Plan Review Details - Permit 15070956
Plan Review Stops For Permit 15070956
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2015-09-11 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-29 Cont ID  
Sent By jwitmer Date 2015-07-29 Time 07:20 Rev Time 0.00
Received By jwitmer Date 2015-07-29 Time 06:26 Sent To  
Notes
2015-07-29 06:42:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070956
 ADD: 1555 PALM BEACH LAKES BLVD. SUITE # 200
 CONT: FISHER
 TEL: ( 561)691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 29/2015
 ACTION: DENIED
  
 1) PAGE LS-1:
  
 1A) CODE INVESTIGATION INDICATES THIS BUILDING IS BUILT
 TO THE BUILDING TYPE IIIA, PLEASE NOTE THIS IS A HIGH
 RISE BUILDING AND AT LEAST A TYPE IB, PLEASE INDICATE
 THE NUMBER OF STORIES IN THIS BUILDING TO CORRECTLY
 IDENTIFY THE MINIMUM BUILDING TYPE. SEE 2014 FBC-B
 TABLE 503.
  
 1B) CODE INVESTIGATION INDICATES THE FLOOR AREA IS 8672
 SQ, FT./ 100= 86 OCCUPANTS. THE 2014 FBC-B 1004.1.2 &
 TABLE 1004.1.2. SEE THE FLORIDA BUILDING CODE INFORMAL
 INTERPRETATION 5479 YOU ALWAYS ROUND UP IN OCCUPANT
 LOADS, NO PARTS OF OCCUPANTS.
  
 1C) DELETED 8/27/2015
  
 2) SHEET A-2:
  
 2A) DOOR # 3 TO CALL CENTER NEEDS TO SHOW THE 18 INCHES
 ON THE LATCH SIDE OF THE DOOR, SEE 2014 FBC-ACCESS.
 CODE 404.2.4.3.
  
 2B) DOOR # 19 OFFICE # 221 DOES NOT COMPLY WITH THE
 REQUIRED 18 INCHES ON THE LATCH SIDE OF DOOR, SEE 2014
 FBC-ACCESS. CODE 404.2.4.3.
  
 2C) DOOR # 23 DOES NOT COMPLY WITH THE REQUIRED 18
 INCHES ON THE LATCH SIDE OF DOOR, SEE 2014 FBC-ACCESS.
 CODE 404.2.4.3.
  
 3) SHEET A-1 DETAIL # 4 SHOWS THE MICROWAVE SHELF AT A
 ELEVATION OF 4'-6". PLEASE PROVIDE COMPLIANCE WITH:
  
 3A) 2014 FBC-ACCESS. CODE SECTION 308.2.2 OBSTRUCTED
 HIGH REACH FRONT APPROACH.
  
 3B) 2014 FBC-ACCESS. CODE SECTION 308. 3.2 OBSTRUCTED
 HIGH REACH SIDE APPROACH.
  
 3C) 20104 FBC-ACCESS. CODE SECTION 209.3. OPERABLE
 PARTS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By ppetty Date 2015-09-18 Time 09:54 Rev Time 0.00
Received By albarran Date 2015-09-18 Time 09:28 Sent To I
Notes
2015-09-18 10:02:31THIS PERMIT WAS PREVIOUSLY REVIEWED AND APPROVED BY
 PHIL PETTY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-24 Cont ID  
Sent By ppetty Date 2015-08-24 Time 10:36 Rev Time 0.00
Received By ppetty Date 2015-08-24 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-10 Cont ID  
Sent By scaldero Date 2015-09-10 Time 12:57 Rev Time 0.00
Received By scaldero Date 2015-09-10 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-03 Cont ID  
Sent By scaldero Date 2015-08-03 Time 12:17 Rev Time 0.00
Received By scaldero Date 2015-08-03 Time 12:10 Sent To  
Notes
2015-08-03 12:17:45PERMIT # 15070956
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 3) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-18 Cont ID  
Sent By albarran Date 2015-09-18 Time 10:03 Rev Time 0.00
Received By albarran Date 2015-09-03 Time 10:49 Sent To  
Notes
2015-09-18 10:05:319/15/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE READY BIN "F". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-24 Cont ID  
Sent By ppetty Date 2015-08-24 Time 10:37 Rev Time 0.00
Received By ppetty Date 2015-07-24 Time 16:30 Sent To  
Notes
2015-07-24 16:30:52C02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-08 Cont ID  
Sent By ccole Date 2015-09-08 Time 15:26 Rev Time 0.00
Received By ccole Date 2015-09-08 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By ccole Date 2015-07-31 Time 09:07 Rev Time 0.00
Received By ccole Date 2015-07-31 Time 09:07 Sent To  
Notes
2015-07-31 09:22:231ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070956
 7/31/15
  
 1) SHEET M-1: THE OUTSIDE AIR CALCULATION SCHEDULE IS
 REFERENCING THE OUTDATED ASHRAE 62.1- 2004. PLEASE
 REVIEW AND REVISE THE CALCULATIONS IN COMPLIANCE WITH
 SECTION 809.2 FBC-14 EXISTING BUILDING CODE: ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 2) M-2: THE AIR DISTRIBUTION TAG PRINT AT THE DIFFUSERS
 IS TOO SMALL TO READ. PLEASE ENLARGE EITHER THE TAGS OR
 THE ENTIRE DRAWING TO EXPEDITE THE REVIEW- SECTION
 107.2.1 WPB AMENDEMENTS TO THE FBC-14 BUILDING CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  