Plan Review Details - Permit 15071223
Plan Review Stops For Permit 15071223
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By Mgonzale Date 2015-09-21 Time   Rev Time 1.00
Received By mgonzale Date 2015-09-21 Time   Sent To FIRE
Notes
2015-09-21 14:44:39PASSED WITH PROVISO:
  
 #1 IT IS UNDERSTOOD THAT PRIOR BACFKLOW WAS VERTICALLY;
 HOWEVER THE PROPOSED BACFLOW MUST BE INSTALLED
 HORIZONTAL WHERE POSSIBLE. CONTACT UTILITY CUSTOMER
 SERVICE FOR INSPECTION.
  
 #2 DUE TO THE LOCATION OF THE BACKFLOW PLEASE RECORD IN
 PALM BEACH COUNTY COURTS THE BACKFLOW ASSEMBLY ACCESS
 COVENANT PRIOR TO FINAL INSPECTION PROVIDE A COPY TO
 CITY OF WEST PALM BEACH.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-08-08 Cont ID  
Sent By mGONZALE Date 2015-08-07 Time   Rev Time 1.00
Received By mgonzale Date 2015-08-07 Time   Sent To M
Notes
2015-08-08 18:42:12#1 EXIST DCDA MUST BE APPROVED FOR LOCATION FROM CITY
 OF WPB UTILITIES CUSTOMER SERVICE.
  
 #2 EXIST. BACFLOW MUST BE IN HORIZONTAL CONFIGURATION.
  
 #3 EXIST BACFLOW MUST BE ACCESSIBLE TO CITY OF WPB
 UTILITIES CUSTOMER SERVICE.
  
 #4 SUBMIT A SPECIFICATION SHEET FOR DCDA FOR APPROVAL
 TO [email protected] CC. [email protected]
 REFERENCE YOUR PERMIT #. ALTHOUGH I UNDERSTAND THIS IS
 THE OLD LOCATION OF THE DCDA
 PLEASE CONTACT STEPHEN HUNTER (561) 644-7329 CITY OF
 WPB UTILITIES CUSTOMER SERVICE
 TO MAKE A SITE VISIT AND MAKE SURE ALL THE COMMENTS ARE
 ADDRESSED,
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-30 Cont ID  
Sent By wjolin Date 2015-09-30 Time 11:24 Rev Time 0.00
Received By wjolin Date 2015-09-30 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-05 Cont ID  
Sent By wjolin Date 2015-08-05 Time 10:47 Rev Time 0.00
Received By wjolin Date 2015-08-05 Time 09:37 Sent To ENG
Notes
2015-08-05 10:32:58114 SOUTH OLIVE AVENUE
 PERMIT #15071223
 REVOKED PERMIT #14040237
 MASTER #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE BACKFLOW PREVENTER (INDICATING CONTROL VALVES)
 SHALL BE LOCATED IN A FIRE RATED ENCLOSURE ACCESSIBLE
 FROM THE EXTERIOR OR IN ACCORDANCE WITH NFPA 24 SECTION
 6.2.1.
  
 PROVIDE FIRE DEPARTMENT CONNECTION ALONG OLIVE AVENUE.
 THE CURRENT ALLEY PLACEMENT IS NOT DESIRABLE AND IS TOO
 GREAT A DISTANCE FROM THE NEAREST FIRE HYDRANT. PER
 NFPA 14 SECTION 6.4.5.1 FIRE DEPARTMENT CONNECTIONS
 SHALL BE VISIBLE AND RECOGNIZABLE FROM THE STREET OR
 NEAREST POINT OF FIRE DEPARTMENT APPARATUS
 ACCESSIBILITY OR ON THE STREET SIDE OF BUILDINGS.
 CONNECTIONS SHALL BE LOCATED NOT MORE THAN 100 FEET
 FROM THE NEAREST FIRE HYDRANT CONNECTED TO AN APPROVED
 WATER SUPPLY.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 CONFIRM THE RESTROOM STALL PARTITIONS ARE NOT SPRINKLER
 SPRAY OBSTRUCTIONS PER NFPA 13. ADDITIONAL SPRINKLERS
 MAY BE REQUIRED.
  
 ***NOTE: A SEPARATE PERMIT IS NEEDED FOR THE
 UNDERGROUND FIRE LINE (THIS MAIN IS NOT EXISTING)***
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-22 Cont ID  
Sent By lmarchan Date 2015-09-21 Time 10:43 Rev Time 0.00
Received By lmarchan Date 2015-08-18 Time 15:23 Sent To  
Notes
2015-08-18 15:23:59ENGINEERING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-11 Cont ID  
Sent By ccole Date 2015-08-11 Time 12:07 Rev Time  
Received By ccole Date 2015-07-31 Time   Sent To  
Notes
2015-07-31 12:33:03FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-11 Cont ID  
Sent By mgonzale Date 2015-08-08 Time 18:54 Rev Time 0.00
Received By ccole Date 2015-08-11 Time 12:07 Sent To  
Notes
***NONE***