Plan Review Details - Permit 15070912
Plan Review Stops For Permit 15070912
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2015-09-11 Time 06:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-28 Cont ID  
Sent By jwitmer Date 2015-07-28 Time 11:04 Rev Time  
Received By jwitmer Date 2015-07-28 Time 08:32 Sent To  
Notes
2015-07-28 10:06:19 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070912
 ADD: 222 LAKEVIEW AVE. # 2S
 CONT: PUZZITIELLO BUILDERS / CBCA37798
 TEL: (561)939-4852
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 28/ 2015
 ACTION: DENIED
  
 1) SHEET A-O.01 NOTE # 3 INDICATES THE REMOVAL AND
 REPLACEMENT OF THE SLIDDING GLASS DOORS. THIS REVIEW
 THERE WERE NO PRODUCT APPROVALS FOR THE NEW SLIDDING
 GLASS DOORS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 2) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 SLIDDING GLASS DOORS:
  
  
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) SHEET A-6.10 DETAIL # 2 PLEASE PROVIDE COMPLIANCE
 FOR HANDRAIL WITH 2014 FBC-B 1012.3 HANDRAIL
 GRASPABILITY FOR TYPE I HANDRAILS.
  
 5) SHEET A1.01 INDICATES THE USE OF NEW FLOORING TILE
 AND LAMINATE WOOD FLOORING. PLEASE SUBMIT THE TESTING
 FOR BOTH PRODUCTS MEETING THE FOLLOWING CRITERIA:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
  
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) SHEET A0.01 NOTES 7 & 20 INDICATE THE REMOVAL OF
 DRYWALL AT WET AREAS, PLEASE REVIEW THE REQUIREMENTS
 FOR BASE FOR TILE AND LIMITATIONS UNDER CODE SECTION
 2014 FBC-B 2509.2 & 2509.3.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 15:37 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-02 Cont ID  
Sent By pleduc Date 2015-09-02 Time   Rev Time 0.00
Received By pleduc Date 2015-09-02 Time 16:58 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By pleduc Date 2015-07-30 Time   Rev Time 0.00
Received By pleduc Date 2015-07-30 Time 12:37 Sent To  
Notes
2015-07-30 13:47:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 1.01, INDICATES AN ENCLOSED STORAGE SPACE
 UNDER THE INTERIOR STAIRS. PROVIDE DOCUMENTATION/DETAIL
 CONFIRMING THE INSTALLATION OF 1 HOUR FIRE RATING UNDER
 THE STAIRS AND/OR THE EXISTANCE OR INSTALLATION OF FIRE
 SPRINKLER PROCTECTION UNDER THE STAIRS.
  
 2. SHEET A 6.10, PROVIDE GREATER DETAIL/DRAWING OF THE
 STAIRWAY COMPLYING WITH NFPA 101, CHAPTER 7, 7.2.2.4,
 GUARDS AND HANDRAILS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 13:01 Sent To  
Notes
2015-09-02 13:01:11RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 15:37 Rev Time 0.00
Received By skennedy Date 2015-07-22 Time 13:48 Sent To  
Notes
2015-07-23 13:48:12B19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-29 Cont ID  
Sent By ccole Date 2015-07-29 Time 08:05 Rev Time 0.00
Received By ccole Date 2015-07-29 Time 08:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-30 Cont ID  
Sent By gjohnson Date 2015-07-30 Time 16:39 Rev Time 0.00
Received By gjohnson Date 2015-07-30 Time 16:39 Sent To  
Notes
***NONE***