Plan Review Details - Permit 15070928
Plan Review Stops For Permit 15070928
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 15:50 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 15:50 Sent To  
Notes
2015-08-25 16:07:461ST REVIEW: FBC 2014 5TH ED.
  
 FROM CITY RECORDS, IT CANNOT BE ASCERTAINED THAT THE
 AREA DEPICTED ON THE PLAN SHOWN AS "AS BUILT" AND
 INDICATED AS HABITAL SPACE CONSISTING OF A FAMILY ROOM,
 TWO BEDROOMS, A LIVING ROOM AND LAUNDRY ROOM, WAS
 PREVIOUSLY CONSTRUCTED FOR HABITAL USE WITHIN THE R3
 OCCUPANCY CLASSIFICATION. PERMIT 6365I WAS ISSUED ON
 6/1/1983, I PRESUME THAT IS WHEN THE APPROXIMATELY 650
 SF AREA WAS BUILT. THE PROPERTY APPRAISER WEB SITE
 SHOWS THIS PORTION OF THE STRUCTURE AS "SEMI FINISHED
 BASE AREA."
  
 PLEASE PROVIDE ANY RECORDS YOU MAY HAVE TO DEMONSTRATE
 CONSTRUCTION DETAILS OF THIS PART OF THE STRUCTURE.
 ALTERNATIEVLY, IF THE IMPROVEMENTS ARE AS COMPLETE AS
 THE PLAN INDICATES, PROVIDE THE FOLLOWING:
  
 AN ENERGY SUBMITTAL
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 DETAILS TO DEMONSTRATE PROPOSED OR EXISTING BUILDING
 ENVELOPE THERMAL EFFICIENTCY.
  
 FBC - R301.2.1.2 PROTECTION OF OPENINGS. PROVIDE AN
 IMPACT PROTECTION SUBMITTAL.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
  
 ADVISORY COMMENT IF WORK WAS COMPLETED WITHOUT A PERMIT
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
  
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 16:40 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 16:39 Sent To  
Notes
2015-08-25 16:43:231ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 FBC- 107.3.5.3 ? PROVIDE EVIDENCE OF EXISTION PERMITTED
 WORK OR PROVIDE A NEW COMPLETE LOAD CALCULATIONS, PANEL
 SCHEDULES AND SHOW CIRCUITS ON FLOOR PLAN.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 FBC 1006.1 MEANS OF EGRESS ILLUMINATION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 16:40 Rev Time 0.00
Received By skennedy Date 2015-07-24 Time 12:53 Sent To  
Notes
2015-07-24 12:53:44BLDG MISC 2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 15:49 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 15:49 Sent To  
Notes
2015-08-25 15:50:091ST REVIEW: FBC 2014 5TH ED.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 16:35 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 16:35 Sent To  
Notes
2015-08-25 16:39:461ST REVIEW: FBC 2014 5TH ED.
  
 IT IS ASSUMED THIS IS AN AREA PREVIOUSLY NOT
 CONDITIONED. PROVIDE EVIDENCE OF EXISTING PERMITTED
 HVAC WORK OR THE BELOW WILL APPLY:
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & EQUIPMENT
  
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION.
  
 FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT BEDROOMS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  