2015-07-16 16:26:36 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15070620 |
| ADD: 701 S. OLIVE AVE. SUITE # 1023 |
| CONT: COMPLETE SOLUTIONS USA |
| TEL: ( 561)337-7793 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 7/16/2015 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES TO INSTALL FLOOR |
| SOUND PROOFING AND WOOD FLOORS. THE SUBMITTED TEST |
| REPORTS ARE FOR A 8 INCH SLAB, NOT VERIFIED, OVERLAID |
| WITH: |
| QUARRY TILE OVER PROFLEX 90 MEGA SOUND CONTROL MEMBRANE |
| UNDERLAYMENT. THERE IS A DISCREPANCY IN THE SUBMITTED |
| REPORT AND ACTUAL FINISH FLOOR. THE SUBMITTED REPORT IS |
| TESTED WITH QUARRY TILE NOT WOOD FLOORING. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| |
| 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |