2015-08-20 09:35:13 | ON SKENNEDY'S DESK |
2015-08-07 08:12:48 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15071145 |
| W. P. B. PERMIT: 15010404 |
| ADD: 255 EVERNIA ST. UNIT MU3/1003 |
| CONT: BLUEWATER BUILDERS |
| TEL: (561)373-2053 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. AUGUST 07/2015 |
| ACTION: DENIED |
| |
| 1) PLEASE SEE SHEET M5.1 DETAIL # 1 SIDE WALL MOUNT A/C |
| CONDENSER MOUNT AND BRAKET. THE PLANS INDICATE TO REFER |
| TO MIAMI TECH ENGINEERING SHEET TO BE SEALED BY A |
| REGISTERED FLORIDA P. E. THE MIAMI TECH ENGINEERING WAS |
| NOT SUBMITTED. MAY REQUIRE PRODUCT APPROVAL IF THIS |
| UNIT IS NOT A CUSTOM DESIGN AND WOULD NEED TO COMPLY |
| WITH: |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31) (G) PRE-ENGINEERED A/C STANDS |
| |
| 2) WITH NOT HAVING THE MIAMI TECH ENGINEERED SHEETS IT |
| IS UNKNOWN IF THEY INCLUDE THE ATTACHMENT ANCHORS FOR |
| THE STAND TO THE WALL. 2010 FBC- ADMINISTRATION. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 2010 |
| FBC-B 1609.6.4. 4.1. COMPONENTS & CLADDING . |
| |
| 3) THE PLANS ALSO FAIL TO SHOW THE CONNECTION FROM THE |
| COMPRESSOR STAND TO THE COMPRESSOR. 2010 FBC- |
| ADMINISTRATION. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. 2010 FBC-B 1609.6.4. 4.1. COMPONENTS & |
| CLADDING . |
| |
| 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA: |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |