Plan Review Details - Permit 15071116
Plan Review Stops For Permit 15071116
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-08-06 Cont ID  
Sent By jwitmer Date 2015-08-06 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2015-08-06 Time 13:24 Sent To  
Notes
2015-08-06 14:13:35BUILDING PROVISO:
 SHEET A-5 DETAIL # 2 THE MICROWAVE MUST MEET:
 2014 FBC-ACCESSIBILITY CODE:
 309 OPERABLE PARTS
 1) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
  
 2) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 3) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-24 Cont ID  
Sent By skennedy Date 2015-08-24 Time 08:16 Rev Time 0.00
Received By skennedy Date 2015-08-24 Time 08:16 Sent To  
Notes
2015-08-24 08:17:33DATA & PHONE, OK TO ISSUE AS L/V ELEC SUB PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-24 Cont ID  
Sent By skennedy Date 2015-08-24 Time 08:09 Rev Time 0.00
Received By skennedy Date 2015-08-24 Time 08:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-30 Cont ID  
Sent By scaldero Date 2015-07-30 Time 16:57 Rev Time 0.00
Received By scaldero Date 2015-07-30 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 15:46 Rev Time 0.00
Received By ccole Date 2015-08-26 Time 15:10 Sent To  
Notes
2015-08-26 15:10:08RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-24 Cont ID  
Sent By skennedy Date 2015-08-24 Time 08:09 Rev Time 0.00
Received By skennedy Date 2015-07-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 15:46 Rev Time 0.00
Received By ccole Date 2015-08-26 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By ccole Date 2015-07-30 Time 15:59 Rev Time 0.00
Received By ccole Date 2015-07-30 Time 15:59 Sent To  
Notes
2015-07-30 16:24:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071116
 7/30/15
  
 1) SHEET M.2: REVISE THE O/A CALCULATIONS IN ACCORDANCE
 WITH SECTION 809.2 ALTERED SYSTEMS FBC-14 EXISTING
 BUILDING:
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 A) PLEASE NOTE THE CALCULATION TABLE ON THE PLAN IS
 REFERENCING THE OUTDATED 2010 FLORIDA MECHANICAL CODE.
 THE 2014 FLORIDA BUILDING CODES 5TH EDITION WENT INTO
 EFFECT 6/30/15
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-08 Cont ID  
Sent By tklarge Date 2015-08-08 Time 06:43 Rev Time 0.00
Received By tklarge Date 2015-08-08 Time 06:26 Sent To  
Notes
2015-08-20 09:36:28ON SKENNEDY'S DESK