Plan Review Details - Permit 15071002
Plan Review Stops For Permit 15071002
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-04-14 Cont ID  
Sent By jwitmer Date 2016-04-14 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-25 Cont ID  
Sent By jwitmer Date 2016-03-25 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2016-03-25 Time 09:58 Sent To  
Notes
2016-03-25 11:34:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15071002
 ADD: 1415 S. OLIVE CONSTRUCTION TRAILERS
 CONT: GILBANE CONSTRUCTION
 TEL: (941)44-8062
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MARCH 25/ 2016
 ACTION: DENIED
  
 1) SHEET A100 RAMP, STAIR, LANDING, HANDRAIL &
 GUARDRAIL DESIGNS SHOW PLANS SIGNED BY A ARCHIECT STATE
 OF GEORGIA SEAL. PLEASE REVIEW FLORIDA ADMINISTRTIVE
 CODE:
 61G16 2.001 SEALS ACCEPTABLE TO THE BOARD.
  
 PURSUANT TO 492.107, F.S. AND CHAPTER 94-119, LAWS OF
 FLORIDA, THE BOARD HEREBY ESTABLISHES AS INDICATED
 BELOW THE FORMS OF METAL-TYPE IMPRESSION OR STAMPED INK
 SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 FLORIDA STATUTE 481.221(2) ?EACH REGISTERED ARCHITECT
 SHALL OBTAIN ONE SEAL IN A FORM APPROVED BY RULE OF THE
 BOARD .ALL FINAL CONSTRUCTION DOCUMENTS AND INSTRUMENTS
 OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED.
  
 PLEASE PROVIDE DETAILS FOR COMPLIANCE WITH THE
 ACCESSIBLE RAMP AND DECK. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 ACCESSIBLE PARKING FL ACC 505.2, 502.3 & 502.3.3
 MARKING TO CITY STANDARD
 RAMPS 2014 FL ACC 405 RAMPS
 HANDRAILS/ GAURDRAILS 2014 FL ACCESS 505
  
 2) THE PLANS SUBMITTED FOR ANCHOR TIE DOWN BY ARCHITECT
 JOHN BODZIAK(SHEET 4 OF 4) ARE NOT SIGNED NOR SEALED,
 NOR ELECTONIC SIGNATURE. PURSUANT TO 492.107, F.S. AND
 CHAPTER 94-119, LAWS OF FLORIDA, THE BOARD HEREBY
 ESTABLISHES AS INDICATED BELOW THE FORMS OF METAL-TYPE
 IMPRESSION OR STAMPED INK SEALS WHICH ARE ACCEPTABLE TO
 THE BOARD.
 FLORIDA STATUTE 481.221(2) ?EACH REGISTERED ARCHITECT
 SHALL OBTAIN ONE SEAL IN A FORM APPROVED BY RULE OF THE
 BOARD .ALL FINAL CONSTRUCTION DOCUMENTS AND INSTRUMENTS
 OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2015-09-10 Time 07:00 Sent To  
Notes
2015-09-10 07:33:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15071002
 ADD: 1415 S. OLIVE CONSTRUCTION TRAILERS
 CONT: GILBANE CONSTRUCTION
 TEL: (941)44-8062
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 10/2015
 ACTION: DENIED
  
 1) SHEET EX-2 SITE PLANS SHOW AN ACCESSIBLE RAMP & DECK
 FOR ACCESS INTO THE JOBSITE TRAILERS. THE SITE PLAN
 ALSO SHOWS ACCESS FROM THE STREET BUT NO ACCESSIBLE
 PARKING SPACES. WITH SHOWING THESE DETAILS IT IS
 ASSUMED THAT THIS CONSTRUCTION OFFICE WILL HAVE
 MEETINGS AND NEED TO COMPLY WITH
 PART V (SECTION 553.501-553.513, FLORIDA STATUTES)
 RELATING TO ACCESSIBILITY BY PERSONS WITH DISABILITIES,
 AND PERMITS SHALL BE REQUIRED FOR STRUCTURAL SUPPORT
 AND TIE DOWN, ELECTRICAL SUPPLY, AND ALL UTILITY
 CONNECTIONS TO SUCH MOBILE OR MODULAR STRUCTURES.
  
 PLEASE PROVIDE DETAILS FOR COMPLIANCE WITH THE
 ACCESSIBLE RAMP AND DECK. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 ACCESSIBLE PARKING FL ACC 505.2, 502.3 & 502.3.3
 MARKING TO CITY STANDARD
 RAMPS 2014 FL ACC 405 RAMPS
 HANDRAILS/ GAURDRAILS 2014 FL ACCESS 505
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By gjohnson Date 2015-08-20 Time 16:33 Rev Time 0.00
Received By skennedy Date 2015-08-20 Time 16:33 Sent To  
Notes
2015-09-10 08:33:08THIS IS AN INADVERTANT REVIEW. SEE REVIEW BY JWITMER.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 08:40 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 08:40 Sent To  
Notes
2015-09-10 08:41:11BY SEPARATE PERMIT

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-11 Cont ID  
Sent By wjolin Date 2016-03-11 Time 13:18 Rev Time 0.00
Received By wjolin Date 2016-03-11 Time 13:02 Sent To  
Notes
2016-03-11 13:18:491451 SOUTH OLIVE AVENUE
 PERMIT #15071002
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OCCUPANCY OF THE CONSTRUCTION TRAILERS IS NOT PERMITTED
 UNTIL A #131 FIRE FINAL INSPECTION HAS BEEN PASSED.
  
 A SEPARATE PERMIT IS NEEDED FOR INSTALLING AUTOMATIC
 FIRE SPRINKLERS.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By wjolin Date 2015-08-26 Time 15:58 Rev Time 0.00
Received By wjolin Date 2015-08-26 Time 15:43 Sent To  
Notes
2015-08-26 15:58:071451 SOUTH OLIVE AVENUE
 PERMIT #15071002
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OCCUPANCY OF THE CONSTRUCTION TRAILERS IS NOT PERMITTED
 UNTIL A #131 FIRE FINAL INSPECTION HAS BEEN PASSED.
  
 PROVIDE AN ADDRESS IN THE TITLEBLOCK CORRESPONDING TO
 THE TRAILER LOCATIONS.
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO PLANS SUBMITTED FOR STAIRS, RAMP, EXTERIOR LIGHTING
 OR WOOD DECKING.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER. GUARDS, AT LEAST 42-INCHES TALL,
 SHALL BE PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS
 (STAIRS, MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE
 THE FLOOR. OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A
 4-INCH DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-03-18 Cont ID  
Sent By fmittner Date 2016-03-18 Time 13:54 Rev Time 0.00
Received By fmittner Date 2016-03-18 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-14 Cont ID  
Sent By jwitmer Date 2016-04-14 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-03-30 Time 12:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-28 Cont ID  
Sent By lmarchan Date 2016-03-28 Time 08:26 Rev Time 0.00
Received By lmarchan Date 2016-03-07 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-24 Cont ID  
Sent By cpuell Date 2015-09-24 Time 15:02 Rev Time 0.00
Received By cpuell Date 2015-08-19 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 08:31 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 04:19 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 04:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 05:57 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 05:44 Sent To  
Notes
2015-09-05 05:56:41INDICATE ON THE PLANS HOW THE SEWAGE WILL BE DISPOSED.
 WILL IT GO TO A HOLDING TANK? HOLDING TANKS EXCEEDING
 300 GALS. REQUIRE AN APPROVAL FOM THE PBC HEALTH DEPT.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-04-14 Cont ID  
Sent By jwitmer Date 2016-04-14 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-04-14 Time   Sent To  
Notes
2016-04-01 12:43:10HAVE ORIGINAL DOCUMENTS WITH PERMIT APPLICATION TO BE
 REVIEWED

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-18 Cont ID  
Sent By jroach Date 2016-03-18 Time 14:29 Rev Time 0.00
Received By jroach Date 2016-03-18 Time 14:29 Sent To  
Notes
2016-03-18 14:29:16ALL SUCH STRUCTURES, INCLUDING TRAILERS, SHALL BE
 REMOVED WITHIN SEVEN DAYS OF THE FINAL CONSTRUCTION
 INSPECTION BY THE CITY AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-24 Cont ID  
Sent By jroach Date 2015-09-24 Time 13:51 Rev Time 0.00
Received By jroach Date 2015-09-24 Time 13:51 Sent To  
Notes
2015-09-24 13:52:00ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.24.2015
 PERMIT NO.: 15071002
 ADDRESS: 1451 S. OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.: 561.236.7052
 SCOPE OF REVIEW: CONSTRUCTION TRAILERS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. STAFF HAS SOME CONCERNS REGARDING THE PLACEMENT OF
 THE CONSTRUCTION TRAILERS AND THEIR IMPACT ON THE
 NUMBER OF PARKING SPACES, EXISTING LANDSCAPING IN THE
 PARKING LOT, ETC. I THINK IT WOULD BE MOST BENEFICIAL
 IF THERE WAS A MEETING BETWEEN THE CONTRACTOR, STAFF,
 REPRESENTATIVES OF THE NORTON, ETC. SO THAT THERE IS AN
 UNDERSTANDING OF MANAGEMENT OF THE SITE THROUGHOUT THE
 ENTIRE CONSTRUCTION PROJECT. THINGS TO DISCUSS WOULD BE
 CONSTRUCTION STAGING, PARKING FOR CONSTRUCTION WORKERS,
 PARKING FOR EMPLOYEES, PUBLIC PARKING, ETC.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  
2015-08-24 11:10:028/24/15