2015-10-26 10:44:09 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| TO RESOLVE EXPIRED PERMITS, SUBMIT APPLICATIONS AT THE |
| BUILDING DIVISION. SUBMIT A RECORDS RESEARCH REQUEST |
| WITH EACH ONE TO OBTAIN THE PLANS REQUIRED. |
| |
| 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. |
| ALSO INCLUDE THE FOLLOWING INFORMATION: |
| |
| A. IF THE WINDOW IS LOCATED IN A BEDROOM, NOTE EXISTING |
| CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| BEDROOMS, FBC R310, FBC EB 704.1. THE CLEAR OPENING |
| CANNOT BE REDUCED BY MORE THAN 5%. |
| |
| TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION |
| NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| HEIGHT: |
| |
| STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS |
| - AWNING, CASEMENT, SINGLE HUNG? |
| |
| STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. |
| CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE |
| WINDOW IS FULLY OPEN. |
| |
| STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. |
| THIS CAN BE OBTAINED FROM THE MANUFACTURER. |
| |
| B. IMPACT PROTECTION REQUIRED,FBC1609.1.2, FBC R |
| 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| (AVAILABLE IN THE LOBBY AND AT: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| |
| IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 706.4, |
| PROVIDE CALCULATIONS. |
| |
| 3. A STOP WORK ORDER VIOLATION HAS BEEN ISSUED FOR THIS |
| PROPERTY. APPLICATION SHOULD ADDRESS THE VIOLATION, |
| WHICH WAS FOR AN ADDITION INCLUDING WINDOWS. |
| |
| 4. FROM PREVIOUS LIST: CONTRACTOR WAS UNDER AN |
| AGREEMENT 1.5 YEARS AGO TO RESOLVE FIVE EXPIRED PERMITS |
| A MONTH. RATHER THAN ADDRESSING FIVE A MONTH, SEVERAL |
| MORE PERMITS ARE NOW IN EXPIRED STATUS. BASED ON THE |
| CONTRACTOR'S AGREEMENT, ALL EXPIRED PERMITS SHOULD BE |
| RESOLVED AT THIS TIME. THIS IS NOT THE CASE. |
| |
| LICENSE U-17813 HAS 36 EXPIRED PERMITS, 5 REVOKED |
| (RESOLVED EXPIRED PERMITS) |
| |
| LICENSE U-20912 HAS 18 EXPIRED PERMITS (THREE HAVE |
| EXPIRED SINCE CONTRACTOR'S AGREEMENT TO RESOLVE OLD |
| EXPIRED PERMITS0, 7 REVOKED). |
| |
| CONTRACTOR HAS 56 EXPIRED PERMITS. FAILURE TO RESOLVE |
| THESE PERMITS WILL RESULT IN A COMPLAINT BEING FILED |
| AGAINST CONTRACTOR. DUE TO THE FAILURE TO FOLLOW |
| THROUGH ON THE AGREEMENT, AND THE ISSUE OF ADDITIONAL |
| PERMITS EXPIRING DURING AFTER CONTRACTOR AGREED TO |
| RESOLVE EXPIRED PERMITS, CONTRACTOR IS TO RESOLVE AT |
| LEAST HALF OF THE EXPIRED PERMITS WITHIN 30 DAYS, AND |
| SUBSTANTIALLY ALL OF THE PERMITS WITHIN 60 DAYS. |
| |
| ISSUANCE OF THIS PERMIT (15070876) IS UNRELATED TO |
| COMMENT #3. THIS PERMIT CAN BE ISSUED TO THIS |
| CONTRACTOR AFTER COMMENTS ARE ADDRESSED. FAILURE TO |
| RESOLVE EXPIRED PERMITS WILL RESULT IN A COMPLAINT |
| AGAINST CONTRACTOR, EVEN IF THIS PERMIT IS ISSUED TO A |
| DIFFERENT CONTRACTOR. |
| |
| |