THERE IS A NOTE THAT THE EXTERIOR WALLS ARE TO
 BE STEEL FRAMED WALLS. IT IS NOT CLEAR IF THESE ARE TO
 BE PART OF THE ENGINEERED BUILDING. SHEET A-7 SHOWS A
 WALL SECTION THROUGH THE EXTERIOR WALL WITH A
 HORIZONTAL GIRT SYSTEM AND WALL PANEL SYSTEM, BUT NO
 SECTION THROUGH THE WALL WHERE THERE ARE STEEL FRAMING
 MEMBERS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) SHEET S-12 SHOWS THE INSTALATION OF A BRIDGE CRANE.
 THERE IS NO DESIGN CRITERIA PLEASE REVIEW 2014 1607
 SECTION 13 FOR CRANE LOADS AND DESIGN.
  
 11) WITHIN THIS SUBMITTAL THERE WAS NO ENERGY
 SUBMITTALS, PLEASE PROVIDE COMPLIANCE WITH 2014
 FBC-ENERGY C401.2 APPLICATIONS.
  
 12) SHEET A-3 THERE IS A NOTE SEE SPECIFICATION SECTION
 13-34-19 PARAGRAPH 1.4.C.2 RATIONAL ANALYSIS
 REQUIREMENTS. PLEASE PROVIDE WHAT IS PERTAINS TOO? WITH
 NO SHOP DRAWINGS BEING SUBMITTED AND THE ABOVE
 STATEMENT UNKNOWN AT THIS TIME, IF THE METAL BUILDING
 IS GOING TO USE OTHER DESIGNS, AISI S100 (2014 FBC-B
 2211.4) OR AISI S210 (2014 FBC-B 2211.5) WE WILL NEED
 TO SEE COMPLIANCE WITH 2007 AISI D6.2.1A
 (A-G).
  
 13) SHEET A-3 INDICATES ROOF LEADERS, PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 1503.7 WITH THE DOWN SPOUTS
 DISCHARGING 1 FOOT FROM THE SIDEWALL OF THE BUILDING.
  
 14) SHEET A-4 INDICATES A AWNING, THIS REQUIRES A
 SEPARATE PERMIT. THERE IS NO WIND DESIGN CRITERIA FOR
 THIS AWNING. SEE 2014 FBC-B 3105.4 & 3105.5 FOR DESIGN
 CRITERIA.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-08 Cont ID  
Sent By albarran Date 2015-12-08 Time 13:47 Rev Time 0.00
Received By albarran Date 2015-12-08 Time 13:26 Sent To I
Notes
2015-12-08 13:48:42ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-30 Cont ID  
Sent By albarran Date 2015-09-30 Time 14:16 Rev Time 0.00
Received By albarran Date 2015-09-30 Time 13:34 Sent To  
Notes
2015-09-30 14:18:15PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. FIRE ALARM WORK SHALL BE UNDER A STAND-ALONE FIRE
 ALARM PERMIT.
 2. WAREHOUSE 101- MISSING AN EXIT LIGHT AT THE E. SIDE
 EXIT.
 3. WAREHOUSE 101- DOES NOT APPEAR TO HAVE ENOUGH
 EMERGENCY ILLUMINATION.
 4. BREAK ROOM 103- MISSING AN EMERGENCY LIGHT BY THE S.
 END, (OPERATIONS)
 5. MECH ROOM 107- MISSING AN EMERGENCY LIGHT.
 6. MECH ROOM 107- MISSING THE SERVICE OUTLET REQUIRED
 BY NEC 210.63
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
 RETURNED TO BIN FOR FURTHER REVIEWS. MA
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-09-04 Cont ID  
Sent By cranford Date 2015-09-04 Time 09:39 Rev Time 0.00
Received By cranford Date 2015-09-04 Time 09:28 Sent To  
Notes
2015-09-04 09:39:34ALSO SEE ENGINEERING DEVELOPMENT APPROVAL E15070003

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-14 Cont ID  
Sent By pleduc Date 2015-12-14 Time   Rev Time 0.00
Received By pleduc Date 2015-12-14 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-07 Cont ID  
Sent By pleduc Date 2015-08-07 Time   Rev Time 0.00
Received By pleduc Date 2015-08-07 Time 12:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-21 Cont ID  
Sent By gjohnson Date 2015-12-21 Time 14:19 Rev Time 0.00
Received By gjohnson Date 2015-12-21 Time 14:19 Sent To  
Notes
2015-12-11 09:25:58C31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-08 Cont ID  
Sent By albarran Date 2015-12-08 Time 13:49 Rev Time 0.00
Received By albarran Date 2015-11-10 Time 16:09 Sent To  
Notes
2015-12-08 13:50:4612/8/15 THOUGH ELECTRICAL PASSED, ALL OTHER TRADES
 REQUIRE ADDITIONAL CORRECTIONS. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "R". MA
2015-11-10 16:20:07C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2015-08-03 Time 09:49 Sent To  
Notes
2015-08-03 09:49:49C20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-18 Cont ID  
Sent By ccole Date 2015-12-18 Time 16:48 Rev Time 0.00
Received By ccole Date 2015-12-18 Time 16:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-11-17 Cont ID  
Sent By ccole Date 2015-11-17 Time 11:15 Rev Time 0.00
Received By ccole Date 2015-11-17 Time 11:15 Sent To  
Notes
2015-11-17 11:28:202ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080007
 11/17/15
  
 1) THE SUBMITTED ENERGY GAUGE SOFTWARE CALCULATION FORM
 506-2010 IS OUTDATED- SECTION C101.5.1 FBC-14 ENERGY
 CONSERVATION. PLEASE PROVIDE TWO CALCULATION FORMS
 USING THE UPDATED 2014 VERSION OF THE PROGRAM.
 2) PLEASE INDICATE THE R-VALUE OF THE DUCT INSULATION
 ON THE PLANS- TABLE C403.2.7.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By ccole Date 2015-08-07 Time 13:47 Rev Time 0.00
Received By ccole Date 2015-08-07 Time 13:47 Sent To  
Notes
2015-08-07 14:34:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080007
 8/7/15
  
 1) REFERENCE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: PROVIDE COOLING AND HEATING LOAD
 CALCULATIONS FOR THE NEW AC SYSTEMS IN ACCORDANCE WITH
 ACCA MANUAL N OR THE ACCA/ASHRAE STANDARD 183.
 2) REFERENCE SECTION C101.3 FBC-14 ENERGY CONSERVATION:
 THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH
 CHAPTER 4 FBC-14 ENERGY CONSERVATION. PLEASE SUBMIT TWO
 COMPLETED EFFICIENCY COMPLIANCE FORMS USING FLORIDA
 BUILDING COMMISSION SOFTWARE.
 3) SHEET M-3: PROVIDE UPDATED VENTILATION CALCULATIONS
 USING EITHER TABLE 403.3 FBC-14 MECHANICAL, OR ASHRAE
 62- 2010. PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES
 THE REQUIRED O/A CFM'S AND THE PROVIDED O/A CFM'S.
 4) SHEET M-5: THE DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN THE RETURN AIR DUCT- SECTION 606.2.1 FBC-14
 MECHANICAL.
 5) PROVIDE TWO COPIES OF A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE GREENHECK LOUVERS PER FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/
 2010.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-12-15 Cont ID  
Sent By gjohnson Date 2015-12-15 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2015-12-15 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-11-19 Cont ID  
Sent By gjohnson Date 2015-11-19 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2015-11-18 Time 13:25 Sent To E
Notes
2015-11-18 13:32:562ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE CALCULATION FOR SIZING THE OIL
 SEPARATOR PROVIDED BY THE MANUFACTURE.YOU CAN CONTACT
 SCHIER REP. LEE SCHNEEWEISS 800-538-4792 HE WILL BE
 ABLE TO HELP YOU.
 2. SEPARATE PERMIT REQUIRED FOR IRRIGATION.IRRIGATION
 PLANS APPROVED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By gjohnson Date 2015-08-14 Time 12:37 Rev Time 0.00
Received By gjohnson Date 2015-08-13 Time 15:29 Sent To  
Notes
2015-08-14 12:59:31 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
 COMMENTS:
 1. SHEET A-8 RESTROOM DETAIL 1-2 SHOW INSTALLATION
 HIGHT MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 TO COMPLY WITH FBC ACC SEC.609.4
 2. SHEET P-2 PLEASE PROVIDE CALCULATION FOR SIZING OIL
 SEPARATOR.
 TO COMPLY WITH FBCP 10003.4.2.2
 3. PLEASE PROVIDE INSTILLATION GUIDE FOR SCHIER MODEL
 OS-75.
 TO COMPLYWITH WPB AMENDMENTS TO FBC 2010 SEC 107.2.1.3

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-11-17 Cont ID  
Sent By jwitmer Date 2015-11-17 Time   Rev Time 0.00
Received By jwitmer Date 2015-11-17 Time   Sent To  
Notes
2015-12-07 08:22:21STRUCTURAL ROOF PANELS C.G.C. CAN APPLY FOR THIS TYPE
 OF PERMIT. DOUG HARVEY & MYSELF CALLED STATE , CILB
 PAUL DIVICIAO. $80.00 SUB-PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time   Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time   Sent To  
Notes
2015-08-12 10:17:58NO ROOFING APPROVALS WERE SUBMITTED THIS REVIEW CYCLE.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-20 Cont ID  
Sent By jroach Date 2015-08-20 Time 14:19 Rev Time 0.00
Received By jroach Date 2015-08-20 Time 14:02 Sent To  
Notes
2015-08-20 14:20:07ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.20.2015
 PERMIT NO.: 15080007
 ADDRESS: 4335 EASLEY DRIVE
 CONTRACTOR/CONTACT: JOSH DELLA-PIETRA
 TELEPHONE NO.: 561.745.8555
 SCOPE OF REVIEW: WAREHOUSE WITH OFFICE SPACE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 THE LANDSCAPING. SUCH APPLICATION SHALL BE ACCOMPANIED
 WITH A CERTIFIED COST ESTIMATE (LABOR + MATERIAL).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved