Plan Review Details - Permit 15071078
Plan Review Stops For Permit 15071078
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-09-18 Cont ID  
Sent By albarran Date 2015-09-18 Time 11:15 Rev Time 0.00
Received By albarran Date 2015-09-18 Time 10:31 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-08-24 Cont ID  
Sent By albarran Date 2015-08-24 Time 18:44 Rev Time 0.00
Received By albarran Date 2015-08-24 Time 18:34 Sent To  
Notes
2015-08-24 19:18:30IT APPEARS THAT THE EC DID NOT UNDERSTAND WHAT WAS
 REQUIRED OF HIM FOR A PROPER SUBMITTAL. I CALLED HIM
 AND EXPLAINED IN SPANISH WHAT WAS REQUIRED. I TOLD HIM
 THAT THE NEMA 14-50 RECEPTACLE REQUIRES A GROUNDED
 CONDUCTOR (NEUTRAL). HE ARGUED THAT THE EQUIPMENT DID
 NOT REQUIRE A NEUTRAL. REGARDLESS THE PROPOSED DEVICE
 REQUIRES A NEUTRAL THEN IF NO NEUTRAL IS REQUIRED
 CHANGE THE RECEPTACLE TYPE. I ALSO TOLD HIM IN SPANISH
 THAT I WAS ASKING FOR SPECS ON THE DEVICE BEING
 INSTALLED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-20 Cont ID  
Sent By albarran Date 2015-08-20 Time 18:19 Rev Time 0.00
Received By albarran Date 2015-08-20 Time 17:50 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-03 Cont ID  
Sent By albarran Date 2015-08-03 Time 18:31 Rev Time 0.00
Received By albarran Date 2015-08-03 Time 18:25 Sent To I
Notes
2015-08-03 18:35:43PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL SUBMIT TWO SET OF DRAWINGS
 2. YOU SHALL DECRIBED YOUR SCOPE OF WORK ON THE
 DRAWINGS
 3. PROVIDE LOAD CALCS TO ASCERTAIN CAPACITY FOR THESE
 DEVICES.
 4. YOU SHALL INDICATE HOW THESE DEVICES ARE BEING
 WIRED.
 5. SHOW/INDICATE WHERE THE SOURCE OF POWER AND
 DISCONNECT FOR THESE OUTLET WILL BE.
 6. A SIMPLE WIRING SKETCH OF THE PROPOSED INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-09-18 Cont ID  
Sent By albarran Date 2015-09-18 Time 11:15 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-09-18 11:17:249/18/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "A". MA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-24 Cont ID  
Sent By albarran Date 2015-08-24 Time 19:18 Rev Time 0.00
Received By albarran Date 2015-08-24 Time 13:33 Sent To  
Notes
2015-08-24 19:22:398/24/15 - AFTER A TELEPHONE CONVERSATION W/THE EC HE
 FINALLY CAME TO UNDERSTAND WHAT I S REQUIRED.
 CONTRACTOR NOTIFIED OVER THE PHONE AND VIA EMAIL. SENT
 TO SMALL DENIED BIN "A". MA
2015-08-24 13:34:07RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-20 Cont ID  
Sent By albarran Date 2015-08-20 Time 18:29 Rev Time 0.00
Received By albarran Date 2015-08-20 Time 09:34 Sent To  
Notes
2015-08-20 18:30:318/20/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA
2015-08-20 09:35:08RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By albarran Date 2015-08-03 Time 18:37 Rev Time 0.00
Received By albarran Date 2015-07-28 Time 16:31 Sent To  
Notes
2015-08-03 18:38:318/3/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA
2015-07-28 16:32:08ELEC -$5000