Plan Review Details - Permit 15071145
Plan Review Stops For Permit 15071145
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By jwitmer Date 2015-08-07 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2015-08-07 Time 07:17 Sent To  
Notes
2015-08-20 09:35:13ON SKENNEDY'S DESK
2015-08-07 08:12:48BUILDING PLAN REVIEW
 W. P. B. REVISION: 15071145
 W. P. B. PERMIT: 15010404
 ADD: 255 EVERNIA ST. UNIT MU3/1003
 CONT: BLUEWATER BUILDERS
 TEL: (561)373-2053
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 07/2015
 ACTION: DENIED
  
 1) PLEASE SEE SHEET M5.1 DETAIL # 1 SIDE WALL MOUNT A/C
 CONDENSER MOUNT AND BRAKET. THE PLANS INDICATE TO REFER
 TO MIAMI TECH ENGINEERING SHEET TO BE SEALED BY A
 REGISTERED FLORIDA P. E. THE MIAMI TECH ENGINEERING WAS
 NOT SUBMITTED. MAY REQUIRE PRODUCT APPROVAL IF THIS
 UNIT IS NOT A CUSTOM DESIGN AND WOULD NEED TO COMPLY
 WITH:
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 2) WITH NOT HAVING THE MIAMI TECH ENGINEERED SHEETS IT
 IS UNKNOWN IF THEY INCLUDE THE ATTACHMENT ANCHORS FOR
 THE STAND TO THE WALL. 2010 FBC- ADMINISTRATION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 2010
 FBC-B 1609.6.4. 4.1. COMPONENTS & CLADDING .
  
 3) THE PLANS ALSO FAIL TO SHOW THE CONNECTION FROM THE
 COMPRESSOR STAND TO THE COMPRESSOR. 2010 FBC-
 ADMINISTRATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. 2010 FBC-B 1609.6.4. 4.1. COMPONENTS &
 CLADDING .
  
 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-15 Cont ID  
Sent By skennedy Date 2015-08-21 Time 16:58 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By skennedy Date 2015-09-15 Time 16:58 Rev Time 0.00
Received By skennedy Date 2015-07-29 Time 15:33 Sent To  
Notes
2015-07-29 15:34:08B34

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By ccole Date 2015-08-06 Time 11:49 Rev Time 0.00
Received By ccole Date 2015-08-06 Time 11:31 Sent To  
Notes
2015-08-06 11:59:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) AS NOTED IN DETAIL NO. 1 ON SHEET M5.1, PROVIDE
 SIGNED AND SEALED ENGINEERED STRUCTURAL DETAILS FOR
 INSTALLATION OF THE MIAMI TECH CU BRACKET, AND
 ATTACHMENT OF THE CU TO THE BRACKET- SECTION 301.12
 FBC-10 MECHANICAL.
 2) IN ACCORDANCE WITH FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3, PROVIDE TWO COPIES OF A VALID
 FLORIDA PRODUCT APPROVAL OR A MIAMI DADE NOA FOR THE
 BRACKLET WITH REVIEW AND APPROVAL STAMPS SIGNED BY THE
 ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By gjohnson Date 2015-08-06 Time 07:50 Rev Time 0.00
Received By gjohnson Date 2015-08-06 Time 07:50 Sent To  
Notes
2015-08-06 07:57:291ST REVIEW FBCP 2010
  
 COMENTS
  
 1.PLEASE CLARIFY REVISIONS ON PLUMBING PER
 WPB AMENDMENTS TO THEFBC SEC. 107.2.1
  
 2. AAV ARE NOT ALLOWED BELOW 4TH FLOOR BRANCH INTERVAL
 PER
 FBCP 917.3.2