Plan Review Stops For Permit 15070532 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-07-14 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-14 |
Time |
19:17 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-07-14 |
Time |
18:47 |
Sent To |
|
|
Notes |
2015-07-14 19:23:13 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR A SECOND REVIEW: | | 1. YOU SHALL SUBMIT LOAD CALCS. | | 2. INDICATE WHICH PANEL IS BEING REPLACED AND WITH WHAT | | IS IT BEING REPLACED. | | 3. YOU SHALL INCLUDE THE INTER-SYSTEM BONDING TERMINAL | | REQUIRED IN NEC250.94 | | 4. YOU SHALL CHECK AND VERIFY THAT ALL GROUNDING IS IN | | ACCORDANCES WITH MINIMUM CODE REQUIREMENTS. | | 5. IF NOT ALREADY IN PLACE, PER FBC-R 314, YOU SHALL | | COME INTO COMPLIANCE WITH SMOKE DETECTOR REQUIREMENTS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-14 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-14 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-07-14 19:31:36 | 7/14/15 - FAILED ELECTRICAL REVIEW AS NOTED. VICON | | ELECTRIC CONTACTED VIA PHONE. SENT TO SMALL DENIED BIN | | "V". MA |
|
|
|