Plan Review Stops For Permit 15070848 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2015-08-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-18 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-18 |
Time |
13:43 |
Sent To |
|
|
Notes |
2015-08-18 13:44:13 | ****PROVISO**** | | ISSUED AT CONTRACTOR?S RISK | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | THE PRODUCT APPROVAL IS VALIDATED. A STATUS OF APPROVED | | IS REQUIRED. | | | | AN APPROVED PRODUCT APPROVAL IS REQUIRED PRIOR TO FINAL | | INSPECTION. IT IS THE CONTRACTOR?S RESPONSIBILITY TO | | ENSURE THAT AN APPROVED PRODUCT APPROVAL IS ON FILE. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2015-08-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-10 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-10 |
Time |
13:34 |
Sent To |
|
|
Notes |
2015-08-10 13:34:25 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC 1609 | | | | 1. PER APPLICANT (AFTER REVIEW #2), THIS IS A RECOVER | | OVER AN INSULATED STEEL DECK. A MOISTURE SURVEY IS | | REQUIRED TO DETERMINE THAT SUBSTRATE (INSULATION) IS | | SUITABLE FOR RECOVER, FBC 5TH EDITION EXISTING BUILDING | | 708.3(1), FBC 1510.3. | | | | IF AN ENGINEER?S STATEMENT THAT THE EXISTING ROOF IS | | SUITABLE FOR RECOVERY IS NOT PROVIDED IN THE MOISTURE | | SURVEY, THIS PERMIT WILL BE ISSUED AT CONTRACTOR?S RISK | | AND A PREINSPECT WILL BE REQUIRED PRIOR TO | | COMMENCEMENT. | | | | PROVIDE INFORMATION REGARDING THE EXISTING FLAT ROOF. | | CONTRACT STATES THAT LOOSE GRAVEL WILL BE REMOVED; IS | | THIS A TAR AND GRAVEL ROOF? IF THIS IS, PROVIDE | | MANUFACTURER?S LETTER THAT A RECOVERY IS SUITABLE FOR | | THIS ROOF. | | | | 2 - 3 OK | | | | 4. OK - PROVISO, PROVIDE 2014 STATE PRODUCT APPROVAL | | WHEN AVAILABLE FOR FOAM ADHESIVE. | | | | 5. COMMENT FROM PREVIOUS LISTS: PROVIDE A ROOF PLAN | | WHICH SHOWS REROOF AREAS AND ROOF RECOVER AREAS. | | INCLUDE ROOF PITCH, ROOF DECK SUBSTRATE TYPE, AND MEAN | | ROOF HEIGHT. THE NOTE (3/12/18/12) IS NOT CLEAR. | | NOT PROVIDED. APPLICANT HAS PROVIDED THE MEAN ROOF | | HEIGHT AND SUBSTRATE FOR THE FLAT ROOF. PLEASE PROVIDE | | A ROOF PLAN SHOWING ROOF AREAS AND ROOF PITCH. ARE | | THERE TWO PITCHED AREAS, 3/12 AND 18/12? APPLICANT CAN | | USE AN AERIAL AND MARK IT UP (PROVIDED THAT IT IS | | LEGIBLE) IF APPLICANT IS UNABLE TO PROVIDE A ROOF PLAN. | | A BUILDING OUTLINE IS AVAILABLE ON PAPA AS WELL: | | | | HTTP://PBCGOV.COM/PAPA/ASPS/PROPERTYDETAIL/STRUCTURALDE | | TAIL.ASPX?ENTITY_ID=74434304150000021&OWNER_NAME=JEROME | | +GOLDEN+CENTER+FOR+BEHAVIORAL | | | | THIS WAS REQUESTED IN PREVIOUS REVIEWS. THIS IS | | REQUIRED TO ASSIST IN DETERMINING THE FOLLOWING: | | BUILDING COVERED UNDER THIS PERMIT (?BUILDING THREE? IS | | AN IDENTIFICATION USED BY THE OWNER, NOT CLEAR WHICH | | BUILDING THIS PERMIT IS FOR, NOT CLEAR HOW THIS NUMBER | | WAS ASSIGNED, WHETHER IT IS CONSISTENT WITH PAPA | | RECORDS), CONFIRM VALUE FBC 109, CONFIRM SCOPE AND | | NATURE OF WORK FBC 107. | | | | IF QUALIFIER HAS ISSUE WITH PROVIDING THIS INFORMATION, | | PLEASE CALL ME TO DISCUSS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-08-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-10 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-10 |
Time |
12:30 |
Sent To |
|
|
Notes |
2015-08-10 12:31:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC 1609 | | | | SEE PREVIOUS LIST. REVIEW CANNOT BE DONE WITHOUT THE | | INFORMATION IN ITEM #5. | | | | 5. PROVIDE A ROOF PLAN WHICH SHOWS REROOF AREAS. | | INCLUDE ROOF PITCH, ROOF DECK SUBSTRATE TYPE, AND MEAN | | ROOF HEIGHT. THE NOTE (3/12/18/12) IS NOT CLEAR. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-08-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-06 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-06 |
Time |
14:50 |
Sent To |
|
|
Notes |
2015-08-06 14:54:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC 1609 | | | | COMMENTS FROM PREVIOUS LIST; DISCUSSED WITH APPLICANT | | AT THE COUNTER. ONE SET WAS GIVEN (MARKED UP) TO | | APPLICANT. | | | | 1. FOR THE FLAT DECK, INDICATE WHICH APPROVED ASSEMBLY | | IS PROPOSED. | | | | 2ND REVIEW, RECOVER PAGES FROM THE EVALUATION REPORT | | WERE SUBMITTED. PROPOSED INSTALLATION IS A REROOF. | | ALSO, SHEETS WERE REDUCED (PRINTED HALF SIZE). PLEASE | | PRINT IN LANDSCAPE ORIENTATION SO THE PAGES ARE | | LEGIBLE. | | | | 2. FOR THE TILE, INDICATE METHOD OF FASTENING (ON THE | | ADHESIVE PRODUCT APPROVAL). | | | | 2ND REVIEW, PLEASE INDICATE WHICH OF THE THREE | | DIFFERENT INSTALLATION METHODS IS PROPOSED. | | | | 3. THE TILE DRAWING WAS PRINTED PORTRAIT ORIENTATION SO | | IS REDUCED AND NOT LEGIBLE. PROVIDE A LEGIBLE DRAWING | | (SHEET 1 OF 1, FL 17330). | | | | 4. OK - PROVISO, PROVIDE 2014 WHEN AVAILABLE FOR FOAM | | ADHESIVE. | | | | 5. PROVIDE A ROOF PLAN WHICH SHOWS REROOF AREAS. | | INCLUDE ROOF PITCH, ROOF DECK SUBSTRATE TYPE, AND MEAN | | ROOF HEIGHT. THE NOTE (3/12/18/12) IS NOT CLEAR. | | | | NOT PROVIDED. | | | | 6. OK | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-07-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-30 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-07-30 |
Time |
14:53 |
Sent To |
|
|
Notes |
2015-07-30 15:00:15 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC 1609 | | | | 1. FOR THE FLAT DECK, INDICATE WHICH APPROVED ASSEMBLY | | IS PROPOSED. | | | | 2. FOR THE TILE, INDICATE METHOD OF FASTENING (ON THE | | ADHESIVE PRODUCT APPROVAL). | | | | 3. THE TILE DRAWING WAS PRINTED PORTRAIT ORIENTATION SO | | IS REDUCED AND NOT LEGIBLE. PROVIDE A LEGIBLE DRAWING | | (SHEET 1 OF 1, FL 17330). | | | | 4. THE TILE, TILE ADHESIVE, TILE UNDERLAYMENT PRODUCT | | APPROVALS ARE EXPIRED (2010 RATHER THAN 2014). | | | | 5. PROVIDE A ROOF PLAN WHICH SHOWS REROOF AREAS. | | INCLUDE ROOF PITCH, ROOF DECK SUBSTRATE TYPE, AND MEAN | | ROOF HEIGHT. THE NOTE (3/12/18/12) IS NOT CLEAR. | | | | 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-08-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-18 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-18 |
Time |
09:15 |
Sent To |
|
|
Notes |
2015-08-18 09:15:12 | RESUB ROUTED TO SHILL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-31 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-07-20 |
Time |
11:54 |
Sent To |
|
|
Notes |
2015-07-23 11:55:03 | ROUTED TO BLDG MISC 1 |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
2 |
Status |
P |
Date |
2015-08-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-08-04 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-08-04 |
Time |
08:30 |
Sent To |
|
|
Notes |
2015-08-04 08:32:43 | THE TOTAL AMOUNT OF IMPROVEMENTS FOR ALL STRUCTURES | | (1,801,631) EQUAL 45% OF TOTAL VALUE OF ALL STRUCTURES | | ($4,013,513) | | | | THERE ARE FOUR BUILDINGS ON THIS PARCEL. IT IS | | IMPOSSIBLE TO ALLOCATE IMPROVEMENTS PER BUILDING. A | | HOLD HAS BEEN PLACED ON THIS BUILDING THAT ALL FUTURE | | PERMITS WILL BE ASSIGNED A BUILDING NUMBER. | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2015-07-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-31 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-07-30 |
Time |
15:01 |
Sent To |
|
|
Notes |
2015-07-31 11:46:15 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. IT APPEARS THAT THIS STRUCTURE IS LOCATED IN A | | SPECIAL HAZARD FLOOD AREA. CITY OF WEST PALM BEACH | | MUNICIPAL CODE 94-546(B), FBC 5TH EDITION EXISTING | | BUILDING 701.3. | | | | PLEASE PROVIDE AN ELEVATION CERTIFICATE FOR THIS | | STRUCTURE, IF AVAILABLE. THIS MAY BE SENT VIA EMAIL FOR | | PRELIMINARY REVIEW. | | | | IF THIS IS NOT AVAILABLE, AN ANALYSIS WILL BE DONE TO | | DETERMINE WHETHER OR NOT THIS CONSTITUTES A | | "SUBSTANTIAL IMPROVEMENT" (CUMULATIVE LIFETIME VALUE OF | | IMPROVEMENTS TO THE STRUCTURE > 50% STRUCTURE VALUE). | | | | IF AN ELEVATION CERTIFICATE IS AVAILABLE AND SHOWS THAT | | THIS STRUCTURE COMPLIES WITH ELEVATION REQUIREMENTS, | | THIS WILL BE PUT ON FILE AND FUTURE PERMITS | | APPLICATIONS WILL NOT BE REQUIRED TO SHOW COMPLIANCE | | UNTIL NEW MAPS ARE ADOPTED. | | | | AS THERE IS MORE THAN ONE STRUCTURE ON THIS PROPERTY, | | PLEASE PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF | | PROPOSED WORK. |
|
|