Plan Review Details - Permit 15071104
Plan Review Stops For Permit 15071104
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-08-06 Cont ID  
Sent By jwitmer Date 2015-08-06 Time 11:37 Rev Time  
Received By jwitmer Date 2015-08-06 Time 08:40 Sent To  
Notes
2015-08-06 11:37:42BUILDING PROVISO:
 SHEET A-7 DETAIL # 1 MICROWAVE MUST MEET:
 2014 FBC-ACCESSIBILITY CODE:
 309 OPERABLE PARTS
 309.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL
 BE 5 POUNDS (22.2 N) MAXIMUM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 14:43 Rev Time 0.00
Received By skennedy Date 2015-08-21 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-30 Cont ID  
Sent By scaldero Date 2015-07-30 Time 16:57 Rev Time 0.00
Received By scaldero Date 2015-07-30 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-02 Cont ID  
Sent By ccole Date 2015-09-02 Time 10:27 Rev Time 0.00
Received By ccole Date 2015-09-01 Time 12:42 Sent To  
Notes
2015-09-01 12:42:33RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 14:44 Rev Time 0.00
Received By skennedy Date 2015-07-28 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-02 Cont ID  
Sent By ccole Date 2015-09-02 Time 10:27 Rev Time 0.00
Received By ccole Date 2015-09-02 Time 10:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By ccole Date 2015-08-18 Time 09:27 Rev Time 0.00
Received By ccole Date 2015-08-18 Time 09:27 Sent To  
Notes
2015-08-20 09:37:35ON SKENNEDY'S DESK
2015-08-18 09:34:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071104
  
 1) SHEET M-1: THE OUTSIDE AIR CALCULATION INDICATES AHU
 1-4, HOWEVER THE PLANS AND EQUIPMENT SCHEDULE INDICATE
 WCHP'S 1-5: PLEASE CLARIFY AND UPDATE THE ASHRAE 62.1
 REFERENCE TO THE CURRENT 2010 STANDARD IN EFFECT.
 2) REFER TO SECTION 809. FBC-14 EXISTING BUILDING CODE:
 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.1. PLEASE REVISE THE PLANS TRO
 SHOW COMPLIANCE.
 3) SUBMIT PRODUCT CUT SHEETS FOR THE STAINLESS STEEL
 HEAT PUMP WATER HOSES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-08 Cont ID  
Sent By tklarge Date 2015-08-08 Time 06:26 Rev Time 0.00
Received By tklarge Date 2015-08-08 Time 06:06 Sent To  
Notes
***NONE***