Plan Review Details - Permit 15070876
Plan Review Stops For Permit 15070876
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-11-08 Cont ID  
Sent By skennedy Date 2015-11-08 Time 09:31 Rev Time 0.00
Received By skennedy Date 2015-11-08 Time 09:31 Sent To  
Notes
2015-11-08 09:35:27ADMINISTRATIVE REVIEW
  
 THIS APPLICATION SHOULD BE REVOKED AND INCORPORATED
 INTO 15091327. THIS IS FOR A WINDOW IN A STRUCTURE
 BUILT WITHOUT A PERMIT, SO 15091327 SHOULD INCLUDE ALL
 DETAOLS TO LEAGALIZE THE STRUCTUREIF POSSIBLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-02 Cont ID  
Sent By shill Date 2015-11-02 Time 15:38 Rev Time 0.00
Received By shill Date 2015-11-02 Time 15:35 Sent To  
Notes
2015-11-02 15:39:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OK
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.2, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 706.4,
 PROVIDE CALCULATIONS.
  
 3. A STOP WORK ORDER VIOLATION HAS BEEN ISSUED FOR THIS
 PROPERTY. APPLICATION SHOULD ADDRESS THE VIOLATION,
 WHICH WAS FOR AN ADDITION INCLUDING WINDOWS.
  
 4. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-26 Cont ID  
Sent By shill Date 2015-10-26 Time 10:43 Rev Time 0.00
Received By shill Date 2015-10-26 Time 10:43 Sent To  
Notes
2015-10-26 10:44:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 TO RESOLVE EXPIRED PERMITS, SUBMIT APPLICATIONS AT THE
 BUILDING DIVISION. SUBMIT A RECORDS RESEARCH REQUEST
 WITH EACH ONE TO OBTAIN THE PLANS REQUIRED.
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
 ALSO INCLUDE THE FOLLOWING INFORMATION:
  
 A. IF THE WINDOW IS LOCATED IN A BEDROOM, NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 704.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
 B. IMPACT PROTECTION REQUIRED,FBC1609.1.2, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 706.4,
 PROVIDE CALCULATIONS.
  
 3. A STOP WORK ORDER VIOLATION HAS BEEN ISSUED FOR THIS
 PROPERTY. APPLICATION SHOULD ADDRESS THE VIOLATION,
 WHICH WAS FOR AN ADDITION INCLUDING WINDOWS.
  
 4. FROM PREVIOUS LIST: CONTRACTOR WAS UNDER AN
 AGREEMENT 1.5 YEARS AGO TO RESOLVE FIVE EXPIRED PERMITS
 A MONTH. RATHER THAN ADDRESSING FIVE A MONTH, SEVERAL
 MORE PERMITS ARE NOW IN EXPIRED STATUS. BASED ON THE
 CONTRACTOR'S AGREEMENT, ALL EXPIRED PERMITS SHOULD BE
 RESOLVED AT THIS TIME. THIS IS NOT THE CASE.
  
 LICENSE U-17813 HAS 36 EXPIRED PERMITS, 5 REVOKED
 (RESOLVED EXPIRED PERMITS)
  
 LICENSE U-20912 HAS 18 EXPIRED PERMITS (THREE HAVE
 EXPIRED SINCE CONTRACTOR'S AGREEMENT TO RESOLVE OLD
 EXPIRED PERMITS0, 7 REVOKED).
  
 CONTRACTOR HAS 56 EXPIRED PERMITS. FAILURE TO RESOLVE
 THESE PERMITS WILL RESULT IN A COMPLAINT BEING FILED
 AGAINST CONTRACTOR. DUE TO THE FAILURE TO FOLLOW
 THROUGH ON THE AGREEMENT, AND THE ISSUE OF ADDITIONAL
 PERMITS EXPIRING DURING AFTER CONTRACTOR AGREED TO
 RESOLVE EXPIRED PERMITS, CONTRACTOR IS TO RESOLVE AT
 LEAST HALF OF THE EXPIRED PERMITS WITHIN 30 DAYS, AND
 SUBSTANTIALLY ALL OF THE PERMITS WITHIN 60 DAYS.
  
 ISSUANCE OF THIS PERMIT (15070876) IS UNRELATED TO
 COMMENT #3. THIS PERMIT CAN BE ISSUED TO THIS
 CONTRACTOR AFTER COMMENTS ARE ADDRESSED. FAILURE TO
 RESOLVE EXPIRED PERMITS WILL RESULT IN A COMPLAINT
 AGAINST CONTRACTOR, EVEN IF THIS PERMIT IS ISSUED TO A
 DIFFERENT CONTRACTOR.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By shill Date 2015-07-31 Time 09:22 Rev Time 0.00
Received By shill Date 2015-07-31 Time 09:22 Sent To  
Notes
2015-07-31 09:39:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE PLANS FOR PROPOSED WORK. A NON IMPACT
 PRODUCT APPROVAL FOR A SINGLE HUNG WINDOW WAS PROVIDED.
 SEE FBC 107, ARCHITECTURAL QUALITY PLANS, TO SCALE,
 WHICH SHOW THE LOCATION AND NATURE OF PROPOSED WORK IS
 REQUIRED.
  
 A REVIEW CANNOT BE DONE AT THIS TIME DUE TO THE LACK OF
 INFORMATION PROVIDED.
  
 2. A STOP WORK ORDER VIOLATION HAS BEEN ISSUED FOR THIS
 PROPERTY. APPLICATION SHOULD ADDRESS THE VIOLATION,
 WHICH WAS FOR AN ADDITION INCLUDING WINDOWS.
  
 3. CONTRACTOR WAS UNDER AN AGREEMENT A YEAR AGO TO
 RESOLVE FIVE EXPIRED PERMITS A MONTH. RATHER THAN
 ADDRESSING FIVE A MONTH, SEVERAL MORE PERMITS ARE NOW
 IN EXPIRED STATUS. BASED ON THE CONTRACTOR'S AGREEMENT,
 ALL EXPIRED PERMITS SHOULD BE RESOLVED AT THIS TIME.
 THIS IS NOT THE CASE.
  
 LICENSE U-17813 HAS 38 EXPIRED PERMITS, 5 REVOKED
 (RESOLVED EXPIRED PERMITS)
  
 LICENSE U-20912 HAS 18 EXPIRED PERMITS (THREE HAVE
 EXPIRED SINCE CONTRACTOR'S AGREEMENT TO RESOLVE OLD
 EXPIRED PERMITS0, 7 REVOKED.
  
 CONTRACTOR HAS 56 EXPIRED PERMITS. FAILURE TO RESOLVE
 THESE PERMITS WILL RESULT IN A COMPLAINT BEING FILED
 AGAINST CONTRACTOR. DUE TO THE FAILURE TO FOLLOW
 THROUGH ON THE AGREEMENT, AND THE ISSUE OF ADDITIONAL
 PERMITS EXPIRING DURING AFTER CONTRACTOR AGREED TO
 RESOLVE EXPIRED PERMITS, CONTRACTOR IS TO RESOLVE AT
 LEAST HALF OF THE EXPIRED PERMITS WITHIN 30 DAYS, AND
 SUBSTANTIALLY ALL OF THE PERMITS WITHIN 60 DAYS.
  
 ISSUANCE OF THIS PERMIT (15070876) IS UNRELATED TO
 COMMENT #3. THIS PERMIT CAN BE ISSUED TO THIS
 CONTRACTOR AFTER COMMENTS ARE ADDRESSED. FAILURE TO
 RESOLVE EXPIRED PERMITS WILL RESULT IN A COMPLAINT
 AGAINST CONTRACTOR, EVEN IF THIS PERMIT IS ISSUED TO A
 DIFFERENT CONTRACTOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-02 Cont ID  
Sent By shill Date 2015-11-02 Time 15:55 Rev Time 0.00
Received By shill Date 2015-10-29 Time 09:17 Sent To  
Notes
2015-10-30 09:18:00RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-26 Cont ID  
Sent By shill Date 2015-10-26 Time 11:43 Rev Time 0.00
Received By shill Date 2015-10-07 Time 13:03 Sent To  
Notes
2015-10-07 13:03:53RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-31 Cont ID  
Sent By shill Date 2015-07-31 Time 09:39 Rev Time 0.00
Received By shill Date 2015-07-22 Time 13:15 Sent To  
Notes
2015-07-23 13:16:05ROUTED TO BLDG <5K