Plan Review Details - Permit 15071167
Plan Review Stops For Permit 15071167
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-05 Cont ID  
Sent By rmcdouga Date 2015-08-05 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2015-08-05 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By rmcdouga Date 2015-07-30 Time 11:08 Rev Time 0.00
Received By rmcdouga Date 2015-07-30 Time 11:08 Sent To  
Notes
2015-07-30 11:09:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A DIAGRAM THAT SHOWS THE
 DIMENSIONS OF THE SLOPED AND FLAT ROOF AREAS THAT ARE
 TO BE RE-ROOFED. FBC 107.2.1
  
 2) SPECIFY THE ROOF SLOPE AND THE MEAN ROOF HEIGHT. FBC
 107.2.1
  
 3) THE ROOF SYSTEM THAT WAS SELECTED FOR THE FLAT ROOF
 ON PAGE 8 OF NOA NO. 12-0703.06 HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR ALL OF
 THE ROOF ZONES AND REQUIRES ENHANCED FASTENING AS
 ALLOWED BY LIMITATION #7 ON PAGE 10 OF THE NOA. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN ACCORDANCE WITH LIMITATION #7.
 FBC 107.2.1.3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-05 Cont ID  
Sent By rmcdouga Date 2015-08-05 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 08:32 Sent To  
Notes
2015-08-04 08:32:34RESUB ROUTED TO RMCDOUGAL