Plan Review Details - Permit 15071043
Plan Review Stops For Permit 15071043
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By jwitmer Date 2015-10-29 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2015-10-29 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-14 Cont ID  
Sent By jwitmer Date 2015-10-14 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2015-10-14 Time 12:21 Sent To  
Notes
2015-10-14 14:48:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15071043
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: (561)236-7052 / (954)444-8062
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
  
 1ST REVIEW
 DATE: TUES. AUG. 11/2015
 ACTION: DENIED
  
 1-12) COMPLIED.
  
 13) NEW COMMENT, DEALS WITH THE MINIMUM ELEMENTS FOR
 PLAN REVIEW:107.3.5.1.1. MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGSCOMMERCIAL BUILDINGS.
 (5) 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 FLORIDA ADMINISTRATIVE CODE: FIRE SPRINKLERS
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
  
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
  
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE: (A-M).
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By jwitmer Date 2015-08-12 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2015-08-10 Time 08:10 Sent To  
Notes
2015-08-12 14:09:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15071043
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: (561)236-7052 / (954)444-8062
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
  
 1ST REVIEW
 DATE: TUES. AUG. 11/2015
 ACTION: DENIED
  
 1) THERE IS NO CODE ANALYSIS ON EITHER THE PHASING PLAN
 AE002 NOR ANY OF THE LIFE SAFETY PLANS LS 01, LS01M OR
 LS 03 PROVIDING HOW CODE COMPLIANCE IS TO BE ACHIEVED.
 THE MEETING HELD JUNE 09/2015 WENT INTO GREAT LENGTH
 ALLOWANCES AND OR EXCEPTIONS THE DESIGNER OF RECORD
 WOULD LIKE THE CITY TO CONSIDER, BUT THERE HAS BEEN NO
 FORMAL (WRITTEN) REQUEST TO THE BUILDING OFFICIAL UNDER
 THE 2014 FLORIDA BUILDING CODE, CHAPTER 1 (A) 104.11
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY
 DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY.
  
 [A] 104.11.1 RESEARCH REPORTS.
 SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN THE
 APPROVAL OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY
 PROVIDED FOR IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
  
 [A] 104.11.2 TESTS.
 WHENEVER THERE IS INSUFFICIENT EVIDENCE OF COMPLIANCE
 WITH THE PROVISIONS OF THIS CODE, OR EVIDENCE THAT A
 MATERIAL OR METHOD DOES NOT CONFORM TO THE REQUIREMENTS
 OF THIS CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE BUILDING OFFICIAL
 SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS EVIDENCE
 OF COMPLIANCE TO BE MADE AT NO EXPENSE TO THE
 JURISDICTION. TEST METHODS SHALL BE AS SPECIFIED IN
 THIS CODE OR BY OTHER RECOGNIZED TEST STANDARDS. IN THE
 ABSENCE OF RECOGNIZED AND ACCEPTED TEST METHODS, THE
 BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES.
 TESTS SHALL BE PERFORMED BY AN APPROVED AGENCY. REPORTS
 OF SUCH TESTS SHALL BE RETAINED BY THE BUILDING
 OFFICIAL FOR THE PERIOD REQUIRED FOR RETENTION OF
 PUBLIC RECORDS.
  
 2) THROUGHOUT THE PLANS ARCHITECTURAL AND STRUCTURAL
 PLANS THERE IS MENTION THAT THE PLANS HAVE BEEN
 DESIGNED TO THE 2012 IBC. PLEASE MAKE CORRECTION THAT
 ON JUNE 30, 2015 THE 5TH EDITION OF THE FLORIDA
 BUILDING CODE OR THE 2014 FBC WAS ADOPTED STATEWIDE.
 PLEASE MAKE CORRECTIONS. EXAMPLE UNDER THE 2014 FBC-B
 THERE IS NO SECTION 1704. RESERVED. SPECIAL
 INSPECTIONS.
  
 3) WITH THE STRUCTURAL RENOVATION AND ADDITION THIS
 BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4) THERE ARE SEVERAL REFERENCES TO THE 2012 IBC PLEASE
 BE AWARE THAT THE STATE OF FLORIDA IS UNDER THE 5TH
 EDITION OF THE FLORIDA BUILDING CODE, OR THE 2014 FBC.
 THE CURRENT EDITION OF THIS CODE WAS ADOPTED STATEWIDE
 JUNE 30/ 2015. PLEASE UPDATE CODE.
  
 5) THE SCOPE OF THIS PROJECT IS NOT CLEAR AS TO WHAT
 PHASES OF THE PROJECT IS REPRESENTED WITHIN THE PERMIT
 APPLICATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED TO BE ABLE TO DO A THOROUGH REVIEW.
  
 6) SHEET 043-SE-002 FOUNDATION INDICATES THERE WAS A
 SOILS INVESTIGATION COMPLETED, PLEASE SUBMIT THE REPORT
 COMPILED BY ARDAMAN & ASSOCIATED PHASE 1 EXPANSION.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS.
  
 7) SHEET 004-SE-003 STRUCTURAL OBSERVATION IS AGAIN
 REFERENCE THE 2012 IBC SECTION 1704. 2014 FBC-B
 RESERVED.
  
 8) SHEET 034-AE-801 THE DOOR SCHEDULE INDICATES NEW
 EXTERIOR DOORS AND SHEET 035-AE-811 INDICATES NEW
 STOREFRONT GLAZING SYSTEM. NOTE THE CONTRACTOR HAS NOT
 SUBMITTED ANY PRODUCT APPROVALS FOR THESE ITEMS. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS
  
 9) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 10) I COULD NOT FIND THE WIND DESIGN FOR THE NEW
 EXTERIOR WINDOW AND DOOR OPENINGS ON THE STRUCTURAL
 SHEETS. 2014 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 10.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 10.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 10.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 10.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT,
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 10.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 11) SHEET 0013- AE121.4
  
 11A) PLANS INDICATE A WOOD SHOP ROOM C164 BUT THERE IS
 NO DOORS OR WALLS DEFINING THIS ROOM AND THE ART
 LANDING ROOM C163. PLEASE PROVIDE WHAT ACTIVITIES OCCUR
 IN THIS ROOM, IS THERE SAW DUST MADE, IF SO HOW MUCH
 DAILY? SEE COMBUSTIBLE DUST IN THE 2014 FBC-B TABLE
 415.10.1.1.1 QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN
 A SINGLE FABRICATION AREA. LOOSE SEE FOOTNOTE B.
  
 11B) THE PLANS DO NOT SHOW WHAT WALLS ARE RATED,
 STAIRWELLS, PLEASE SHOW THE OCCUPANT LOADS FOR THE
 STAIR ENCLOSURE 1 & 2. PLEASE PROVIDE THE OCCUPANT LOAD
 FOR EACH FLOOR THE STAIRWELL OPENS ONTO AND THE AMOUNT
 OF OCCUPANTS EACH OF THE STAIRWELLS CAN HANDLE. 2014
 FBC-B 105.3.1 / 0.2 PER OCCUPANT SPRINKLERED BUILDINGS.
  
 11C) ROOM C170 MOTHERS ROOM IS UNDERNEATH STAIR 1A
 PLEASE SHOW COMPLIANCE WITH HOW THE STAIRWELL IS FIRE
 RATED AND THE AREA BENEATH THE STAIRWELL. FBC-B
 1009.3.1 (1) HOUR FIRE BARRIER.
  
 12) SHEET AE123.4 THIS PLAN SHOWS A NEW FLOOR OPENING
 BELOW AND WALL WITH NO DOOR OPENING INTO THE STAIRWELL.
 PLANS ARE NOT CLEAR AS TO THE INTENT. 107.2.1.4.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-15 Cont ID  
Sent By albarran Date 2015-10-15 Time 15:23 Rev Time 0.00
Received By albarran Date 2015-10-15 Time 13:36 Sent To  
Notes
2015-10-15 15:24:36PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-16 Cont ID  
Sent By albarran Date 2015-09-16 Time 13:08 Rev Time 0.00
Received By albarran Date 2015-09-11 Time 13:07 Sent To  
Notes
2015-09-16 13:13:10PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. THE ELECTRICAL RISER IS NOT CLEARLY DEFINED AS TO
 WHAT IS EXISTING TO REMAIN, WHAT IS TO BE DEMOED AND
 WHAT IS TO BE NEW. PLEASE GO OVER THE LINES TO BETTER
 IDENTIFY THE VARIOUS LINES.
 2. WITHOUT CLEARLY DEFINING THE RISER DIAGRAM, THE
 PANEL SCHEDULES ARE VERY DIFFICULT TO FOLLOW.
 3. THE PANEL SCHEDULES ARE TOO LIGHT TO BE VIEWED
 EASILY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-08-11 Cont ID  
Sent By cranford Date 2015-08-11 Time 13:12 Rev Time 0.00
Received By cranford Date 2015-08-11 Time 12:02 Sent To  
Notes
2015-08-11 13:12:33SEE E15070005 FOR WATER AND SEWER AUTHORIZATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-28 Cont ID  
Sent By wjolin Date 2015-10-28 Time 10:46 Rev Time 0.00
Received By wjolin Date 2015-10-28 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-10-07 Cont ID  
Sent By wjolin Date 2015-10-07 Time 15:11 Rev Time 0.00
Received By wjolin Date 2015-10-07 Time 14:22 Sent To  
Notes
2015-10-07 15:11:391451 SOUTH OLIVE AVENUE
 PERMIT #15071043
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW: SHEET PE601 INDICATES, "CONTRACTOR SHALL
 SUBMIT SPRINKLER PLANS IN ACCORDANCE WITH 61G-15."
 HOWEVER, COMPLIANCE WITH FAC 61G15-32 IS THE
 RESPONSIBILITY OF THE ENGINEER OF RECORD. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE ITEMS
 SUCH AS THE POINT OF SERVICE FOR THE WATER SUPPLY, A
 LIST OF APPLICABLE NFPA STANDARDS APPLICABLE TO THE
 PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH
 ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ORIGINAL COMMENT: ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By wjolin Date 2015-08-07 Time 12:01 Rev Time 0.00
Received By wjolin Date 2015-07-30 Time 10:39 Sent To  
Notes
2015-07-30 10:58:481451 SOUTH OLIVE AVENUE
 PERMIT #15071043
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET ADE001: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 SHEET ADE001: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) AND APPROVED BY
 THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY."
  
 LIFE SAFETY PLANS ARE DIFFICULT TO READ DUE TO
 EXTREMELY LIGHT AND DARK DRAWING LINE WEIGHTS. PLANS
 SHALL INDICATE FIRE RATED WALLS, EXIT TRAVEL DISTANCES,
 COMMON PATH OF TRAVEL DISTANCE, DEAD-END CORRIDOR
 LENGTHS, ETC.
  
 SHEET AE121.4 & AE121M.4: THE ADD/ALTERNATE STORAGE
 MEZZANINE APPEARS TO CREATE A COMMON PATH OF TRAVEL OF
 APPROXIMATELY 130 - 150 FEET TO REACH AN EXIT/EXIT
 ACCESS CORRIDOR. FULLY SPRINKLERED STORAGE OCCUPANCIES
 ARE LIMITED TO A COMMON PATH OF TRAVEL OF 100 FEET.
  
 SHEET AE121.4: WOODSHOP C164 REQUIRES A 1-HOUR FIRE
 BARRIER HAZARD SEPARATION FROM THE STORAGE OCCUPANCY
 PER NFPA 1 SECTION 8.7 - SPECIAL HAZARD PROTECTION.
  
 SHEET AE121.4: HOW WILL WOODSHOP C164 BE PROTECTED TO
 PREVENT A DUST EXPLOSION? PER NFPA 101 SECTION 8.7.2 -
 EXPLOSION PROTECTION, WHERE HAZARDOUS PROCESSES OR
 STORAGE IS OF SUCH A CHARACTER AS TO INTRODUCE AN
 EXPLOSION POTENTIAL, AN EXPLOSION VENTING SYSTEM OR AN
 EXPLOSION SUPPRESSION SYSTEM SPECIFICALLY DESIGNED FOR
 THE HAZARD INVOLVED SHALL BE PROVIDED.
  
 SHEET AE121.4: MOTHERS' ROOM #C170 APPEARS TO BE
 LOCATED BELOW THE FIRE RATED STAIR AND WILL REQUIRE THE
 CEILING AND DOOR TO BE PROVIDED WITH A FIRE RATING
 EQUAL TO THE PROTECTED STAIR ENCLOSURE.
  
 SHEET AE121M.4: EXISTING PLANS INDICATE THERE IS A
 LARGE STORAGE ROOM (C205) TO THE WEST OF STAIR #1 THAT
 HAS ACCESS TO BOTH STAIR #1 & STAIR #2. THIS FLOOR PLAN
 APPEARS TO ELIMINATE ACCESS TO STAIR #2 FROM THE
 STORAGE ROOM.
  
 SHEET AE121M.4: PLANS DO NOT INDICATE OF EITHER
 STAIRWELL #1 ENTRANCE DOOR HAS AN EXISTING FIRE RATING.
  
 SHEET AE121M.4: STAIRWELL #2 DOOR C212 DOES NOT
 INDICATE A FIRE RATING AND IS NOT LOCATED IN THE DOOR
 SCHEDULE.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-29 Cont ID  
Sent By cpuell Date 2015-10-29 Time 13:17 Rev Time 0.00
Received By cpuell Date 2015-10-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-15 Cont ID  
Sent By cpuell Date 2015-10-15 Time 16:54 Rev Time 0.00
Received By cpuell Date 2015-09-23 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-21 Cont ID  
Sent By cpuell Date 2015-09-21 Time 16:51 Rev Time 0.00
Received By cpuell Date 2015-07-28 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-15 Cont ID  
Sent By ccole Date 2015-10-15 Time 14:21 Rev Time 0.00
Received By ccole Date 2015-10-15 Time 14:21 Sent To  
Notes
2015-10-15 14:27:52MECHANICAL APPROVED WITH EXCEPTIONS.
 SUBMITTALS REQUIRED PRIOR TO 1ST INSPECTION:
  
 1) ENERGY CALCULATIONS
 2) EXTERIOR PIPE INSULATION AND UV PROTECTION.
 3) WIND LOAD TIE DOWN ENGINEERING FOR THE ROOFTOP PIPE
 SUPPORT STANDS AND CURBS.
 4) FIRE DAMPERS
 5) FL. PRODUCT APPROVALS/MIAMI-DADE NOA'S FOR THE
 DRAINABLE O/A LOUVERS.
  
 PLEASE NOT ALL FUTURE MECHANICAL LAYOUT PLANS MUST
 CLEARLY SHOW THE LOCATIONS OF FIRE-RATED WALLS AND
 FIRE-RATED CEILING ASSEMBLIES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-10 Cont ID  
Sent By ccole Date 2015-08-10 Time 13:55 Rev Time 0.00
Received By ccole Date 2015-08-10 Time 13:54 Sent To  
Notes
2015-08-10 15:03:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071043
  
 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF
 CURRENT CODES AND STANDARDS USED FOR DESIGN AND
 INSTALLATION OF THE PROPOSED HVAC SYSTEM(S)
 ALTERATIONS.
 2) PROVIDE A NARRATIVE TO CLARIFY THE SCOPE AND EXTENT
 OF THE PROJECT PROJECT TO BE COVERED UNDER THIS PERMIT
 APPLICATION. BASED ON THE THE PHASING DIAGRAMS ON SHEET
 AE002 IT APPEARS THAT THE SUBMITTED PLANS WILL LIMIT
 THE PROJECT TO THE NORTH SIDE ALTERATIONS CULMINATING
 AT STAGE 2, AND WILL NOT INCLUDE THE EXPANSION ON THE
 WEST AND SOUTH SIDES.
 3) REFERENCE THE FBC-14 EXISTING BUILDING CODE, SECTION
 809.2 ALTERED EXISTING SYSTEMS: IN MECHANICALLY
 VENTILATED SPACES, EXISTING MECHANICAL VENTILATION
 SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR EXTENDED
 SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER MINUTE
 (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR AND NOT
 LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION AIR PER
 PERSON; OR NOT LESS THAN THE AMOUNT OF VENTILATION AIR
 DETERMINED BY THE INDOOR AIR QUALITY PROCEDURE OF
 ASHRAE 62. PLEASE PROVIDE A VENTILATION SCHEDULE ON THE
 PLAN INDICATING THE REQUIRED CFM'S OF O/A PER THE
 REFERENCED SECTION, AND THE CFM'S OF O/A TO BE
 PROVIDED. SEE ALSO TABLE 403.3 FBC-14 MECHANICAL.
 4) SIZING CALCULATIONS ARE REQUIRED FOR AHU'S 25,
 26,27,28, & 29. REFERENCE THE FBC-14 ENERGY
 CONSERVATION CODE, SECTION C403.2.1 C403.2.1
 CALCULATION OF HEATING AND COOLING LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 5) PROVIDE CHILLED AND HOT WATER PIPING AND VALVE
 SCHEDULES, AND INSTALLATION NOTES AND DETAILS.
 6) REFERENCE SECTION C403.4.5 FBC-14 ENERGY
 CONSERVATION AND SHOW COMPLIANCE- REQUIREMENTS FOR
 COMPLEX MECHANICAL SYSTEMS SERVING MULTIPLE ZONES:
 SECTIONS C403.4.5.1 THROUGH C403.4.5.4 SHALL APPLY TO
 COMPLEX MECHANICAL SYSTEMS SERVING MULTIPLE ZONES.
 SUPPLY AIR SYSTEMS SERVING MULTIPLE ZONES SHALL BE VAV
 SYSTEMS WHICH, DURING PERIODS OF OCCUPANCY, ARE
 DESIGNED AND CAPABLE OF BEING CONTROLLED TO REDUCE
 PRIMARY AIR SUPPLY TO EACH ZONE TO ONE OF THE FOLLOWING
 BEFORE REHEATING, RECOOLING OR MIXING TAKES PLACE:
 1. THIRTY PERCENT OF THE MAXIMUM SUPPLY AIR TO EACH
 ZONE.
 2. THREE HUNDRED CFM (142 L/S) OR LESS WHERE THE
 MAXIMUM FLOW RATE IS LESS THAN 10 PERCENT OF THE TOTAL
 FAN SYSTEM SUPPLY AIRFLOW RATE.
 3. THE MINIMUM VENTILATION REQUIREMENTS OF CHAPTER 4 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
  
 EXCEPTION: THE FOLLOWING DEFINE WHERE INDIVIDUAL ZONES
 OR WHERE ENTIRE AIR DISTRIBUTION SYSTEMS ARE EXEMPTED
 FROM THE REQUIREMENT FOR VAV CONTROL:
 1. ZONES WHERE SPECIAL PRESSURIZATION RELATIONSHIPS OR
 CROSS-CONTAMINATION REQUIREMENTS ARE SUCH THAT VAV
 SYSTEMS ARE IMPRACTICAL.
 2. ZONES OR SUPPLY AIR SYSTEMS WHERE AT LEAST 75
 PERCENT OF THE ENERGY FOR REHEATING OR FOR PROVIDING
 WARM AIR IN MIXING SYSTEMS IS PROVIDED FROM A
 SITE-RECOVERED OR SITE-SOLAR ENERGY SOURCE.
 3. ZONES WHERE SPECIAL HUMIDITY LEVELS ARE REQUIRED TO
 SATISFY PROCESS NEEDS.
 4. ZONES WITH A PEAK SUPPLY AIR QUANTITY OF 300 CFM
 (142 L/S) OR LESS AND WHERE THE FLOW RATE IS LESS THAN
 10 PERCENT OF THE TOTAL FAN SYSTEM SUPPLY AIRFLOW RATE.
 5. ZONES WHERE THE VOLUME OF AIR TO BE REHEATED,
 RECOOLED OR MIXED IS NO GREATER THAN THE VOLUME OF
 OUTSIDE AIR REQUIRED TO MEET THE MINIMUM VENTILATION
 REQUIREMENTS OF CHAPTER 4 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
 6. ZONES OR SUPPLY AIR SYSTEMS WITH THERMOSTATIC AND
 HUMIDISTATIC CONTROLS CAPABLE OF OPERATING IN SEQUENCE
 THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONES
 AND WHICH ARE CAPABLE OF PREVENTING REHEATING,
 RECOOLING, MIXING OR SIMULTANEOUS SUPPLY OF AIR THAT
 HAS BEEN PREVIOUSLY COOLED, EITHER MECHANICALLY OR
 THROUGH THE USE OF ECONOMIZER SYSTEMS, AND AIR THAT HAS
 BEEN PREVIOUSLY MECHANICALLY HEATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-26 Cont ID  
Sent By gjohnson Date 2015-10-26 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2015-10-26 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 05:24 Rev Time 0.00
Received By tklarge Date 2015-10-03 Time 10:17 Sent To  
Notes
2015-10-04 05:15:571) IT IS DIFFICULT TRYING TO REVIEW THE PLANS FROM ON
 SECTION OF AN AREA TO ANOTHER. PLEASE PLACE MATCH LINES
 ON THE FLOOR PLANS ( ADE & AE) DRAWINGS TO ASSIST IN A
 TIMELY REVIEW OF THIS PROJECT. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHT.AE420 -DETAILS #1 &2 - SUBMIT DETAILS HOW THE
 PIPE SUPPORTS/STANDS ARE ATTACHED TO THE EXISTING ROOF.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. AE611 - MEN & WOMEN'S ACCESSIBLE TOILET STALL-
 SHOW THAT THE LAVATORY DOES NOT ENCROACH INTO THE CLEAR
 FLOOR SPACE FOR THE WATER CLOSET. FBC-ACCESS.
 SEC.604.3.
 4) SHT.AE612 - SHOW THE MOUNTING HEIGHTS OF THE GRAB
 BARS ABOVE THE FINISH FLOOR. HEIGHTS SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. FBC-ACCESS. SEC.
 609.4.
 5) SHT. AE613 - DETAIL #2 - SHOW THE REQUIRED CLEAR
 FLOOR SPACE (LXW) FOR THE WATER CLOSET AS REQD. BY
 FBC-ACCESS. SEC.604.3.
 6) SHT. AE613 - DETAIL #2 SHOWS THE CENTERLINE OF THE
 ACCESSIBLE WATER CLOSET 20 INCHES FROM THE SIDE WALL.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16-18
 INCHES FROM THE SIDE WALL.FBC-ACCESS. SEC.604.2.
 7) SHT. AE614 - DETAIL 1A - SHOW THE HEIGHT OF THE
 SHOWER SEAT FROM THE FINISH FLOOR. THE HEIGHT SHALL BE
 17-19 INCHES ABOVE THE FINISH FLOOR. FBC-ACCESS
 SEC.610.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By gjohnson Date 2015-08-12 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2015-08-12 Time 14:48 Sent To  
Notes
2015-08-12 15:32:191ST REVIEW 2014 FBC
  
 COMMENTS:
  
 1.PLEASE INDICATE ON THE PLANS OCCUPANCY LOAD AND
 CALC..
 PB AMENDMENTS TO FBC 2014 SEC. 107.2.1.3
 2.PLEASE INDICATE ON THE PLANS OCCUPANCY CLASSIFICATION
 THIS IS A MIXED OCCUPANCY BUILDING, INDICATE WHICH BATH
 SERVES WHICH OCCUPANCY.
 WPB AMENDMENTS TO FBC 2014 SEC.107.2.1.3
 3.PLEASE SHOW DEMINTIONS FOR SHOWER SEAT SHALL COMPLY
 WITH.
 FBCA SEC. 610.3.2
 4.SHOWER CONTROLS ARE SHOWN ON OPPOSITE WALL FROM SEAT
 ELEVATION 1/A PG. AE 614 CONTROLS SHALL BE ON ADJACENT
 WALL FROM SEAT.TO COMPLY N.
 FBCA SEC. 608.5.2
 5. SHOW DETAIL ON DEMINTIONS FOR GRAB BARS IN TOILET
 ROOM .
 SIDE WALL SHALL COMPLY WITH 604.5.1
 REAR WALL SHALL COMPLY WITH 604.5.2
 6.SHOW DETAIL FOR KNEE AND TOE CLEARANCE ON BREAK ROOM
 SINKS AND LAVATORY'S IN BATHROOMS SHALL COMPLY WITH.
 FBCA SEC. 306.2 AND 306.3
 7. SHOW CLEAR FLOOR SPACE FOR BREAK ROOM SINKS
 ,LAVATORY'S, SHOWER AND TOILETS SHALL COMPLY WITH .
 FBCA SEC. 305
 8.SHOW RISER DIAGRAM FOR SANITARY IN BATHROOM C-158 TO
 COMPLY WITH.
 WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13]
 9. DOMESTIC WATER RISER NOT COMPLETE MISSING RM
 C-158,4IN. CW MAIN AND P-11.MUST SHAOW ALL WATER LINE
 IN THIS PHASE.
 WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13]
 10COPE OF WORK ON THIS PROJECT IS UNCLEAR .IS PLUMBING
 ON THIRD FLOOR CHANGING ,
 WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13
  
  
 11. PLEASE CLARIFY WHAT PHASE OF THIS PROJECT IS UNDER
 THIS PERMIT AND WHAT PHASES WILL BE UNDER OTHER PERMIT
 SOME SYSTEMS WILL OVERLAP AND I NEED ADDITIONAL
 INFORMATION TO DO A THOROUGH REVIEW.
 WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2015-11-03 Cont ID  
Sent By cpuell Date 2015-11-03 Time 14:02 Rev Time 0.00
Received By cpuell Date 2015-11-03 Time 14:02 Sent To  
Notes
2015-11-03 14:02:30DIGITAL SIGNATURES COMPAIRED, ON CD IN STORAGE

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By jroach Date 2015-10-08 Time 12:02 Rev Time 0.00
Received By jroach Date 2015-10-08 Time 12:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-21 Cont ID  
Sent By jroach Date 2015-09-21 Time 16:46 Rev Time 0.00
Received By jroach Date 2015-09-21 Time 16:46 Sent To  
Notes
2015-09-21 16:47:40AWAITING RESPONSE FROM CITY'S RISK MANAGEMENT
 DEPARTMENT TO DETERMINE REQUIREMENTS FOR PROOF OF
 INSURANCE, ETC. AS THE PROPOSED CONSTRUCTION WILL BE
 OCCURING ON CITY-OWNED PROPERTY.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved