Plan Review Details - Permit 15070821
Plan Review Stops For Permit 15070821
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-27 Cont ID  
Sent By hmoser Date 2015-07-27 Time 13:42 Rev Time 0.00
Received By hmoser Date 2015-07-27 Time 10:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By hmoser Date 2015-07-27 Time 13:42 Rev Time 0.00
Received By hmoser Date 2015-07-27 Time 10:25 Sent To  
Notes
2015-07-27 13:42:10REVISION DENIED
 1) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL.
 2010 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE SIZE
 AND TYPE BOLTS USED 310.12 WIND RESISTANCE
 2010 FBC (M)
 3) PLEASE SUBMIT A DETAIL SHOWING A WAY TO
 ANCHOR THE CONDENSERS WITH OUT THE STRAP GOING
 OVER THE TOP OF THE CONDENSER
 4) REFER TO TABLE 305.4 PIPING SUPPORTS SPACINGS
 2010 FBC (M)
 5) FRESH AIR MUST BE 10 FT FROM LOT LINE SECTION 401.4
 #1 2010 FBC (M)
 6) PLEASE PROVIDE A DETAIL FROM THE ENGINEER ON
 HOW THE PIPING SUPPORT WILL BE ANCHORED TO THE
 ROOF. 301.12 WIND RESISTANCE 2010 FBC (M)
 7) REFER TO SECTION 305.2 MATERIALS
 2010 FBC (M)
 8) REFER TO SECTION 304.11 GUARDS
 (EQUIPMENT AND ROOF HATCH)
 2020 FBC (M)
 9) KITCHEN HOOD AND GREASE DUCT REQUIRE
 SEPARATE PERMITS.
 10) PLEASE IDENTIFY THE PAGES ON THE PLAN
 ( 1ST FLOOR 2 FLOOR ) SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved